3.1 Power supply
Depending on the model:
MC****D*** voltage 230V 1~ 50Hz
MC****1*** voltage 110V 1~ 60Hz
Important:
The cables must be shielded and conform to local
standards. Install a power switch outside the humidifi er to completely
isolate the mains power supply.
G0
NO4
L
N/W
GR
G0
NO4
ID1
ID1
ID2
ID2
ID3
ID3
ID4
ID4
ID6
ID6
ID7
ID7
COM1
COM1 COM2
COM2
COM3
COM3
F1 1A
F2 1A
L
N/W
GR/PE
Connections:
MC cabinet
Power cable
L
L/F (phase)
N
N/W (neutral)
GR
GR/PE (earth)
3.2 Remote ON/OFF (ID & COM)
Use two-wire shielded cable, AWG20/22
G0
NO4
L
N/W
GR
G0
NO4
ID1
ID1
ID2
ID2
ID3
ID3
ID4
ID4
ID6
ID6
ID7
ID7
COM1
COM1 COM2
COM2
COM3
COM3
F1 1A
F2 1A
1
1
Remote ON/OFF
Connections:
MC cabinet
Remote ON/OFF
ID1
NC/NO
COM (1 or 2 or 3)
CON
GR
shield
3.3 Modulating control signal (J24 & J2)
The input control signal connections depend on the control algorithm
activated.
cables
up to 30 m: shielded cables, size 0.5 mm
2
(AWG20)
over 30 m: shielded cables, size 1.5 mm
2
(AWG15)
connect the shield (cabinet side) to specifi c earth
terminal GR (see connection diagrams)
the signal can
come from
a. modulating control with external controller
b. modulating control with ambient humidity probe
c. external controller & limit humidity probe
d. ambient humidity probe & limit humidity probe
e. modulating control with temperature control
f. mod. control with temperature control & limit probe
To set the type of operation, control and signal:
installer menu > type of control (see chap. 7).
a. Modulating control with external controller
0 to 1 V
0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA
J 4
J 3
J 2
VG
VG
0
Y1
Y2
Y3
B4
BC4
B5
BC5
B1
B2
B3
J 2 4
+V
term
GND
+5V
re
f
GND
+VDC
1
GR
1
External controller
Connections:
MC cabinet
external controller
J24
GND
REF
J2
B1
OUT
b. Modulating control with ambient humidity probe
0 to 1 V
0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA
J 4
J 3
J 2
VG
VG
0
Y1
Y2
Y3
B4
BC4
B5
BC5
B1
B2
B3
J 2 4
+V
term
GND
+5V
re
f
GND
+VDC
1
GR
1
Ambient humidity probe
Connections:
MC cabinet
ambient humidity probe
J24
+V term
+(G)
GND
M
J2
B1
out H
c. Modulating control with external controller and limit
probe
0 to 1 V
0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA
J 4
J 3
J 2
VG
VG
0
Y1
Y2
Y3
B4
BC4
B5
BC5
B1
B2
B3
J 2 4
+V
term
GND
+5V
re
f
GND
+VDC
1
GR
2
GR
1
Limit humidity probe
2
External controller