background image

31

1.

Compressors are shipped without service valves 
(unless specially ordered) and have blank-off pads 
bolted over the service valve openings. The suction 
and discharge service valves and the economizer 
adapter must be ordered for each compressor.

2.

Compressor part number on the nameplate will be 
the same as the package ordering number, EXCEPT 
the last digit of the part number on the compressor 
will be a zero (0) instead of a one to five (1 to 5).

3.

All Carlyle

®

 Compound Cooling compressor (16 to  

37 cfm)  are wired for XL (across the line) start only.

4.

All Carlyle Compound Cooling compressor

  

(50 to   

99 cfm)  are suitable for XL (across the line) or PW 
(part winding) start EXCEPT the 460-v in the 208/
230/460 triple voltage compressors. The distinct  
460-v model must be used for any 460-v part winding 
applications. Customer is required to hook up termi-
nal plate for applicable voltage. Wiring hook up dia-
grams are included in the compressor terminal box. 
Also a typical 230-v wiring schematic is included with 
this guide on page 27.
NOTE: These compressors will also operate at        
50 Hz.

5.

Carlyle Compound Cooling compressors:
a.

have an oil sight glass

b.

are dehydrated and have dry air holding charge 
(5 to 15 psi)

c.

16 to 37 cfm compressors oil level is 1/2 of a 
sight glass

d.

50 to 99 cfm compressors oil level is 1/8 to 3/8 of 
a sight glass

e.

refer to Carlyle Compound Cooling compressor 
model numbers for oil or oil-less compressors

f.

have pressure connections for oil protection

6.

Carlyle recommends but does not require cylinder 
head cooling fans for all Carlyle Compound Cooling 
compressor R-22 applications.

7.

All Carlyle Compound Cooling compressors (16 to  
37 cfm)  are provided with complete motor overcur-
rent and overtemperature protection, which complies 
with UL and NEC requirements for inherent motor 
protection. Primary motor protection is provided by 
current sensitive relays located inside the compres-
sor terminal box. Thermal protection is provided by 
an internal thermostat embedded in the motor wind-
ings. All Carlyle Compound Cooling compressor (16 
to 37 cfm) models are UL and CSA approved with   
R-22, R-404A, and R-507 refrigerants.

8.

The 50 to 99 cfm Carlyle Compound Cooling com-
pressor models are provided WITHOUT motor over-
current protection, which MUST be supplied by the 
customer. Calibrated circuit breakers and Furnas 
solid-state overload relays specifically selected for 
each motor and voltage are available and recom-
mended.

9.

See circuit breaker accessory selection. If OEM cus-
tomer selects alternate overcurrent protection, it 
must be approved by Carlyle Application Engineering 
Department. The use of authorized overcurrent pro-
tection is part of the basis of UL recognition. Selec-
tion of alternate overcurrent protection without 
Carlyle’s approval will VOID warranty.

10. All nine Carlyle Compound Cooling compressor mod-

els have a well in the cast iron bottom plate in which 
a crankcase heater can be inserted. A crankcase 
heater is recommended for use with all Carlyle Com-
pound Cooling compressor

 

models. All 180 watt 

insertion type crankcase heaters are required to use 
thermal grease provided in the accessory package 
(grease part number 38AQ680001).

11. All Carlyle Compound Cooling compressor models 

are provided with a temperature sensor installed in 
the high stage cylinder head to monitor the tempera-
ture of the discharge gas. If the discharge gas tem-
perature in the head exceeds the trip setting of 295 F 
(146.1 C), the sensor will open the control circuit and 
shut off the compressor.

12. All Carlyle Compound Cooling compressor models 

are now being shipped without oil.

Appendix

Summary of Contents for 06CC

Page 1: ...06CC CARLYLE COMPOUND COOLING COMPRESSOR APPLICATION GUIDE...

Page 2: ...ultiple Compressor System 20 1 17 Control Scheme 20 1 18 De Superheating Expansion Valves 20 1 19 Interstage Check Valves 20 1 20 Capacity Control 20 1 21 Low Stage Discharge Gas Temperatures 20 1 22...

