   TABLE 1   SPECIFICATIONS  

 

 

mm 

07KHP 

012 

07KHP 

018 

07KHP 

024 

07KHP 

040 

07KHP 

060 

07KHP 

090 

508.0 623.0 

H1 

355.0 549.0 

H2 

254.0 

H3 

179.0 

H4 

105.0 

569.0 

680.0 

W1 

329.0 

W2 

179.0 

W3 

130.0 

W4 

420.0 

 

 
 
 
 
 
 

 

 

 
 
 
 
 

 

 

 

 

07KHP 

MODEL 

013 

018 

024 

040 

060 

090 

 

RATED CAPACITY 

(TONS)

 

1.0  1.5  2.0  3.0 5.0 7.5 

 

CDU POWER INPUT 

(kW)

 1.08 

1.75 

2.22 

3.15 

5.15 

6.45 

 

NET WEIGHT 

(kg)

 

52  54  63  70 78 93 

 

Type

 R-22 

 

REFRIGERANT 

Charging method

 

By Superheat Method 

 

Type

 Rotary Scroll 

 

Compr. Model

 RH189NRAT

RH277NHDT 

PH39NPBT 

NH52NAHT 

ZR61KC-TF5 ZR81KC-TF5

 

RLA (A)

 4.8 

7.8 

12.6 

16.8 

20.7 

25.0 

 

LRA (A)

 35 

47 

66 

91 

139 

179 

 

COMPRESSORS 

Refill Oil Charged (lit. / oz)

 

0.52 / 17.6 

0.52 / 17.6 

0.90 / 30 

1.30 / 44 

1.83 / 62 

1.66 / 56 

 

Quantity

 1 

 

PLATE HEAT EXCHANGER 
 (STAINLESS STEEL) 

 

Water Inlet / Outlet ,mm (in.)

 

25.4 (1”)  FPT 

 

Suction,mm (in.) Flare Type

 

12.7 (1/2) 

12.7 (1/2) 

15.8 (5/8) 

15.8 (5/8) 

19.05 (3/4) 

S-28.6      
(1-1/8) 

 

REFRIGERANT CONNECTIONS 

Liquid, mm (in.) Flare Type

 

6.35 (¼)  

6.35 (¼) 

9.52 (3/8) 

9.52 (3/8) 

9.52 (3/8) 

S-15.8 (5/8)

 

High Press  (PSIG)

 

426 ± 7   /   320 ± 20 

 

CONTROL PRESSURESTAT SETTINGS 
(Open / Close pressure  settings) 

Low Press  (PSIG)

 

n.a. 

27 ± 4   /   67 ± 7 

 

POWER SOURCE (V-Ph-Hz) NOMINAL 

(V)

 

208/230 - 1 - 60 

230 - 3 - 60 

 

PERMISSIBLE  MIN-MAX VOLTAGE 

(V)

 

197 - 253 

 

REFRIGERANT CONTROL DEVICE IN UNIT 

Capillary Tube 

Capillary*/Accurator** 

RLA : Rated Load Amps                LRA : Locked Rotor Amps

  Data rated at 29.5° Water Out, 27°C/19°C Indoor Condition 
 
*   - Capillary tube located at FCU on model ASBFM0360-060 (Floor Standing) 
**  - Accurator is located at FCU on model 42AR0036-060 (Ceiling Type), 42GKX036-060(Cassette 
type), 42LX036-060(Ceiling-Ducted). 7.5TR system normally uses TXV metering device. 

Note: Refill oil charge is for service use after compressor has been drained. This value is different 
and less than Factory oil charged. Use only corresponding compressor maker approved specs. 
(S) under refrigerant connections section means Sweat Type connection. 
 
 

FIG. 2 DIMENSIONAL DRAWING  

FRONT VIEW

TOP VIEW

Summary of Contents for 07KHP

Page 1: ...ny transmission of noise and vibration to the ceiling or walls Provide enough pipe flexibility before fixing unit to the structure Provide access panel in ceiling Make sure the panel is located near the unit for easy maintenance and servicing After the unit is installed and pipe work are completed be sure to insulate the unit s surroundings with acoustic treatment An acoustic type insulation can b...

