RSWT
RSWT DS ENG
17/05/2018
Outputs
RSWT..12….
RSWT..16….
RSWT..25….
RSWT..32….
RSWT..37….
Overload cycle acc.
to EN/IEC 60947-4-2
@ 40°C surrounding temperature
AC53b:4-6:174
AC53b:
3.5-5:175
AC53b:
4 - 6:174
RSWT40:
AC53b:
3.5 - 6: 174
RSWT60:
AC53b:
4 - 6: 174
Maximum number of starts per hour
@ 40°C @ rated overload cycle
20
20
Rated operational current @ 40°C
12 AAC
16 AAC
25 AAC
32 AAC
37 AAC
Rated operational current @ 50°C
11 AAC
15 AAC
23 AAC
29 AAC
34 AAC
Rated operational current @ 60°C
10 AAC
13 AAC
21 AAC
27 AAC
31 AAC
Minimum load current
2 AAC
2 AAC
2 AAC
5 AAC
5 AAC
RSWT..45….
RSWT..55….
RSWT..70….
RSWT..90….
Overload cycle acc.
to EN/IEC 60947-4-2
@ 40°C surrounding temperature
RSWT40:
AC53b: 3.5 - 6: 174
RSWT60:
AC53b: 4 - 6: 174
AC53b:
3 - 12: 168
AC53b: 4-6: 174
Maximum number of starts per hour
@ 40°C @ rated overload cycle
20
Rated operational current @ 40°C
45 AAC
55 AAC
70 AAC
90 AAC
Rated operational current @ 50°C
41 AAC
50 AAC
64 AAC
83 AAC
Rated operational current @ 60°C
37 AAC
46 AAC
59 AAC
76 AAC
Minimum load current
5 AAC
5AAC
5 AAC
5 AAC
Note: The overload cycle describes the switching capability of the soft starter at a surrounding temperature
of 40ºC as described in EN/IEC 60947-4-2. An overload cycle AC53b:4-6:174 means that the soft starter can
handle a starting current of 4x Ie for 6 seconds followed by an OFF time of 174 seconds.