15
1.3 Agency Approvals
All Carlyle 06CC models are UL (Underwriters Laborato-
ries) and CSA (Canadian Standards Association)
approved with R-22, R-407A, R-404A and R-507. The 50
to 99 cfm, 06CC models are supplied without included
motor protection. The 50 to 99 cfm, 06CC models require
the use of Carlyle-approved motor protection to maintain
UL approval. Approved motor protection devices / acces-
sories are shown in the Circuit Breaker Selection Table.
The use of alternate overcurrent protection devices must
be approved by the Carlyle Applications Engineering
department. The application of alternate overcurrent
devices without Carlyle's approval will VOID warranty.
UL File No. SA4936
All Carlyle 06CC models meet CE requirements for the
Low-Voltage and Machinery Directive.
1.4 Circuit Breaker Selection Table
06CC (50 to 99 cfm) 3 Phase Electrical Specifications
LEGEND
* Circuit breaker that requires “ring” terminal connection.
NOTES:
1.
Compressor must-trip (MT) amps and RLA values are maximum figures.
2.
LRA values for PW second winding = 1/2 the LRA XL value.
3.
3-Pole XL circuit breakers shown, other 3-Pole XL alternatives and 6-Pole
PW breakers available. Terminal lugs for circuit breakers available in pack-
age 06EA660152.
4.
Recommended RLA value shown is determined by: circuit breaker must trip
value ÷ 1.40. Use this recommended (and minimum) RLA value to deter-
mine name plate stamping, minimum contactor sizing and wire sizing. REC-
OMMENDED RLA FOR 06CC COMPRESSORS EQUALS: MUST-TRIP
(MT) OF CARLYLE APPROVED OVERCURRENT DEVICE BEING USED ÷
1.40.
5.
Compressor operating amps at any specific condition can only be deter-
mined from a performance curve.
6.
Ohm values for resistance are approximate and shown for reference pur-
poses only. Motors from different vendors and motors of different efficiencies
can differ up to 15% from data shown.
Allowable Operating Ranges
COMPRESSOR
INFORMATION
RECOMMENDED
CIRCUIT BREAKERS
OVERLOAD
INFORMATION
06CC
Models
Voltage
HP
See Note 1
See Note 2
Recom.
Part No.
Must
Hold
Amps
Must
Trip
Amps
LRA
See
Note 3
Recom.
RLA
Alternate
Part No.
Must
Hold
Amps
Must
Trip
Amps
LRA Part Number
Req.
Dial
Setting
Max.
Must
Trip
Amps
Max.
RLA
LRA
XL
LRA PW
1st
Winding
06CC550J
06CC550F
06CC550E
06CC550E
575
400/460
208/230
460
15
27
32
68
32
22
26
54
26
98
142
283
142
59
85
170
85
HH83XB438*
HH83XB414*
HH83XB455*
HH83XB414*
23
27
59
27
27
32
68
32
86
145
245
145
19.3
22.9
45.6
22.9
HH83XB689
HH83XB698
HH83XB697
HH83XB698
23
27
59
27
27
32
68
32
86
145
245
145
06EA907185
06EA907185
06EA907186
06EA907185
24
28
60
28
06CC665J
06CC665F
06CC665E
06CC665E
575
400/460
208/230
460
20
38
50
100
50
30
40
80
40
120
173
345
173
72
104
207
104
HH83XA461*
HH83XB437*
HH83XB376*
HH83XB437*
33
43
73
43
38
50
85
50
124
176
333
176
27.1
35.7
60.7
35.7
—
HH83XB606
—
HH83XB606
—
43
—
43
—
49
—
49
—
173
—
173
06EA907185
06EA907186
06EA907186
06EA907186
33
44
89
44
06CC675J
06CC675F
06CC675E
06CC675E
575
400/460
208/230
460
20
38
50
100
50
30
40
80
40
120
173
345
173
72
104
207
104
HH83X461
HH83XB437*
HH83XB378*
HH83XB437*
33
43
77
43
38
50
89
50
124
176
365
176
27.1
35.7
63.6
35.7
—
HH83XB606
—
HH83XB606
—
43
—
43
—
49
—
49
—
173
—
173
06EA907185
06EA907186
06EA907186
06EA907186
33
44
89
44
06CC899J
06CC899F
06CC899E
06CC899E
575
400/460
208/230
460
30
46
58
113
58
46
58
113
58
176
253
506
253
106
152
304
152
HH83XA430
HH83XB432*
HH83XC406
HH83XB432*
50
63
122
63
58
73
141
73
168
240
464
240
41.4
52.1
100.7
52.1
HH83XA469
HH83XB604
—
HH83XB604
46
63
—
63
53
73
—
73
164
240
—
240
06EA907186
06EA907186
06EA907187
06EA907186
51
65
125
65
LRA —
Locked Rotor Amps
MH
—
Must Hold Amps
MT
—
Must Trip Amps
PW
—
Part-Winding Start
RLA —
Rated Load Amps
XL
—
Across the Line Start
NOMINAL VOLTAGE
MAXIMUM
MINIMUM
208/230
254
187
460
529
414
575
661
518
400 (50 Hz)
460
342
200 (50 Hz)
230
180