Page 2: ...8 6 1 1 8 REFRIGERANT CONNECTIONS Liquid mm in Flare Type 6 35 6 35 9 52 3 8 9 52 3 8 9 52 3 8 S 15 8 5 8 High Press PSIG 426 7 320 20 CONTROL PRESSURESTAT SETTINGS Open Close pressure settings Low Press PSIG n a 27 4 67 7 POWER SOURCE V Ph Hz NOMINAL V 208 230 1 60 230 3 60 PERMISSIBLE MIN MAX VOLTAGE V 197 253 REFRIGERANT CONTROL DEVICE IN UNIT Capillary Tube Capillary Accurator RLA Rated Load A...

Page 3: ... supplied and field installed applicable for model 07KHP036 048 060 and 090 only Warranty will be voided if these models were not fitted with external filter drier in the field installation TUBING CONNECTIONS AND LEAK TEST Both suction and liquid are equipped with flare type connections except for Model 090 uses sweat connection Assemble flare joint by aligning tubing with machine surface of fitti...

Page 4: ...eak is detected the refrigerant should be recovered before repairing the leak This is in compliance with the Clean Air Act WATER PIPING Water inlet and outlet are equipped with 25 4mm or 1 FPT female pipe thread Make sure that internal water piping is clean Use correct size wrenches and proper sealing for water inlet and outlet connections Do not over tighten the connections Suspend or use vibrati...

Page 5: ...5 FIG 6 CEILING MOUNTED INSTALLATION FIG 7 FLOOR MOUNTED INSTALLATION ...

Page 6: ...balance is satisfactory as it is below the maximum allowable 2 Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components OPERATION AND START UP PRELIMINARY CHECKS Before operating the unit be sure the following are in order 1 All wiring connections are correct and tight 2 All barriers covers and panels are in place 3 Electrical ...

Page 7: ... maintenance LUBRICANT Compressor contains factory oil charge Replace oil when lost See table 3 for oil recharge and refer to Carrier Manual Chapter 1 page 1 21 for oil recharging procedure CLEANING HEAT EXCHANGER Use a tank with 5 phosphoric acid Pump the cleaning liquid through the plate heat exchanger at 1 5 times normal flow rate for optimum cleaning preferably in back flush mode Then rinse wi...

Page 8: ......

Page 9: ...1 1 22 2 23 3 24 4 12 5 6 7 7 8 9 4 11 1 12 8 14 4 16 1 17 8 19 4 20 6 22 2 23 3 25 15 5 3 9 5 6 6 7 8 3 10 11 7 13 3 15 16 7 18 3 19 4 21 1 22 2 23 9 18 3 3 3 5 8 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 1 22 8 21 1 7 5 6 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 7 23 9 3 3 5 6 7 8 3 10 11 7 13 3 15 6 17 2 18 9 20 6 26 7 2 8 4 4 6 7 8 3 10 11 7 13 9 15 6 17 2 19 4 29 4 4 4 6 1 8 3 10 6 12 2 14 4...

Page 10: ...10 FIG 8 WIRING DIAGRAM 07KHP012 FIG 9 WIRING DIAGRAM 07KHP018 024 ...

Page 11: ...11 FIG 10 WIRING DIAGRAM 07KHP040 050 FIG 11 WIRING DIAGRAM 07KHP060 ...

Page 12: ...12 FIG 12 WIRING DIAGRAM 07KHP090 FIG 13 RECOMMENDED SERVICE CLEARANCES ...

Page 13: ...H LOOSE LEADS AT COMPRESSOR COMPRESSOR STUCK COMPRESSOR POWER SUPPLY OPEN COMPRESSOR INTERNAL PROTECTION OPEN OVERCHARGED OR NONCONDENSABLES IN SYSTEM OPEN SHORTED OR GROUNDED COMPRESSOR MOTOR WINDING HIGH SUPERHEAT COMPRESSOR BEARINGS DEFECTIVE FAN CAPACITOR LINE VOLTAGE TOO HIGH OR LOW LOW REFRIGERANT CHARGED RESTRICTED DISCHARGE LINE INTERNAL PRESSURE RELIEF OPEN DEFECTIVE COMPRESSOR VALVES CON...

Page 14: ...inlupa City Tel No 63 2 850 1367 Fax No 63 2 809 9979 Website www carrier com ph Manufacturer reserve the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Form 07KHP 4IOM Replaces 07KHP 3IOM Concepcion Carrier Air conditioning Company ...

Reviews: