“ultimateSAM - user” +03U0070EF - rel. 3.0 - 20201120
1.7.1
Mounting SAB/SAT models
NOT AVAILABLE ON THE NORTH AMERICAN MARKET
Fig. 1.p
NORTH AMERICAN MARKET ONLY
Fig. 1.q
Facing around
unit if necessary
Fig. 1.r
Note:
The inlet adapter, control valve, actuator, trap, and strainer
shown above are available as options. The “P” drains are not provided
as part of the ultimateSAM system.
•
Attach any optional inlet and/or drain connections to the distributor that
will need to pass through the wall of the duct. (Fig.1.o) See section 2 for
information in inlet connections. See section 3 for information on drain
connections.
•
Unless the distributor has been assembled inside the duct or AHU, cut an
opening in the duct through which the distributor can be inserted. The
opening can be in either the side or bottom of the duct, depending on
accessibility. (Fig.1.o)
•
Cut out any additional openings in the duct or AHU as needed for the
inlet and/or drain connections.
•
If desired, shim the inlet side of the distributor so that condensate in the
header with flow toward the drain pipe. A 1% grade (~1 cm per meter,
~1/8” per foot) is suggested.
•
Secure the bottom pedestals to the duct.
•
Secure the top corners of the side channels to the walls of the duct or
AHU.
•
Face off all sides of the duct, as necessary, so that air flow is directed
through the uprights as much as possible. (Fig.1.p)
Mounting SA0 (single-pipe) versions)
Fig. 1.s
Installation with manifold outside the duct
Fig. 1.t
Summary of Contents for ultimateSAM SA0
Page 2: ......
Page 4: ......
Page 6: ......
Page 29: ...29 ENG ultimateSAM user 03U0070EF rel 3 0 20201120 Note ...
Page 30: ......
Page 32: ......
Page 34: ......
Page 57: ...29 FRE ultimateSAM user 03U0070EF rel 3 0 20201120 Note ...
Page 58: ......
Page 59: ...31 FRE ultimateSAM user 03U0070EF rel 3 0 20201120 ...