4.4 pLAN network connection (J11)
Use two-wire cables plus earth, AWG 20/22, maximum distance between
two cabinets: 200 m (219 yd).
MASTER
SLAVE
GR
GR
s e r v i c e c a rd
Rx-/Tx-
Rx+/Tx+
GND
J 9
J 1 0
J11
s e r v i c e c a rd
Rx-/Tx-
Rx+/Tx+
GND
J 9
J 1 0
J11
Connections:
MC Master cabinet J11
MC Slave cabinet
J11
RX+/TX+
J11
RX+/TX+
RX-/TX-
RX-/TX-
GND
GND
In multizone mode, by disabling the “stop slave off line” function, if the
pLAN is interrupted the slaves operate independently according to the
signals from the probes or/and controllers. In this mode, the values will
not be shown on the master display.