+050004104 rel. 2.2 del 26.09.07
10
ENGL
ISH
H3
Remote control enabling code
AD
-
C
0
255
0
H4
Disable buzzer
AD
flag
C
0
1
0
0: Buzzer enabled
1: Buzzer disabled
H5
Function of relay 5
AD
flag
C
0
13
1
As for H1
H6
Lock keypad
AD
-
C
0
255
0
H8
Select activation of output with time band
AD
flag
C
0
1
0
0: Time band linked to output configured for light
1: Time band linked to output configured for aux
H9
Enable set point variation with time band
AD
flag
C
0
1
0
0: Set point variation with time band disabled
1: Set point variation with time band enabled
Hdh
Anti-sweat heater offset
AD
°C/°F
C
-50
200
0.0
Simbol
Code
Parameter
AD
U.O.M.
Type
Min
Max
Def.
HAn
Number of HA events recorded
AD
-
C
0
15
0
HA
Date/time of last HA event
AD
-
C
-
-
y__
Year
years
0
99
0
M__
Month
months
0
12
1
d__
Day
days
0
7
1
h__
Hour
hours
0
23
0
n__
Minute
minutes
0
59
0
t__
Duration
hours
0
99
0
HA1
Date/time of penultimate HA event
AD
-
C
-
-
-
HA2
Date/time of third-to-last HA event
AD
-
C
-
-
-
HFn
Number of HF events recorded
AD
-
C
0
15
0
HF
Date/time of last HF event
AD
-
C
-
-
-
y__
Year
years
0
99
0
M__
Month
months
0
12
1
d__
Day
days
0
7
1
h__
Hour
hours
0
23
0
n__
Minute
minutes
0
59
0
t__
Duration
hours
0
99
0
HF1
Date/time of penultimate HF event
AD
-
C
-
-
-
HF2
Date/time of third-to-last HF event
AD
-
C
0
-
-
Htd
HACCP alarm delay
AD
minutes C
0
250
0
Simbol
Code
Parameter
AD
U.O.M.
Type
Min
Max
Def.
td1
Defrost time band 1
AD
-
C
-
-
-
d__
Day
days
0
11
0
h__
Hour
hours
0
23
0
n__
Minute
minutes
0
59
0
td2
Defrost time band 2
AD
-
C
-
-
-
td3
Defrost time band 3
AD
-
C
-
-
-
td4
Defrost time band 4
AD
-
C
-
-
-
td5
Defrost time band 5
AD
-
C
-
-
-
td6
Defrost time band
AD
-
C
-
-
-
td7
Defrost time band 7
AD
-
C
-
-
-
td8
Defrost time band 8
AD
-
C
-
-
-
ton
Light/aux on time band, variation set point
AD
-
C
-
-
-
d__
Day
days
0
11
0
h__
Hour
hours
0
23
0
n__
Minute
minutes
0
59
0
toF
Light/aux off time band, variation set point
AD
-
C
-
-
-
d__
Day
days
0
11
0
h__
Hour
hours
0
23
0
n__
Minute
minutes
0
59
0
tc
RTC date/time setting
AD
-
C
-
-
-
y__
Year
years
0
0
99
0
M__
Month
months 1
1
12
1
d__
Day of the month
days
1
1
31
1
u__
Day of the week
hours
6
6
7
1
h__
Hour
minutes 0
0
23
0
n__
Minute
hours
0
0
59
0
Tab. 4.a
Important warning:
for the set times to become immediately operational, turn the instrument on and off again. If the instrument is not switched off, the
times will only become operational when next used, when the internal timers are set.