CONTENTS 
 
Installation 

 

CONTENTS 

 
Installation   - - - - - - - - - - - - - - - - - - - - - - - - - - - - -  1 
 

 

 

 

 

 

 

Dimensional Drawing    - - - - - - - - - - - - - - - - - - - - -  2 

 

Specifications  - - - - - - - - - - - - - - - - - - - - - - - - - - -   2 

 

Piping Works   - - - - - - - - - - - - - - - - - - - - - - - - - - -  3 

 

 

Electrical Connections & Diagrams  - - - - - - - - - - -  6,9-13 

 

Operation and Start-Up   - - - - - - - - - - - - - - - - - - - -  6 

 

Refrigerant Charging  - - - - - - - - - - - - - - - - - - - - - -  7 

 

Maintenance  - - - - - - - - - - - - - - - - - - - - - - - - - - - -  7 

 

Trouble Shooting - - - - - - - - - - - - - - - - - - - - - - - - -   13 

 

INSTALLATION 

 

UNPACKING – 

Move unit to final location. Remove plastics wrap 

from unit being careful not to damage or cause scratch to the unit. 
Check the shipment against shipping list and remove unit protective 
covering. If the unit has been damaged, file  claim with transportation 
company and immediately notify Concepcion-Carrier or its authorized 
Dealer. 

 

CEILING MOUNTED INSTALLATION 

 

 

Select a suitable location for the unit. For example, use 
Kitchen or Bathroom ceiling spaces.    (See Fig. 6) 

 

 

Make sure that there is enough ceiling clearance between unit 
and slab. Check unit’s dimensional drawing. Clearance should 
also be allowed for ceiling acoustic treatment and piping. 

 

 

To design steel frame for unit’s base, do not place unit directly 
on the ceiling. Use a strong hanging suspension when 
installing the steel frame to slab. 

 

 

Ensure there is sufficient clearance between hanging rods 
and cabinet  access panels, so that service work can be 
carried easily. See the back page drawing for details. 

 

 

Place the unit onto the steel frame and make sure that the 
unit is leveled. Use vibration isolators between unit and steel 
frame. Do not use rubber blocks as isolators. 

 

 

Vibration isolators are also required for water pipe and 
refrigerant tube connections. Care should be taken with 
refrigerant piping to avoid any transmission of noise and 
vibration to the ceiling or walls. Provide enough pipe flexibility 
before fixing unit to the structure. 

 

 

Provide access panel in ceiling. Make sure the panel is 
located near the unit for easy maintenance and servicing.

 

 

 

After the unit is installed and pipe work are completed, be 
sure to insulate the unit’s surroundings with acoustic 
treatment. An acoustic type insulation can be used for 
additional sound reduction. 

 
 

 
 

 
 

 
 

 

 
 
 
 
 
CAUTION – 

Consult local building and National Electrical codes for 

special installation requirements. Check that electrical data on unit’s 
nameplate correspond to job site electrical supply. Check that field 
power supply is sized for the units and additional accessories like water 
pumps, cooling towers and indoor units. 
 

 

 

 
 

FLOOR MOUNTED INSTALLATION  

 

 

Select a suitable location for the unit. For example, use 
kitchen or balcony spaces.  (See Fig. 7) 

 

 

Make sure that enough space clearance for unit. Check unit’s 
dimensional drawing. Clearance should be also allowed for 
acoustic treatment and piping. 

 

 

To design a compartment complete with access panel or door 
for maintenance and servicing the unit. 

 

 

Use vibration isolators between the unit and floor. Do not 
place the unit directly onto the floor. 

 

 

After the unit is installed and pipe works are completed, be 
sure to insulate the unit’s internal compartment with acoustic 
treatment.

  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Concepcion 
Carrier 
Air conditioning 
Company 

 

07KHP WATER–COOLED

SPLIT CONDENSING UNIT

INSTALLATION MANUAL, START-UP & 
SERVICE INSTRUCTIONS 

PRIOR TO INSTALLATION OF THE 07KHP 
UNITS, REVIEW THE FOLLOWING IMPORTANT 
POINTS 

However, for applications such as hotel rooms, care needs to 
be taken to prevent break out noise from the immediate 
surroundings into the room below. 

Summary of Contents for 07KHP

Page 1: ...ny transmission of noise and vibration to the ceiling or walls Provide enough pipe flexibility before fixing unit to the structure Provide access panel in ceiling Make sure the panel is located near the unit for easy maintenance and servicing After the unit is installed and pipe work are completed be sure to insulate the unit s surroundings with acoustic treatment An acoustic type insulation can b...

