W A R N I N G S

  1.  

 Warning  –  Do not attempt to confirm combustion simply by inspecting the flame visually. You must use combustion test instru-
ments. Failure to properly verify/adjust combustion could allow unsafe operation of the burner, resulting in severe personal injury, 
death or substantial property damage. Refer to the burner manual for proper setup instructions.

  2.  

 Warning  –  Never test an ignitor by placing a screwdriver (or other metallic object) across the high voltage clips. Check ignitors only 
by observing spark at appliance ignition electrodes, with fuel supply OFF. Using any other method could cause ignitor damage and 
severe personal injury.

  3.  

Danger – Fire, explosion, or carbon monoxide hazard. Water damage can lead to unreliable operation or cause the control to 
malfunction which could lead to severe personal injury or death. Do not install the control module where it can get wet. Always 
replace the control if it gets wet or if it has any signs of water residue.

  4. 

 Warning – Electrical shock hazard. To prevent electrical shock, death, or equipment damage, disconnect power supply before 
installing or servicing control. Only qualified personnel may install or service this control in accordance with local codes and ordi-
nances. Read instructions completely before proceeding.

  5.  

Warning – Electrical shock hazard. The ignition circuit of the control can produce over 10,000 volts which can cause severe injury 
or death.

  6.  

Warning – Frozen pipes/water damage. This is not a freeze protection device. Central heating systems are prone to shut down as 
a result of power or fuel outages, safety related fault conditions or equipment failure. Installation of freeze protection monitoring or 
other precautions are recommended for unattended dwellings in climates subject to sustain below-freezing temperatures.

  7.  

Warning – All work must be performed by a qualified and licensed professional in accordance with all applicable codes and ordi-
nances.

  8. 

Notice – Read these instructions completely before proceeding with the installation.

  9. 

Notice – Retain these instructions for future reference.

10. 

Notice – All wiring must comply with the National Electric Code or any other state or local codes or regulations.

11.  

Danger – Carbon Monoxide Hazard. Improper application or use can result in dangerous flue products, such as carbon monox-
ide, which can escape into the living space causing severe injury or death. All venting must be checked for proper operation before 
allowing the burner to run.

Hazard Definitions

The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or 

to important information concerning the life of the product.

Indicates presence of hazards that will cause 

severe personal injury, death or substantial 

property damage.

Indicates presence of hazards that will cause 

severe personal injury, death or substantial 

property damage.

Indicates presence of hazards that will cause 

minor personal injury or property damage.

Indicates special instructions on installation, 

operation or maintenance that are important 

but not related to personal injury or property 

damage.

Installing

 

  The 60200FR control must be installed and serviced only by a qualified service technician.

Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must 
comply with applicable codes and ordinances.

Mounting
 The control may be mounted on a 4" x 4" junction box in any convenient location on the burner, furnace or wall. The 
location must not exceed the ambient temperature limit, 140°F.

Summary of Contents for 60200FR

Page 1: ...ht 2019 Carlin Combustion Technology Inc Carlin Combustion Technology Inc On Board LCD Screen Fully Programmable Settings 32 Cycle Fault History Alarm Contacts Serviceman Reset Protection Blocked Vent...

Page 2: ...ection monitoring or other precautions are recommended for unattended dwellings in climates subject to sustain below freezing temperatures 7 Warning All work must be performed by a qualified and licen...

Page 3: ...3 Carlin Combustion Technology Inc MN60200FR1 070319 Wiring Commercial Gas Train 120V EZGas Pro 24V EZGas 120V Wiring must comply with local and national electrical codes and with the wiring diagram...

Page 4: ...s displayed on the screen press the E ENTER button The display will briefly indicate that the new setting has been Entered and the new setting will replace the previous setting on the second line of t...

Page 5: ...d the motor is on after the Call for Heat is satisfied to allow for evacuation of combustion gases A call for heat during Post Purge will result in a recycle Allowed Recycles Number of Recycles allowe...

Page 6: ...icates that the ignitor is energized flashes if ignitor not detected VALVE Indicates that the gas valve is energized on entry to pump prime will flash if not detected Operating Sequence With power to...

Page 7: ...ove the E button can be pressed to view the same data in the previous fault cycle For example if in Fault 1 the most recent fault the Ignitor Amps were low by pressing the E button the Ignitor Amps in...

Page 8: ...unless the Allowed Recycles is set to None in the Set up Menu A Recycle results in the burner shutting down for 60 seconds then resuming operation in Standby if there is no Call for Heat or initiatin...