Page 3: ...erant lines and therefore a smaller refrigerant charge Simple application of subcooling Eliminates compressor short cycling as capacity remains stable over a wide range of head pressures Can be used w...

Page 4: ...re and flow to the intermediate manifold 3 A tap off the main liquid line directly expands refrigerant at condensing pressure to interstage pressure in the subcooler 4 Liquid on the way to the evapora...

Page 5: ...Cooling Model 06CY Service Compressor 06C8 Compressor Special NOTE USE OF cfm AS MODEL SIZE DESIGNATION Carlyle uses the cfm designation in the model number to identify the compressor size The cfm val...

Page 6: ...2 78 26 02 0 59 on 8 88 11 38 Centers 1 3 8 ODS 16 90 8 26 7 8 ODS Dischage 1 3 8 ODS Suction 13 37 1 72 2X 0 5 11 37 0 57 9 88 15 98 11 97 1 17 1 625 Economizer Port 2X 5 16 18 UNC 2B 0 56 NOTE Dimen...

Page 7: ...S 7 38 12 78 26 05 0 59 on 8 88 11 38 Centers 17 67 8 64 1 5 8 ODS Suction 1 1 8 ODS Discharge 1 91 12 76 11 38 2X 0 50 0 95 12 23 16 41 1 02 1 625 Economizer Port 10 15 2X 5 16 18 UNC 2B 0 56 NOTE Di...

Page 8: ...8 Compressor Physical Dimensions cont NOTE Dimensions are in inches Fig 4 06CC550 665 675 899 Models...

Page 9: ...to Relieve Crankcase Pressure Suction Valve Location 1 4 NPT High Side Oil Safety Switch Connection Suction Manifold To Low Stage Cylinders 7 16 20 SAE Oil Drain Connection Adaptor Part No DE14CA126...

Page 10: ...onnection Factory Supplied Schrader Type Fitting Oil Level Sightglass Discharge Valve Location 7 16 20 SAE Oil Drain Connection Adapter Part No DE14CA126 1 4 NPT 2 Connections 1 Above Sightglass 1 Abo...

Page 11: ...request from Carlyle s Applications Engineering department R 22 Approximate Interstage Pressure 10 psig 0 7 bar with Subcooler Indicates vacuum Absolute pressure where 1 bar ATM Atmospheric Pressure...

Page 12: ...3 29 37 2 57 40 3 77 44 4 05 48 4 32 53 4 67 50 F 45 C 0 9 1 08 33 3 29 37 3 57 40 3 77 45 4 19 49 4 39 53 4 67 58 5 01 45 F 43 C 3 1 1 23 35 3 43 39 3 70 44 4 05 48 4 32 53 4 67 57 4 94 62 5 29 40 F...

Page 13: ...0 1 7 13 1 9 14 2 0 15 2 1 17 2 2 20 2 4 24 2 7 41 3 1 50 F 45 C 8 9 0 71 12 1 9 15 2 1 18 2 2 19 2 3 21 2 5 24 2 7 29 3 0 46 3 5 45 F 43 C 5 6 0 82 15 2 0 19 2 3 21 2 5 23 2 6 26 2 8 29 3 0 34 3 3 51...

Page 14: ...o 23 06CC337 06CY337 60 to 10 51 to 23 40 to 10 40 to 23 06CC550 See Note 2 06CY550 40 to 10 40 to 23 40 to 10 40 to 23 06CC665 06CY665 60 to 10 51 to 23 40 to 10 40 to 23 06CC675 06CY675 60 to 10 51...

Page 15: ...ferent efficiencies can differ up to 15 from data shown Allowable Operating Ranges COMPRESSOR INFORMATION RECOMMENDED CIRCUIT BREAKERS OVERLOAD INFORMATION 06CC Models Voltage HP See Note 1 See Note 2...

