18
Essential information
EM530/EM540 - User manual | CARLO GAVAZZI Controls SpA
Essential information
Alarms
Introduction
EM500 manages a measured variable alarm. To set the alarm, define:
• the variable to be monitored (
VARIABLE
)
• alarm activation threshold value (
SET POINT 1
)
• alarm deactivation threshold value (
SET POINT 2
)
• alarm activation delay (
ACTIVATION
DELAY
)
Variables
The unit can monitor one of the following variables:
• system active power
• system apparent power
• system reactive power
• system power factor
•
phase-neutral voltage (OR logic)
•
phase-phase voltage (OR logic)
•
current (OR logic)
Note:
if you select a current or a voltage, the analyzer simultaneously monitors all the phases available in the set measurement
system and triggers the alarm when at least one of the phases is in alarm (OR logic)
Alarm types
Up alarm (Set point 1 ≥ Set point 2)
The alarm activates when the monitored variable exceeds the Set 1 value for a time equal to the activation delay (Delay) and
deactivates when the values drops below Set 2.
(s)
ON
Set 1
Set 2
Delay
Down alarm (Set point 1 < Set point 2)
The alarm activates when the monitored variable drops below the Set 1 value for a time equal to the activation delay (Delay) and
deactivates when it exceeds Set 2.
(s)
ON
Set 2
Set 1
Delay
Summary of Contents for EM530DINAV23XM1PFA
Page 1: ...EM530 EM540 Energy analyzer for three phase and two phase systems USER MANUAL...
Page 25: ...EM530 EM540 Analizzatore di energia per sistemi trifase e bifase MANUALE D USO...
Page 49: ...EM530 EM540 Energieanalysator f r Dreiphasen und Zweiphasensysteme BETRIEBSANLEITUNG...
Page 73: ...EM530 EM540 Analyseur d nergie pour syst mes bi et triphas s MANUEL D EMPLOI...
Page 97: ...EM530 EM540 Analizador de energ a para sistemas trif sicos y bif sicos MANUAL DE USUARIO...
Page 121: ...EM530 EM540 Energianalysator til to og trefasede systemer BRUGERMANUAL...
Page 145: ...EM530 EM540...
Page 153: ...9 EM530 EM540 CARLO GAVAZZI Controls SpA 3Pn PF 0 7 L PF 0 96 C UCS MENU INFO TERMINAL...
Page 154: ...10 EM530 EM540 EM530 EM540 CARLO GAVAZZI Controls SpA EM530 EM540 SETTINGS INFO RESET...
Page 164: ...20 EM530 EM540 CARLO GAVAZZI Controls SpA RESET RESET QUICK SET UP MID CT CT...