8510234P03 © Danfoss Commercial Compressors 09/07
MPZ
compressors
are not designed for use
in mobile and explo-
sion-proof
applications.
Use of flammable refrige-
rant (e.g hydrocarbons) or
air is also strictly forbidden.
MPZ compressors must
only be used for their desi-
gned purpose(s) and within
their scope of application (re-
fer to "operating limits").
Consult Application guide-
lines and datasheet availa-
ble from cc.danfoss.com
Pressure tests must be
performed by qualified
personnel in accordance
with service Pressure (Ps)
printed on compressor na-
meplate. Max test pressure
shall never exceed 25 bar
(362 psig). For test pressure
use only nitrogen.
The rubber grommets
must be installed under the
compressor feet, as shown.
Tighten up until the flat
washer makes contact with
the steel mounting sleeve.
Recommended torque 15
Nm.
MPZ compressors are deli-
vered under nitrogen gas
pressure (between 0.3 and
0.7 bar) and hence cannot
be connected as is; please
refer to the "assembly"
sec-
tion for further details.
Under all circumstan-
ces, the EN378 (or other
applicable local safety
regulation) requirements
must be fulfilled.
Modifications or alte-
rations (such as welding
or brazing on the shell)
invalidate the user’s autho-
rization to operate the
equipment.
Never operate the com-
pressor without terminal
cover fitted.
The compressor must be
handled with caution in the
vertical position (maximum
offset from the vertical : 15°)
Do not leave compressor
open to atmosphere for ex-
tended period of time (less
than 1/2 h ).
Operating limits
°F
95
104
131
122
113
140
86
149
°C
35
40
55
50
45
60
30
65
Condensing temper
atur
e
Evaporating temperature
10
5
0
-5
-10
-15
-20
-25
-30
14
-5
-4
23
32
41
50
°F
-22
-13
°C
MPZ - R404A / R507A
RGT 20°C / 68°F
SH10K
Housing
Service
Pressure
Lubricant : Polyolester oil
Vol: 1.1 liter
Supply Voltage
Maximum current
Starting current
R404A/R507A
M
nameplate marKing
Earth M4-12
Knock out
Ø21mm
(0.83 in)
Hole Ø21mm (0.83 in)
C/T1
R/T3
S/T2
Power terminals 1/4" (6.35 mm) quick connect spade
connection (C/T1 - S/T2 - R/T3).
Cable gland
designed for
H07NRF cable
Internal
Ø
12 mm
terminal BOX
Installation and servicing of the compressor
by qualified personnel only. Follow these
instructions and sound refrigeration engi-
neering practice relating to installation, commis-
sioning, maintenance and service.
wiring diagrams
230 V
A
Thermostat
C
S
R
IOL
Single phase PSC
Single phase CSR
Three Phase
F1
CONTROL
CIRCUIT
F1
KA
KA
KA
KS
KS
KS
KA
KM
KM
TH
180 s
BP
HP
DGT
L1 L3 L2
Q1
F2
T1
T2
T3
M
230 V
Thermostat
BµF
Start Relay
5
2
1
15 kΩ -1 w
C
S
R
IOL
A
Discharge tube
ODF 1/2”
(12.7 mm)
Process tube
ODF 3/8” (9.5 mm)
Suction tube
ODF 3/4”
(19 mm)
Foot print: 7.5” (190 mm)
Bolt HM8x40
23 mm
(0.91 in)
15 mm
(0.59 in)
Ø 32 mm
(1.25 in)
Flat washer
Sleeve
Lock washer
InSTRuCTIonS