Page 2: ...8 6 1 1 8 REFRIGERANT CONNECTIONS Liquid mm in Flare Type 6 35 6 35 9 52 3 8 9 52 3 8 9 52 3 8 S 15 8 5 8 High Press PSIG 426 7 320 20 CONTROL PRESSURESTAT SETTINGS Open Close pressure settings Low Press PSIG n a 27 4 67 7 POWER SOURCE V Ph Hz NOMINAL V 208 230 1 60 230 3 60 PERMISSIBLE MIN MAX VOLTAGE V 197 253 REFRIGERANT CONTROL DEVICE IN UNIT Capillary Tube Capillary Accurator RLA Rated Load A...

Page 3: ... supplied and field installed applicable for model 07KHP036 048 060 and 090 only Warranty will be voided if these models were not fitted with external filter drier in the field installation TUBING CONNECTIONS AND LEAK TEST Both suction and liquid are equipped with flare type connections except for Model 090 uses sweat connection Assemble flare joint by aligning tubing with machine surface of fitti...

Page 4: ...eak is detected the refrigerant should be recovered before repairing the leak This is in compliance with the Clean Air Act WATER PIPING Water inlet and outlet are equipped with 25 4mm or 1 FPT female pipe thread Make sure that internal water piping is clean Use correct size wrenches and proper sealing for water inlet and outlet connections Do not over tighten the connections Suspend or use vibrati...

Page 5: ...5 FIG 6 CEILING MOUNTED INSTALLATION FIG 7 FLOOR MOUNTED INSTALLATION ...

Page 6: ...balance is satisfactory as it is below the maximum allowable 2 Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components OPERATION AND START UP PRELIMINARY CHECKS Before operating the unit be sure the following are in order 1 All wiring connections are correct and tight 2 All barriers covers and panels are in place 3 Electrical ...

Page 7: ... maintenance LUBRICANT Compressor contains factory oil charge Replace oil when lost See table 3 for oil recharge and refer to Carrier Manual Chapter 1 page 1 21 for oil recharging procedure CLEANING HEAT EXCHANGER Use a tank with 5 phosphoric acid Pump the cleaning liquid through the plate heat exchanger at 1 5 times normal flow rate for optimum cleaning preferably in back flush mode Then rinse wi...

Page 8: ......

Page 9: ...1 1 22 2 23 3 24 4 12 5 6 7 7 8 9 4 11 1 12 8 14 4 16 1 17 8 19 4 20 6 22 2 23 3 25 15 5 3 9 5 6 6 7 8 3 10 11 7 13 3 15 16 7 18 3 19 4 21 1 22 2 23 9 18 3 3 3 5 8 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 1 22 8 21 1 7 5 6 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 7 23 9 3 3 5 6 7 8 3 10 11 7 13 3 15 6 17 2 18 9 20 6 26 7 2 8 4 4 6 7 8 3 10 11 7 13 9 15 6 17 2 19 4 29 4 4 4 6 1 8 3 10 6 12 2 14 4...

Page 10: ...10 FIG 8 WIRING DIAGRAM 07KHP012 FIG 9 WIRING DIAGRAM 07KHP018 024 ...

Page 11: ...11 FIG 10 WIRING DIAGRAM 07KHP040 050 FIG 11 WIRING DIAGRAM 07KHP060 ...

Page 12: ...12 FIG 12 WIRING DIAGRAM 07KHP090 FIG 13 RECOMMENDED SERVICE CLEARANCES ...

Page 13: ...H LOOSE LEADS AT COMPRESSOR COMPRESSOR STUCK COMPRESSOR POWER SUPPLY OPEN COMPRESSOR INTERNAL PROTECTION OPEN OVERCHARGED OR NONCONDENSABLES IN SYSTEM OPEN SHORTED OR GROUNDED COMPRESSOR MOTOR WINDING HIGH SUPERHEAT COMPRESSOR BEARINGS DEFECTIVE FAN CAPACITOR LINE VOLTAGE TOO HIGH OR LOW LOW REFRIGERANT CHARGED RESTRICTED DISCHARGE LINE INTERNAL PRESSURE RELIEF OPEN DEFECTIVE COMPRESSOR VALVES CON...

Page 14: ...inlupa City Tel No 63 2 850 1367 Fax No 63 2 809 9979 Website www carrier com ph Manufacturer reserve the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Form 07KHP 4IOM Replaces 07KHP 3IOM Concepcion Carrier Air conditioning Company ...