Fault History
The 60200FR stores information from the last 32 cycles in
which a fault condition occurred. To Enter the Fault History
, simultaneously press and hold the
H
and
E
buttons for 2
seconds. The display below will appear –
Press the
E
button to scroll through the history of fault
conditions. Fault 1 is the most recent cycle in which a fault
occurred. To view faults experienced in earlier run cycles,
continue to press the
E
button. The control will display Fault
2 followed by Fault 3, etc.
To view the details of any fault (ex. Fault 1 in the screen
above), press the
H
button to see the Fault Message.
Press the
H
button again to determine how many cycles ago
the fault occurred.
Press the
H
button again to determine if the fault resulted in a
lockout or a recycle.
Press the
H
button again to examine the Microamps at the
time of the fault.
View 13 Faults
To Exit Hold
Total History
To Exit Hold
Carlin Combustion Technology, Inc.
MN60200FR1 070319
Fault 1 Message
No Flame Check Vlv
Fault 1
X X X X cycles ago
Fault 1 Result
Lockout
Fault 1
0.1 uAmps
Continue pressing the
H
button to examine the following
information recorded during the fault cycle.
• Line Voltage
• Recycle (Yes or No)
• Motor Amps (OK or Low)
• Burn Time
• Ignitor Amps (OK or Low)
• Flame Delay
• Valve Amps (OK or Low)
On any fault detail screen listed above, the
E
button can be
pressed to view the same data in the previous fault cycle. For
example, if in Fault 1 (the most recent fault), the Ignitor Amps
were low, by pressing the
E
button, the Ignitor Amps in Fault
2 (the previous fault cycle) will be displayed.
To Exit Fault History: Press and hold the
F
/
ESCAPE but-
ton for 3 seconds at any time.
Total/Run History
In addition to the Fault History (left),the 60200FR also logs the
total run history of the control. To enter this menu, simultane-
ously press the
E
and
F
buttons for 3 seconds. The display
below will appear.
To Exit Total History: Press and hold the / ESCAPE but-
ton for 3 seconds at any time.
Press
H
button to scroll through the history which includes:
• Total On Time
• Max Line Volts
• Total Burn Time
• Min Line Volts
• Total Burner Run Cycles
• Total Recycles
• Faults Cleared (cycles ago)
Fault 1 Details
View Fault 2
PRESS THE BUTTON TO VIEW NEXT FAULT
FAULT 1
FAULT 2
FAULT 3
FAULT 4
FAULT 5
PRESS THE
BUTTONS
TO
VIEW
FAULT
DETAILS
Message
No Flame ck vlv No Flame ck MTR
No Flame ck IGN
No Flame ck vlv
No Flame ck vlv
Cycles Ago
2
3
4
5
6
Result
Lockout
Lockout
Lockout
Lockout
Lockout
µAmps
0.1
0.1
0.1
0.1
0.1
Line Volts
114
114
114
114
114
Motor Amps
OK
Low
OK
OK
OK
Ignitor Amps
OK
OK
Low
OK
OK
Valve Amps
Low
OK
OK
Low
Low
Recycle Y/N
No
No
No
No
No
Burn Time
5 sec
5 sec
5 sec
5 sec
5 sec
Flame Delay
4 sec
4 sec
4 sec
4 sec
4 sec
F A U L T
H I S T O R Y
NOTE: Fault information in chart
is representation only.
Fault 1
Ignitor Amps Low
Fault 2
Ignitor Amps OK