Page 16: ...istance Ohms 06CC016J101 D101 G101 6 25 5 575 208 230 460 10 8 27 0 13 5 6 9 17 3 8 7 40 100 50 3 3 0 54 2 1 HN69GZ032 HN69GZ024 HN69GZ014 8347A23 42 8347A23 63 8347A23 53 06CC017J101 D101 G101 6 25 5...

Page 17: ...ubcooler Selection Two stage systems have the inherent benefit of being able to utilize interstage subcooling and de superheating through the use of a subcooler The application of a liquid subcooler i...

Page 18: ...tor Solenoid Valve TXV Expansion Valve Evaporator Subcooler TXV Bulb TXV Bulb Suction Accumulator Required Condenser High Efficiency Oil Separator Required Oil Return to Crankcase Set for Pressure Equ...

Page 19: ...ration discharge temperature to 70 F Allowing saturated discharge tem peratures to fall below 70 F does not significantly affect energy usage is not recommended and may lead to increased valve stresse...

Page 20: ...to con trol discharge gas temperatures Liquid injection is accomplished through the use of Carlyle recommended de superheating expansion valves These valves are designed to operate only when the suct...

Page 21: ...ll Carlyle 06CC models are provided with connections for oil pressure safety switches All 06CC model com pressors are provided with connections for low oil pres sure protection Low oil pressure protec...

Page 22: ...06CC mod els This design reduces the amount of liquid injection required for motor cooling These manifolds act to effi ciently distribute cool refrigerant gas to the interstage connection points of a...

Page 23: ...e intermediate pressure may be calculated by taking the square root of the product of the suction and discharge pressure plus or minus ten psi P1 Suction Pressure PSIA P2 Discharge Pressure PSIA AIP A...

Page 24: ...for the interstage of the 06CC model compres sors Carlyle has implemented a design change that eliminates the need for these switches The 06CC mod els do not require this additional safety switch as...

Page 25: ...rminal box intended for overcurrent protection The 50 to 99 cfm model versions require the application of a Carlyle approved calibrated circuit breaker or a solid state over load relay The specific ca...

Page 26: ...verload Control Circuit Contactor No 1 L3 L2 L1 Customer wiring shown dotted Third overload required on some compressions Fig 12 Typical 06CC 16 to 37 cfm Installation Wiring 5 0 Compressor Wiring Typ...

Page 27: ...30 460V 300 Series Models 208 230 PW Start Only 9 Pin Term Pl 208 230 460V Models 460V XL Start CAUTION With 208 230 460 v 300 Series Models the 460 v cannot be wired for PW start Use distinct 460 v 6...

Page 28: ...s Terminal Parts Package NOTE Package contains 6 ring terminals to connect power wiring to compressor terminal studs plus 3 spare 2 hole jumper bars PACKAGE NO QTY CONN VOLTAGE 06DAA660115 1 ELEC 120...

Page 29: ...X10X7 8S 12 000 540 B8X20X7 8S 24 000 1080 B8X30X7 8S 36 000 1619 B8X40X7 8S 48 000 2159 B15X30X7 8S 60 000 2699 B25X30X1 1 8S 90 000 4048 MODEL NUMBER CAPACITY Btuh MASS FLOW lb hr B15X10X7 8S 12 000...

Page 30: ...57 0 79 1 92 B8X30 12 28 2 83 10 94 1 57 0 79 2 80 B8X40 12 28 2 83 17 01 1 57 0 79 3 69 B15X10 18 35 2 83 17 01 1 57 0 79 1 21 B15X20 18 35 2 83 17 01 1 57 0 79 2 09 B15X30 18 35 2 83 17 01 1 57 0 79...

Page 31: ...rent and overtemperature protection which complies with UL and NEC requirements for inherent motor protection Primary motor protection is provided by current sensitive relays located inside the compre...

Page 32: ...15 432 3274 In U S and Puerto Rico 1 800 GO CARLYLE 1 800 462 2759 In Canada 1 800 258 1123 In Mexico 001 800 GO CARLYLE 001 800 462 2759 Manufacturer reserves the right to discontinue or change at an...

Reviews: