background image

 

6

ELECTRICAL CONNECTIONS 

 

POWER WIRING 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Unit is factory wired for voltage shown on nameplate. 

 

Provide adequate fused disconnect switch within sight of unit, 
readily accessible but out of reach of children. 

 

Provision for locking switch open (off) is advisable to prevent 
power from being turned on while unit is installed or serviced. 

 

Disconnect switch, fuses and field wiring must comply with 
local codes. Size the wire as per electrical specification shown 
in CCAC Service Installer Blue Book. 

 

Use terminal marked ‘L’ and ‘N’ for 230V-1Ph-60Hz (or 230V-
3Ph-60Hz for 3phase) power supply. See respective wiring 
diagram shown on the preceding pages. 

 
 

CONTROL CIRCUIT WIRING 
 
 
 
 
 
 
 
 
 
 

 

For FCU model 42LX036-060,  Wall mounted Thermostat 
complete with 3 speed switch and CDU factory wired 
minimum 3/5 minutes time delay  is standard. Do not reset the 
delay time to lower setting.  

 

All 07KHP models are equipped with High Pressure switch to 
protect Compressor from overload condition. This is an auto –
reset type, no necessary changes or alteration is required in 
the field. 

 

Use terminal block marked ‘S1’ for Compressor signal control 

 

 
 
 

 

 
 

 

All final electrical connections must be made with a length of flexible 
conduit to minimize vibration and sound transmission to the building. 
 
Field wiring must comply with local and national fire, safety and 
electrical codes.   
 

 
SUPPLY VOLTAGE 

 
Operating voltage to unit must be within voltage range indicated in  
Table 1. On 3-phase units voltage imbalanced must be within 2%. Use 
the following formula to determine the percent voltage imbalance. In 
some areas where single phasing is more likely to occur, the electrical 
contractor/Installer is encourage to install a voltage phase protector to 
protect the unit from single phasing. 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

 

 
       This amount of phase imbalance is satisfactory as it is below 
        the maximum allowable 2%. 
 
       Operation on improper line voltage or excessive phase 
        imbalance constitutes abuse and may cause damage to  
        electrical components. 

 
 
 
 

OPERATION AND START-UP  

 

PRELIMINARY CHECKS 
 

Before operating the unit be sure the following are in order. 
 
1. 

All wiring connections are correct and tight. 

2. 

All barriers, covers and panels are in place. 

3. 

Electrical power supply conform to unit’s requirement. 

4. 

Water piping system are flushed and clean. 

5. 

Water system is chemically treated. 

6. 

Water inlet temperature is maintained around 29.5°C (85°F). 

7. 

All joints are leak tested and leak free. 

8. 

All valves are opened. 

 
 

TO START UNIT 
 

1. 

Field disconnect switch is closed. 

2. 

Set room temperature below ambient setting. 

3. 

Compressor will start once time delay has elapsed (3 or 5 minutes 
is standard depending on model) 

4. 

Operate unit for 30 minutes, then check system refrigerant charge. 

 

Consult the unit wiring diagram located on the inside of the 
access panel to ensure proper electrical hookup. Route power 
supply and signal wires through opening in unit’s side panel to 
their respective terminals.  

Check all electrical connections, 

including factory wiring within the unit and make sure all 
connections are tight. 

                                   

WARNING 

TO AVOID POSSIBLE INJURY OR DEATH DUE TO 
ELECTRICAL SHOCK, OPEN THE POWER SUPPLY 
DISCONNECT SWITCH (SWITCH-OFF) AND SECURE 
IT IN AN OPEN POSITION DURING INSTALLATION. 
USE LOCK-OUT AND TAG-OUT SECURITY LOCKS! 

                                   

CAUTION 

THE CONTROL VOLTAGE FROM THE FAN COIL UNIT 
MUST BE OF 230V. DO NOT CONNECT THE POWER 
SUPPLY TO THE

 

SIGNAL 

%Voltage Imbalance 
 
                  max voltage deviation from average voltage                  
= 100 x 
                                        average voltage 
 
           Example: Supply voltage is 460 - 3 - 60. 
  
                                                    AB = 452 v 
                                                    BC = 464 v 
                                                    AC = 455 v 
                                      
                                                                               452 + 464 + 455
                                              Average Voltage = 
                                                                                           3 
 
                                                                                1371 
                                                                          = 
                                                                                   3  
 
                                                                          = 457  
 
Determine maximum deviation from average voltage: 
(AB) 457 - 452 = 5 v 
(BC) 464 - 457 = 7 v 
(CA) 457 - 455 = 2 v 
Maximum deviation is 7 v. 
 
Determine percent voltage imbalance: 
 
                                                     7 
% Voltage Imbalance = 100 x 
                                                   457 
 
                                   = 1.53%  

Summary of Contents for 07KHP

Page 1: ...ny transmission of noise and vibration to the ceiling or walls Provide enough pipe flexibility before fixing unit to the structure Provide access panel in ceiling Make sure the panel is located near the unit for easy maintenance and servicing After the unit is installed and pipe work are completed be sure to insulate the unit s surroundings with acoustic treatment An acoustic type insulation can b...

Page 2: ...8 6 1 1 8 REFRIGERANT CONNECTIONS Liquid mm in Flare Type 6 35 6 35 9 52 3 8 9 52 3 8 9 52 3 8 S 15 8 5 8 High Press PSIG 426 7 320 20 CONTROL PRESSURESTAT SETTINGS Open Close pressure settings Low Press PSIG n a 27 4 67 7 POWER SOURCE V Ph Hz NOMINAL V 208 230 1 60 230 3 60 PERMISSIBLE MIN MAX VOLTAGE V 197 253 REFRIGERANT CONTROL DEVICE IN UNIT Capillary Tube Capillary Accurator RLA Rated Load A...

Page 3: ... supplied and field installed applicable for model 07KHP036 048 060 and 090 only Warranty will be voided if these models were not fitted with external filter drier in the field installation TUBING CONNECTIONS AND LEAK TEST Both suction and liquid are equipped with flare type connections except for Model 090 uses sweat connection Assemble flare joint by aligning tubing with machine surface of fitti...

Page 4: ...eak is detected the refrigerant should be recovered before repairing the leak This is in compliance with the Clean Air Act WATER PIPING Water inlet and outlet are equipped with 25 4mm or 1 FPT female pipe thread Make sure that internal water piping is clean Use correct size wrenches and proper sealing for water inlet and outlet connections Do not over tighten the connections Suspend or use vibrati...

Page 5: ...5 FIG 6 CEILING MOUNTED INSTALLATION FIG 7 FLOOR MOUNTED INSTALLATION ...

Page 6: ...balance is satisfactory as it is below the maximum allowable 2 Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components OPERATION AND START UP PRELIMINARY CHECKS Before operating the unit be sure the following are in order 1 All wiring connections are correct and tight 2 All barriers covers and panels are in place 3 Electrical ...

Page 7: ... maintenance LUBRICANT Compressor contains factory oil charge Replace oil when lost See table 3 for oil recharge and refer to Carrier Manual Chapter 1 page 1 21 for oil recharging procedure CLEANING HEAT EXCHANGER Use a tank with 5 phosphoric acid Pump the cleaning liquid through the plate heat exchanger at 1 5 times normal flow rate for optimum cleaning preferably in back flush mode Then rinse wi...

Page 8: ......

Page 9: ...1 1 22 2 23 3 24 4 12 5 6 7 7 8 9 4 11 1 12 8 14 4 16 1 17 8 19 4 20 6 22 2 23 3 25 15 5 3 9 5 6 6 7 8 3 10 11 7 13 3 15 16 7 18 3 19 4 21 1 22 2 23 9 18 3 3 3 5 8 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 1 22 8 21 1 7 5 6 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 7 23 9 3 3 5 6 7 8 3 10 11 7 13 3 15 6 17 2 18 9 20 6 26 7 2 8 4 4 6 7 8 3 10 11 7 13 9 15 6 17 2 19 4 29 4 4 4 6 1 8 3 10 6 12 2 14 4...

Page 10: ...10 FIG 8 WIRING DIAGRAM 07KHP012 FIG 9 WIRING DIAGRAM 07KHP018 024 ...

Page 11: ...11 FIG 10 WIRING DIAGRAM 07KHP040 050 FIG 11 WIRING DIAGRAM 07KHP060 ...

Page 12: ...12 FIG 12 WIRING DIAGRAM 07KHP090 FIG 13 RECOMMENDED SERVICE CLEARANCES ...

Page 13: ...H LOOSE LEADS AT COMPRESSOR COMPRESSOR STUCK COMPRESSOR POWER SUPPLY OPEN COMPRESSOR INTERNAL PROTECTION OPEN OVERCHARGED OR NONCONDENSABLES IN SYSTEM OPEN SHORTED OR GROUNDED COMPRESSOR MOTOR WINDING HIGH SUPERHEAT COMPRESSOR BEARINGS DEFECTIVE FAN CAPACITOR LINE VOLTAGE TOO HIGH OR LOW LOW REFRIGERANT CHARGED RESTRICTED DISCHARGE LINE INTERNAL PRESSURE RELIEF OPEN DEFECTIVE COMPRESSOR VALVES CON...

Page 14: ...inlupa City Tel No 63 2 850 1367 Fax No 63 2 809 9979 Website www carrier com ph Manufacturer reserve the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Form 07KHP 4IOM Replaces 07KHP 3IOM Concepcion Carrier Air conditioning Company ...

Reviews: