CARLO GAVAZZI RSWT Series Manual Download Page 22

22

Carlo Gavazzi LTD

 

RSWT

RSWT DS ENG

17/05/2018

Number of flashes

2

Alarm

Wrong phase sequence

Alarm description

If the connection to the soft starter is not done in the correct sequence (L1, 

L2, L3), the RSWT will trigger the wrong phase sequence alarm and the motor 

will not be started.

Alarm recovery period

N/A

Consecutive alarms for hard reset

1

Action to recover alarm

User intervention is required to change the wiring sequence to recover alarm.

Note: the phase sequence monitoring can be disabled. To disable the alarm, 

press the Test/Reset button for 10 seconds when the RSWT is in IDLE state. 

The yellow LED will turn ON.

ATTENTION: in this mode, if the wiring is not in the correct sequence, the mo-

tor will rotate in the reverse direction.

Troubleshooting

• 

Check that wiring on L1, L2, L3 is in the correct sequence.

• 

If you need to reverse the motor, make sure that the phase sequence LED 

is ON (phase sequence protection disabled).

Number of flashes

3

Alarm

Line voltage out of range

Alarm description

At every power-up the RSWT automatically detects the supply voltage level 

and determines whether it is working on a 220, 400, 480* or 600* V supply. 

The under- or over- voltage alarm level is then set at a level of -20% and + 

20% (from the measured supply voltage level) respectively.

If the supply voltage level is out of these limits for more than 5 seconds then 

the line voltage out of range alarm will be triggered.

* Applies to RSWT60 models.

Note: for RSWT60 over-voltage alarm level (for the case of a 600V supply) is 

675V (600V + 11%).

Alarm recovery period

5 minutes

(If manual reset mode is applied, alarm can be reset by pressing the Test/

Reset button).

Consecutive alarms for hard reset

4

Action to recover alarm

The alarm will self-recover (in auto-recovery mode) after 5 minutes from when 

the supply voltage is within limits.

Troubleshooting

• 

Check supply voltage level across L1, L2, L3 terminals.

• 

Make sure that you are not using a RSWT40 model on a supply voltage > 

440 VAC.

Number of flashes

4

Alarm

Phase loss (motor side)

Alarm description

If any of the phases on the load (motor) side becomes open the RSWT will 

trip after 5 seconds to protect the motor from running/ starting on 2 phases.

Note: this alarm will also be triggered when a current unbalance of > 20% is 

detected on any of the three line currents for a minimum of 5 secs. Addition-

ally if a SCR and/or bypass relay is open (damaged) the same alarm will be 

triggered.

Alarm recovery period

5 minutes

(If manual reset mode is applied, alarm can be reset by pressing the Test/

Reset button).

Consecutive alarms for hard reset

4

Action to recover alarm

Check connections on the output side of the soft starter and on the motor 

terminals. The alarm will self-recover (in Auto-recovery mode) after 5 minutes.

Troubleshooting

• 

Check for any loose connections on the T1, T2, T3 side of the soft starter.

• 

Check for any loose connections on the motor terminals.

• 

Check motor windings.

Summary of Contents for RSWT Series

Page 1: ...ousing 32 55 Arms in 75 mm wide housing 70 90 Arms in 120 mm wide housing Integrated protection Diagnostic functions provide additional protection RSWT is also equipped with an overload protection Cla...

Page 2: ...nal current 40 C 16 16 Arms 25 25 Arms 32 32 Arms 37 37 Arms 45 45 Arms 55 55 Arms 70 70 Arms 90 90 Arms E0 110 400 VAC 10 15 control voltage Uc Supply voltage internally supplied F0 24 VAC DC 10 10 c...

Page 3: ...rms RSWT4055E0V111 RSWT4055F0V111 RSWT6055GGV111 RSWT6055FFV111 70 Arms RSWT4070E0V111 RSWT4070F0V111 RSWT6070GGV111 RSWT6070FFV111 90 Arms RSWT4090E0V111 RSWT4090F0V111 RSWT6090GGV111 RSWT6090FFV111...

Page 4: ...Fans Centrifugal fan 0 5m diameter 10 5 to 10 0 1 x Motor FLC Centrifugal fan 0 5m diameter 20 10 to 20 0 1 2 x Motor FLC Vacuum blowers 10 5 to 10 0 1 x Motor FLC Note For Trip class 20 applications...

Page 5: ...g 575V Trip class 5 Trip class 10 Trip class 20 2 7 1 5 2 RSWT6012 RSWT6012 RSWT6012 3 9 2 2 3 RSWT6012 RSWT6012 RSWT6012 5 3 4 RSWT6012 RSWT6012 RSWT6012 6 3 5 RSWT6012 RSWT6012 RSWT6012 9 5 7 5 RSWT...

Page 6: ...Idle state Set alarm recovery mode press for 5 sec when RSWT is in Idle state Reset alarms press for 1sec when RSWT is in alarm mode and alarm mode is Manual E1 LED indicators Supply Indicates that th...

Page 7: ...ation settings section on page 3 in case of Trip Class 20 loads Step 4 Set the alarm recovery mode Make sure the RSWT is in idle mode Green LED ON To set the alarm recovery to auto press the Test Rese...

