8. CONFIGURATION
PARAMETERS
8.1 Parameter access and setting
See chapter 6 “Start and user interface”
Note
: variable type: A = analog I=full, D = digital.
8.2 Basic operation parameters
Par.
Description
UM
range
def
Variable
type
CAREL
protocol
notes
A0
Operating mode
0,…,3
2
l
9
0= ON/OFF command
1= external proportional signal
2= autonomous adjusting with room probe
3= autonomous adjusting with room probe and limit probe
A1
Unit of measurement:
0,1
0
l
10
0=°C, kg/h – 1 = °F, Ib/h
A2
signal applied to room probe input
autonomous control (A0=1, 2 or 3)
0,…, 4
0
I
11
0= 0…1 V
1= 0…10 V
2= 2…10 V
3= 0…20 mA
4= 4…20 mA
A3
room probe minimum
%rH
0, .., (A4)
0
I
12
can only be accessed in autonomous control (A0=2 or 3)
A4
room probe maximum
%rH
(A3), .., 255 *
100
I
13
A5
room probe calibration
%rH
-10.0,…,10.0
0
A
4
A6
signal applied to the outlet probe
input can only be accessed in
autonomous control with outlet
probe (A0=3)
0,…,4
0
I
14
0= 0…1 V
1= 0…10 V
2= 2…10 V
3= 0…20 mA
4=4…20 mA
A7
minimum limit probe
%rH
0,…,(A8)
0
I
15
can only be accessed in autonomous control with outlet probe (A0=3)
A8
maximum limit probe
%rH
(A7), .., 100
100
I
16
A9
limit probe calibration
%rH
-10…10
0
A
5
Tab. 8.a
8.3 Auxiliary function parameters
Par.
Description
UM
range
def
Variable
type
CAREL
protocol
notes
b0
period of modulation (if set to 0 modulation is disabled)
s
0,…,199
**
I
17
b1
Check the functions assigned to parameter b1 in the table given in chapter 12.
0…63
0
I
18
b2
start pre-heating off set (referred to set point)
%% r.H.
2,…,19.9
3.0
A
6
They can only
be accessed
with pre-heating
function enabled
(b1=1 or 3)
b3
pre-heating temperature
°C
70,…,90
80
I
19
b5
conductivity pre-alarm threshold (displayed as 1•2)
μS/cm
0,…,2000
1250
I
21
b6
conductivity alarm threshold (displayed as 1•5)
μS/cm
0,…,2000
1500
I
22
b7
control of the foam detection threshold (if set to 0 foam detection is disabled)
%
0,…,100
50
I
23
b8
setting the maximum number of evaporation cycles between two drain cycles for
dilution step:1
The actual value used is internally calculated based on the value read for the conduc-
tivity of the water supply (the higher the conductivity, the lower the calculated value),
however if the calculated value is greater than b8, b8 will be used. If b8=0, it shall
be automatically set to 2 at fi rst heaters start-up and if conductivity measured in the
supply water is <= 100 μS/cm, or at 5.
-
0…50
0
I
33
b9
minimum time for passing from 0 to 100% of steam production
min
0,…,100
0
I
24
bA
percentage reduction in the duration of the water fi ll time
%
20…100
100
I
34
bb
steam production value (step 0.1%)
it allows the user to “adjust” the value displayed by parameter d3, if there is a system
available for measuring the diff erence between the value displayed d3 and the actual
steam production.
Example of use:
d3= 10 kg/h and bb= +10% changes d3 to 11 kg/h (= 10 kg/h + 10%)
%
-19.9…19.9
0
A
7
bC
automatic total drain for inactivity (see par. 12)
days
1…199
3
I
35
bd
user-adjustable duration of dilution drain (see par. 12)
%
0…190
100
I
36
bE
fi ll-up cycle duration, after dilution drain, in pwn mode
s
1…199
5
I
37
Tab. 8.b