27
ENG
“Ultrasound for fancoil” +0300059IE - rel. 1.5 - 15.07.2019
“I”
integer variables (Modbus®: REGISTERS)
R/W
CAREL
Modbus®
63
190
Value of variable on slave unit identifi ed by integer 62 (see paragraph 14.4)
R/W
65
192
Parameter C4: Timeout for master serial offl
ine
R/W
69
196
AA: Waiting time for retry
R/W
70
197
Ab: Percentage of A8 for carrying out level test
R/W
71
198
Pn: Minimum production
R
72
199
bF: Drain activation delay in standby
R/W
73
200
AC: Maximum time to measure level when refi lling
R/W
74
201
Ad: Maximum time to measure high level
R/W
82
209
AE: Restart fan time in standby for integrated probe reading
R
87
214
Slave 1 fi rmware release
R
89
216
Slave 1 humidifi er status
R
92
219
Parameter d3, slave 1: Operating hour counter
R/W
93
220
Slave 2 fi rmware release
R
95
222
Slave 2 humidifi er status
R
98
225
Parameter d3, slave 2: Operating hour counter
R/W
99
226
Slave 3 fi rmware release
R
101
228
Slave 3 humidifi er status
R
104
231
Parameter d3, slave 3: Operating hour counter
R/W
105
232
Piezoelectric transducer operating hour counter
R
106
233
Parameter d6 Time remaining to end of piezoelectric transducer life
R/W
107
234
Parameter AF: Piezoelectric transducer working life
R/W
112
239
Parameter bH: Enable probe TH as humidity limit
R/W
113
240
Parameter SL: Humidity limit set point
R/W
114
241
Parameter bP: proportional band for control with probe TH or external probe
R/W
115
242
Parameter bL: limit proportional band
R/W
117
244
Parameter d7: manage slave unit production
R/W
Tab. 12.b
“D”
digital variables (Modbus®: COILS)
R/W
CAREL
Modbus®
2
1
Just started fl ag
R
3
2
Humidifi er ready to produce
R
4
3
Humidity set point reached
R
5
4
Green LED
R
6
5
Red LED
R
7
6
Yellow LED
R
8
7
Remote On/Off
R
9
8
Low level
R
10
9
High level
R
11
10
Aux level
R
12
11
Autotest completed
R
14
12
BMS serial in tLAN mode
R
15
14
TAM enabled
R
16
15
TAM reading
R
17
16
Terminal connected
R
18
17
Production in progress
R
19
18
Fill
R
20
19
Drain
R
21
20
Transducer 1
R
22
21
Transducer 2
R
23
22
Fan
R
24
23
Alarm relay
R
25
24
Auxiliary relay
R
26
25
Manual drain
R/W
27
26
Disable from serial
R/W
28
27
Reset hour counter
R/W
29
28
Reset alarms
R/W
30
29
Status of dipswitch 8: parallel/series modulation
R
31
30
Functional test performed
R
33
31
Unit of measure
R/W
34
32
Slave 1 online
R
35
34
Slave 2 online
R
36
35
Slave 3 online
R
37
36
Enable control from serial
R/W
38
37
Wash activation from serial
R/W
39
38
Skip Autotest or washing while in progress
R/W
43
42
Reset piezoelectric transducer hour counter
R/W
44
43
Backup unit ready for production
R
46
45
Production limiting in progress (limit probe function)
R
47
46
On/Off control from keypad for master/slave network
R/W
49
48
On/off control from master unit keypad
R/W
50
49
On/off control from slave unit 1 keypad
R/W
51
50
On/off control from slave unit 1 keypad
R/W
52
51
On/off control from slave unit 1 keypad
R/W
Tab. 12.c