Carlin 60200FR Installation And Operating Instructions Manual Download Page 1

Model 60200FR  

Gas Burner 

Primary Control 

Installation and  

Operating Instructions

For Use By Qualified Service Technicians Only

It is important that the installation of the oil burner, 
piping and fittings, safety devices, controls, electrical 
wiring and equipment be done in accordance with 
national and/or local regulations of the authorities 
having jurisdiction over such installation.

126 Bailey Rd   

 North Haven, CT 06473

Ph  203-680-9401 

Fx  203-680-9403

Tech Support 800-989-2275 

carlincombustion.com

©

 

Copyright 2019  — Carlin Combustion Technology, Inc.

Carlin Combustion Technology, Inc.

•  On-Board LCD Screen
• Fully Programmable Settings 
•  32 Cycle Fault History
• Alarm Contacts
• Serviceman Reset Protection
• Blocked Vent Protection
•  Provides Flame Signal in Microamps 
• Low Voltage Terminals

Power input  

  (red/white wire) ................................ 120 VAC, 60 HZ, 9 VA
Limit circuit input  

  (black wire)  .............................................. 120 VAC, 60 HZ
Motor load  

  (orange wire) .........10 FLA / 60 LRA (reduce by valve load)
Ignitor load  

  (blue wire) .................................... 120 VAC, 60 HZ, 500 VA
Valve load 

  (violet wire) .......................................... 120 VAC, 60 HZ, 2A
Auxiliary ..................................................... 120 VAC, 1 amp
Alarm contacts (dry contacts)....................24V, AC/DC, 2A
Operating temperature limits ..................+32°F to +140°F
Thermostat .....................................................24 VAC, 0.1A
Blocked Vent ................................................. 12 VDC, 2mA
CO .................................................................. 12 VDC, 2mA
Agencies .............................. UL recognized (US & Canada)

Summary of Contents for 60200FR

Page 1: ...ht 2019 Carlin Combustion Technology Inc Carlin Combustion Technology Inc On Board LCD Screen Fully Programmable Settings 32 Cycle Fault History Alarm Contacts Serviceman Reset Protection Blocked Vent...

Page 2: ...ection monitoring or other precautions are recommended for unattended dwellings in climates subject to sustain below freezing temperatures 7 Warning All work must be performed by a qualified and licen...

Page 3: ...3 Carlin Combustion Technology Inc MN60200FR1 070319 Wiring Commercial Gas Train 120V EZGas Pro 24V EZGas 120V Wiring must comply with local and national electrical codes and with the wiring diagram...

Page 4: ...s displayed on the screen press the E ENTER button The display will briefly indicate that the new setting has been Entered and the new setting will replace the previous setting on the second line of t...

Page 5: ...d the motor is on after the Call for Heat is satisfied to allow for evacuation of combustion gases A call for heat during Post Purge will result in a recycle Allowed Recycles Number of Recycles allowe...

Page 6: ...icates that the ignitor is energized flashes if ignitor not detected VALVE Indicates that the gas valve is energized on entry to pump prime will flash if not detected Operating Sequence With power to...

Page 7: ...ove the E button can be pressed to view the same data in the previous fault cycle For example if in Fault 1 the most recent fault the Ignitor Amps were low by pressing the E button the Ignitor Amps in...

Page 8: ...unless the Allowed Recycles is set to None in the Set up Menu A Recycle results in the burner shutting down for 60 seconds then resuming operation in Standby if there is no Call for Heat or initiatin...