“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinet
distribution
maint
enanc
e
alarms
displayed
meaning
cause
solution
reset
alarm
relay
action
notes
high humidity
humidity
outside of set
limits
value measured
by the probe
greater than the
humidity alarm
threshold
check the set parameter
manual
inactive
signal only
on
low humidity
humidity
outside of set
limits
value measured
by the probe
less than the
humidity alarm
threshold
check the set parameter
manual
inactive
signal only
on
humidity probe
broken or
disconnected
humidity probe
broken or
disconnected
main humidity
probe
disconnected or
broken
check the connection & the operation
of the probe
manual
active
stop
production
on
high humidity
limit probe
limit humidity
outside of set
limits
value measured
by the probe
greater than the
humidity alarm
threshold
check the set parameter
manual
inactive
signal only
fl ash
can only be
reset switching
the unit off
from “set”,
signalled only in
sequence after
other alarms
but not when
forced.
limit probe
broken or
disconnected
limit probe
broken or
disconnected
limit humidity
probe
disconnected or
broken
check the connection & the operation
of the probe
manual
active
stop
production
on
slave (2-3-4-5-6)
unit offl
ine
slave unit not
connected to
the pLAN
pLAN network
disconnected
check connection of pLAN cable to
terminals on controller
manual
active
signal only
on
master unit
offl
ine
master unit not
connected to
the pLAN
pLAN network
disconnected
check connection of pLAN cable to
terminals on controller
manual
active
signal only
on
low pressure
alarm
insuffi
cient air
pressure
insuffi
cient air
pressure
check air line pressure
manual
active
stop
production
on
for ON/OFF
units
compressor
alarm from air
compressor
compressor fault
alarm
check air compressor
manual
active
signal only
on
fl ow switch
alarm from AHU
fl ow switch
no air in AHU
alarm
check AHU
manual
active
signal only
on
water treatment
system
alarm from
water treatment
system
water treatment
system fault
alarm
check water treatment system
manual
active
signal only
on
pressure
sensor faulty or
disconnected
pressure
sensor faulty or
disconnected
pressure
sensor faulty or
disconnected
check pressure sensor
manual
active
stop
production
on
for proportional
units with air
pressure sensor
pressure off
scale
air pressure
outside of set
limits
insuffi
cient air
pressure
check air supply pressure
manual
active
stop
production
on
for proportional
units with air
pressure sensor
clock fault
clock error
backup battery
completely
discharged or
generic clock
fault
replace clock
manual
inactive
signal only
off
9. TABLE OF ALARMS
When an alarm is activated, the alarm button starts fl
ashing
intermittently.
In these conditions, pressing the alarm button once displays the type of
alarm .
In the case of potentially dangerous alarms, the controller automatically
stops production. For some alarm events, the alarm relay is also activated
at the same time as the signal (see the table below).