Status Icons

Status Icons will appear at the top of the 60200FR display to indicate the control’s current operating condition.

POWER 

Indicates that the control is powered (flashes if voltage is too low or too high)

HV LIM 

Indicates that the burner limit circuit is powered.

TT 

 Displayed when the TT terminals are physically jumpered, jumpered in the set-up menu, or when thermostat  

is calling for heat.

BV 

 Monitors the BV contacts where a Blocked Vent Switch (Spill Switch) is connected. (Flashes if the Spill Switch 

contacts are open – indicating that the vent is blocked). See Blocked Vent Operation below for more information.

FLAME 

Indicates the control is sensing flame 

FAULT 

Flashes in unison with other status icons indicating a problem exists in that area

MOTOR 

Indicates that the motor is energized (flashes if motor not detected)

IGNITOR  Indicates that the ignitor is energized (flashes if ignitor not detected)
VALVE 

Indicates that the gas valve is energized (on entry to pump prime will flash if not detected)

Operating Sequence

With power to the control and the gas valve open, set 

thermostat (and limit) to call for heat. 

NOTE: The thermostat 

circuit must be closed and power must be coming to black 

wire from limit circuit.
During

 Pre-Purge, the motor starts.

Following 

Pre-Purge, the control advances to a  

3 second

 Pre-Ignition

 
During 

Pre-Ignition, the ignitor turns on and enters Trial for 

Ignition.

 

During 

Trial for Ignition, the gas valve opens. When flame is 

detected, the screen will briefly display “Flame Detected” and 

then procedes to 

Burner Running 

When the Call for Heat ends (or a limit control interrupts the 

burner circuit), the gas valve will turn off. The motor remains 

on for the 

Post-Purge period. When the Post-Purge timer 

expires, the control returns to 

Standby mode awaiting the 

next call for heat.

Pre-Purge 

 

X X  Sec

Pre-Ignition 

 

X X  Sec

Trial for Ign 

 

X X  Sec

Post-Purge 

 

X X  Sec

Standby  

5 9  Sec

No Call for Heat

Burner Running 

 

5 9  Sec

Summary of Contents for 60200FR

Page 1: ...ht 2019 Carlin Combustion Technology Inc Carlin Combustion Technology Inc On Board LCD Screen Fully Programmable Settings 32 Cycle Fault History Alarm Contacts Serviceman Reset Protection Blocked Vent...

Page 2: ...ection monitoring or other precautions are recommended for unattended dwellings in climates subject to sustain below freezing temperatures 7 Warning All work must be performed by a qualified and licen...

Page 3: ...3 Carlin Combustion Technology Inc MN60200FR1 070319 Wiring Commercial Gas Train 120V EZGas Pro 24V EZGas 120V Wiring must comply with local and national electrical codes and with the wiring diagram...

Page 4: ...s displayed on the screen press the E ENTER button The display will briefly indicate that the new setting has been Entered and the new setting will replace the previous setting on the second line of t...

Page 5: ...d the motor is on after the Call for Heat is satisfied to allow for evacuation of combustion gases A call for heat during Post Purge will result in a recycle Allowed Recycles Number of Recycles allowe...

Page 6: ...icates that the ignitor is energized flashes if ignitor not detected VALVE Indicates that the gas valve is energized on entry to pump prime will flash if not detected Operating Sequence With power to...

Page 7: ...ove the E button can be pressed to view the same data in the previous fault cycle For example if in Fault 1 the most recent fault the Ignitor Amps were low by pressing the E button the Ignitor Amps in...

Page 8: ...unless the Allowed Recycles is set to None in the Set up Menu A Recycle results in the burner shutting down for 60 seconds then resuming operation in Standby if there is no Call for Heat or initiatin...

Reviews: