+050004104 rel. 2.2 del 26.09.07
8
ENGL
ISH
Simbol
Code
Parameter
AD
U.O.M. Type
Min
Max
Def.
c0
Comp., fan and AUX delay on start-up in dead band
AD
min
C
0
15
0
c1
Minimum time between successive starts
AD
min
C
0
15
0
c2
Minimum compressor OFF time
AD
min
C
0
15
0
c3
Minimum compressor ON time
AD
min
C
0
15
0
c4
Duty setting
AD
min
C
0
100
0
cc
Continuous cycle duration
AD
ore
C
0
15
0
c6
Alarm bypass after continuous cycle
AD
ore
C
0
250
2
c7
Maximum pump down time
AD
s
C
0
900
0
c8
Comp. start delay after open PD valve (factory set to 0 and not visible)
AD
s
C
0
60
5
c9
Enable autostart function in PD
AD
flag
C
0
1
0
c10
Select Pump down by time or pressure
AD
flag
C
0
1
0
0: Pump down by pressure
1: Pump down by time
c11
Second compressor delay
AD
s
C
0
250
4
Simbol
Code
Parameter
AD
U.O.M. Type
Min
Max
Def.
d0
Type of defrost
AD
flag
C
0
4
0
0: Electric heater defrost by temperature
1: Hot gas defrost by temperature
2: Electric heater defrost by time
3: Hot gas defrost by time
4: Electric heater defrost thermostat by time
dI
Interval between defrosts
AD
ore
F
0
250
8
dt1
End defrost temperature, evaporator
AD
°C/°F
F
-50
200
4.0
dt2
End defrost temperature, aux evap.
AD
°C/°F
F
-50
200
4.0
dP1
Maximum defrost duration, evaporator
AD
min
F
1
250
30
dP2
Maximum defrost duration, aux evap.
AD
min
F
1
250
30
d3
Defrost start delay
AD
Min
C
0
250
0
d4
Enable defrost on start-up
AD
flag
C
0
1
0
0: No defrost is performed when the instrument is switched on
1: A defrost is performed when the instrument is switched on
d5
Defrost delay on start-up
AD
min
C
0
250
0
d6
Display on hold during defrost
AD
-
C
0
2
1
0: Alternating display of dEF and probe value
1: Display of the last temp. shown
2: Display of dEF steady
dd
Dripping time after defrost
AD
min
F
0
15
2
d8
Alarm bypass after defrost
AD
ore
F
0
15
1
d8d
Alarm bypass after door open
AD
ore/min C
0
250
0
d9
Defrost priority over compressor protectors
AD
flag
C
0
1
0
0: The protection times c1, c2 and c3 are observed
1: The protection times c1, c2 and c3 are not observed
d/1
Display of defrost probe 1
AD
°C/°F
F
-
-
-
d/2
Display of defrost probe 2
AD
°C/°F
F
-
-
-
dC
Time base for defrost
AD
flag
C
0
1
0
0: dI in hours, dP1 and dP2 in minutes
1: dI in minutes, dP1 and dP2 in seconds
d10
Compressor running time
AD
ore
C
0
250
0
d11
Running time temperature threshold
AD
°C/°F
C
-20
20
1.0
d12
Advanced defrost
AD
-
C
0
3
0
dn
Nominal defrost duration
AD
-
C
1
100
65
dH
Proportional factor, variation in dI
AD
-
C
0
100
50
Simbol
Code
Parameter
AD
U.O.M. Type
Min
Max
Def.
A0
Alarm and fan differential
AD
°C/°F
C
0.1
20
2.0
A1
Type of threshold ‘AL’ and ‘AH’
AD
flag
C
0
1
0
0: AL and AH are relative thresholds
1: AL and AH are absolute thresholds
AL
Low temperature alarm threshold
AD
°C/°F
F
-50
200
0.0
AH
High temperature alarm threshold
AD
°C/°F
F
-50
200
0.0
Ad
Low and high temperature signal delay
AD
min
F
0
250
120
A4
Digital input 1 configuration
A
-
C
0
14
0
D
-
C
0
14
3
0: Input not active
1: Immediate external alarm
2: Delayed external alarm
3: If model M, probe selection
3: Other models enable defrost
4: Start defrost
5: Door switch with compressor and fan stop
6: Remote on/off
7: Curtain switch