Carlin 60200FR Installation And Operating Instructions Manual Download Page 5

5

Carlin Combustion Technology, Inc.

MN60200FR1  070319

Shaded box = default setting.

*

* MA Code (“N” models) are non-recycling and will lock out on flame failure.

**Changing this setting to ‘Yes’, with limits powered will exit Settings mode and result in immediate ‘Call For Heat’. 

*

†  

If flame is sensed during Pre-Purge, control will lockout immediately (except when Pre-Purge is set to 0 seconds). 

A V A I L A B L E   S E T T I N G S

Setup Menu Definitions

   Pre-Purge:  Time period motor and ignitor are on prior to Trial 

for Ignition. 

Note: If flame is sensed during Pre-Purge, control 

will lockout immediately (except when Pre-Purge is set to 0 or 3 

seconds).

 

• 

Trial for Ignition: Flame-establishing period during ignition. 

   Post-Purge:  Time period the motor is on after the Call for Heat is 

satisfied to allow for evacuation of combustion gases. A call for 

heat during Post-Purge will result in a recycle. 

•  

Allowed Recycles: Number of Recycles allowed during a single 

Call for Heat prior to lockout.

•  

TT Jumpered Internal: Allows TT to be “jumpered” by software 

program.

• 

 Clear Fault History: Allows all prior burner fault conditions stored 

in control to be cleared.

• 

 Restore Factory Defaults: Allows all factory defaults to be 

restored in control (refer to settings shaded in gray in the table 

above). Will reset and reboot control .

  PRESS THE          BUTTON TO VIEW DIFFERENT SETTING MODES

Pre -Purge

Trial for

Ignition

Post-Purge

Allowed

Recycles

TT

Jumpered

Internal**

Clear Fault

History

Restore

Factory

Defaults

PRESS THE

BUTTONS

TO

CHANGE

SETTINGS

   0 Sec

4 Sec

0 Sec

None*

Yes

Yes

Yes

10 Sec

6 Sec

10 Sec

1

No

No

No

30 Sec

15 Sec

3

90 Sec

30 Sec

60 Sec

2 min

SETTING

MODE

OPTIONS

Summary of Contents for 60200FR

Page 1: ...ht 2019 Carlin Combustion Technology Inc Carlin Combustion Technology Inc On Board LCD Screen Fully Programmable Settings 32 Cycle Fault History Alarm Contacts Serviceman Reset Protection Blocked Vent...

Page 2: ...ection monitoring or other precautions are recommended for unattended dwellings in climates subject to sustain below freezing temperatures 7 Warning All work must be performed by a qualified and licen...

Page 3: ...3 Carlin Combustion Technology Inc MN60200FR1 070319 Wiring Commercial Gas Train 120V EZGas Pro 24V EZGas 120V Wiring must comply with local and national electrical codes and with the wiring diagram...

Page 4: ...s displayed on the screen press the E ENTER button The display will briefly indicate that the new setting has been Entered and the new setting will replace the previous setting on the second line of t...

Page 5: ...d the motor is on after the Call for Heat is satisfied to allow for evacuation of combustion gases A call for heat during Post Purge will result in a recycle Allowed Recycles Number of Recycles allowe...

Page 6: ...icates that the ignitor is energized flashes if ignitor not detected VALVE Indicates that the gas valve is energized on entry to pump prime will flash if not detected Operating Sequence With power to...

Page 7: ...ove the E button can be pressed to view the same data in the previous fault cycle For example if in Fault 1 the most recent fault the Ignitor Amps were low by pressing the E button the Ignitor Amps in...

Page 8: ...unless the Allowed Recycles is set to None in the Set up Menu A Recycle results in the burner shutting down for 60 seconds then resuming operation in Standby if there is no Call for Heat or initiatin...

Reviews: