Wiring diagrams
IMPORTANT: L1, L2, L3 should already be connected when A1, A2 and ST signals are applied. A minimum delay of 200ms should
be allowed between switching of L1, L2, L3 and A1, A2 and ST respectively. If L1, L2 and L3 are not present, when A1, A2 is applied
the “Line voltage out of range alarm will be triggered”. The alarm will automatically recover if L1, L2, L3 are within operational range
for 1 sec (on power up only).
Note 1: For RSWT60..FFV... models apply 24VAC/DC across A1, A2 terminals. For RSWT60..GGV... models apply 100 - 240VAC across A1, A2 terminals.
Note 2: For DC supply, connect A1 to the positive (+) and A2 to the negative (-) terminal of the power supply.
Note 3: ST terminal has to be at the same potential of A2 (refer to wiring diagrams)
RSWT60...FFV.. / RSWT60...GG..