Page 8: ...l be optimised during the first start and the RSWT might trigger an alarm If this happens fol lowing the alarm recovery period the RSWT will update the self learned start parameters and perform anothe...

Page 9: ...2018 Features General RSWT 45mm RSWT 75mm RSWT 120mm Material PA66 Assembly DIN or panel Protection grade IP20 Weight 0 5 to 0 85 Kg About 2 3 Kg About 3 5 Kg Overvoltage category Cat III Fig 1 RSWT 4...

Page 10: ...10 Carlo Gavazzi LTD RSWT RSWT DS ENG 17 05 2018 Fig 3 RSWT 75mm 32 Arms 55 Arms Fig 4 RSWT 120mm 70 Arms 90 Arms...

Page 11: ...87 440 VACrms 187 660 VACrms Supply current at idle 30 mArms Blocking voltage 1200 Vp 1600 Vp Rated AC frequency 50 60 Hz 10 Rated insulation voltage 630 VAC 690 VAC Dielectric withstand voltage Suppl...

Page 12: ...Criteria 2 Performance Criteria 2 Conducted Radio Frequency Immunity 10V m 0 15 80 MHz IEC EN 61000 4 6 Performance Criteria 1 Electrical Surge Immunity Output line to line 1kV Output line to earth 2k...

Page 13: ...0 4 3 mA 0 4 1 mA Input to output response time Mains supply already present 300 msec Input to output response time Mains supply applied with control 2 5 sec 2 sec Integrated varistor Yes Note 1 For...

Page 14: ...AAC RSWT 45 RSWT 55 RSWT 70 RSWT 90 Overload cycle acc to EN IEC 60947 4 2 40 C surrounding temperature RSWT40 AC53b 3 5 6 174 RSWT60 AC53b 4 6 174 AC53b 3 12 168 AC53b 4 6 174 Maximum number of star...

Page 15: ...C 30 VDC Rated insulation voltage 250 VAC Dielectric withstand voltage Coil to contacts 2 5 kV Overvoltage category II Type of control circuit Electromechanical relay Number of contacts Alarm and bypa...

Page 16: ...30 HP 30 kW 40 HP 45 kW 50 HP RSWT 70 70 Arms 20 kW 25 HP 37 kW 40 HP 45 kW 50 HP 55 kW 60 HP RSWT 90 90 Arms 22 kW 30 HP 45 kW 50 HP 55 kW 60 HP 75 kW 75 HP Ratings kW rating according to IEC EN 6094...

Page 17: ...ply voltage Control voltage Supply voltage ST Control voltage Control voltage 11 12 Alarm indication normally closed NC 11 14 Alarm indication normally open NO 21 22 Top of ramp indication normally cl...

Page 18: ...18 Carlo Gavazzi LTD RSWT RSWT DS ENG 17 05 2018 Wiring diagrams Valid up to 400 VAC RSWT40 E0V RSWT E0V RSWT40 F0V...

Page 19: ...applied the Line voltage out of range alarm will be triggered The alarm will automatically recover if L1 L2 L3 are within operational range for 1 sec on power up only Note 1 For RSWT60 FFV models appl...

Page 20: ...tors A1 A2 Acc to EN60998 RSWT 12 to RSWT 25 RSWT 32 to RSWT 90 Flexible 0 5 1 5 mm2 Rigid solid or stranded 0 5 2 5 mm2 Flexible with end sleeve ferrule 0 5 1 5 mm2 UL cUL rated data Rigid solid or s...

Page 21: ...te Supply green LED Relay contact position RSWT 45 mm RSWT 75 mm RSWT 120 mm Alarm 11 12 Bypass 21 24 Alarm 11 12 14 Bypass 21 22 24 Run 31 34 Idle ON Closed Open 11 12 21 22 Open Ramping ON Closed Op...

Page 22: ...en the line voltage out of range alarm will be triggered Applies to RSWT60 models Note for RSWT60 over voltage alarm level for the case of a 600V supply is 675V 600V 11 Alarm recovery period 5 minutes...

Page 23: ...cutive alarms for hard reset 4 Action to recover alarm The alarm will self recover in Auto recovery mode the recovery period will depend on the cooling time required by RSWT The higher the surrounding...

Page 24: ...ee phases and if there is a difference of more than 20 for 5sec between any of the phases the RSWT will trigger the voltage unbalance alarm Alarm recovery period 5 minutes Consecutive alarms for hard...

Page 25: ...rcuitry the Red LED will remain continuously ON Alarm recovery period Consecutive alarms for hard reset 1 Action to recover alarm Note this alarm is not resettable and it is suggested to replace the u...

Page 26: ...des the conductors from the voltage source to the manual manual starter from the manual motor starter to the soft starter and from the soft starter to the load Protection Co ordination Type 1 vs Type...

Page 27: ...HP RSWT4055 55 AAC 15 kW 20 HP 30 kW 30 HP RSWT4070 70 AAC 20 kW 25 HP 37 kW 40 HP RSWT4090 90 AAC 22 kW 30 HP 45 kW 50 HP RSWT6012 12 AAC 3 kW 3 HP 5 5 kW 5 HP 5 5 kW 7 5 HP 9 kW 10 HP RSWT6016 16 A...

Reviews: