5
Carlin Combustion Technology, Inc.
MN60200FR1 070319
Shaded box = default setting.
*
* MA Code (“N” models) are non-recycling and will lock out on flame failure.
**Changing this setting to ‘Yes’, with limits powered will exit Settings mode and result in immediate ‘Call For Heat’.
*
†
If flame is sensed during Pre-Purge, control will lockout immediately (except when Pre-Purge is set to 0 seconds).
A V A I L A B L E S E T T I N G S
Setup Menu Definitions
•
Pre-Purge: Time period motor and ignitor are on prior to Trial
for Ignition.
Note: If flame is sensed during Pre-Purge, control
will lockout immediately (except when Pre-Purge is set to 0 or 3
seconds).
•
Trial for Ignition: Flame-establishing period during ignition.
•
Post-Purge: Time period the motor is on after the Call for Heat is
satisfied to allow for evacuation of combustion gases. A call for
heat during Post-Purge will result in a recycle.
•
Allowed Recycles: Number of Recycles allowed during a single
Call for Heat prior to lockout.
•
TT Jumpered Internal: Allows TT to be “jumpered” by software
program.
•
Clear Fault History: Allows all prior burner fault conditions stored
in control to be cleared.
•
Restore Factory Defaults: Allows all factory defaults to be
restored in control (refer to settings shaded in gray in the table
above). Will reset and reboot control .
PRESS THE BUTTON TO VIEW DIFFERENT SETTING MODES
Pre -Purge
Trial for
Ignition
Post-Purge
Allowed
Recycles
TT
Jumpered
Internal**
Clear Fault
History
Restore
Factory
Defaults
PRESS THE
BUTTONS
TO
CHANGE
SETTINGS
0 Sec
†
4 Sec
0 Sec
None*
Yes
Yes
Yes
10 Sec
6 Sec
10 Sec
1
No
No
No
30 Sec
15 Sec
3
90 Sec
30 Sec
60 Sec
2 min
SETTING
MODE
OPTIONS