Carel EVD ice User Manual Download Page 22

22

ENG

“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018

Parameter

Description

Def.

Min

Max

Type Carel Modbus® R/W Note

Pctrl_rev_set

Reserved

-

-20(-290)

200(2900)

A

23

22

R/W

SH_actual_set       

Reserved

0

-40(-72)

180(324)

A

24

23

R

SH_Set_smooth_line   

Superheat Setpoint-Offset for smooth line

0

-55(-99)

55(99)

A

25

24

R/W

S1_value_remote  

Reserved

0

-20(-290)

200(2900)

A

26

25

R/W

Tab. 8.b 

8.9  Control states

The electronic valve controller can have six different control states, 
each of which may correspond to a specific phase in the operation of 
the refrigeration unit and a certain status of the driver-valve system. The 
states are as follows:

• 

forced closing: initialisation of the valve position when switching the 
instrument on;

• 

standby: no temperature control, unit OFF (at temp.);

• 

wait: opening of the valve before starting control, also called pre-
positioning, when powering the unit on;

• 

control: effective control of the electronic valve, unit ON;

• 

positioning: step-change in the valve position, corresponding to the 
start of control when the cooling capacity of the controlled unit varies 
(only EVD connected to a pCO);

• 

stop: of control with closing of the valve, corresponds to the end of 
temperature control of the refrigeration unit, unit OFF (at temp.).

Forced closing

Forced closing is performed after the driver is powered on and corresponds 
to the typical number of closing steps for CAREL E2V and E3V unipolar  valves. 
This is used to realign the valve to the physical position corresponding to 
completely closed. The driver and the valve are then ready for control and 
both aligned at 0 (zero). At power-on, first a forced closing is performed, 
and then the standby phase starts. The valve is also closed in the event of 
a mains power failure if the Ultracap module is connected. In this case, the 
“Forced valve closing not completed” parameter is set to 1. On restarting, if 
the valve forced closing procedure is not completed successfully:

1. 

the Master programmable controller (pCO) will check the value of the 
parameter, and if equal to 1 will decide the best strategy to adopt, 
based on the application;

2. 

on restarting the driver positions the valve as explained in the paragraph 
“Pre-positioning/start control”. The parameter is set to 0 (zero) by the 
Master controller (e.g. pCO), or alternatively by pressing the PRG/
Set button on the keypad. Once the parameter has been set to 1, 
the driver sets it back to 0 (zero) only if an emergency forced closing 
procedure is completed successfully.

Note:

 lthe user can only select the resolution of the valve control 

signal: 480 or 960 steps.

Par. Description

Def. Min. Max. UoM

U3 Valve control steps: 1 / 2 = 480/ 960 steps

1

1

2

-

Standby

Standby corresponds to a situation of rest in which no signals are received 
to control the electronic valve: it is closed and manual positioning can be 
activated. This status is normally set on the driver when the refrigeration 
unit is shutdown manually (e.g. from the supervisor) or when reaching the 
control set point. It can also occur when opening the digital input (which 
involves closing the valve) or in the event of a probe alarm. In general, it can 
be said that the electronic valve driver is in standby when the compressor 
stops or the control solenoid valve closes. 

Pre-positioning/start control

If during standby a control request is received, before starting control the 
valve is moved to a precise initial position. Internally, the pre-positioning time 
is set at 6 s and represents the time that the valve is held in a fixed position. 
By default the valve is opened 50 % when starting (from digital input), so as to 
minimise the movement needed to reach the correct position.

Par. Description

Def.

Min.

Max. UoM

U4 Valve opening at start-up

50

0

100

%

This parameter should be set based on the ratio between the rated 
cooling capacity of the evaporator and the valve (e.g. rated evaporator 
cooling capacity: 3kW, rated valve cooling capacity: 10kW, valve opening 
= 3/10 = 33%). 

The driver calculates the valve opening based on the required capacity:

If required capacity is 100%:

Opening (%)= (Valve opening at start-up);

If required capacity is less than 100% (capacity control):

Opening (%)= (Valve opening at start-up) x (Current unit cooling 
capacity), where the current unit cooling capacity is sent to the driver 
via RS485 by the pCO controller. If the driver is stand-alone, this is always 
equal to 100%.

Notes:

 

• 

this procedure is used to anticipate the movement and bring the valve 
significantly closer to the operating position in the phases immediately 
after the unit is powered on;

• 

if there are problems with liquid return after the refrigeration unit starts 
or in units that frequently switch on-off, the valve opening at start-up 
must be decreased. If there are problems with low pressure after the 
refrigeration unit starts, the valve opening must be increased.

Wait

When the calculated position has been reached, regardless of the time taken 
(this varies according to the type of valve and the objective position), there 
is a constant 5 second delay before the actual control phase starts. This is to 
create a reasonable interval between standby, in which the variables have no 
meaning, as there is no flow of refrigerant, and the effective control phase. 

Control

The control request can be received by the closing of the digital input 
or via network (RS485). The solenoid or the compressor are activated 
when the valve, following the pre-positioning procedure, has reached 
the calculated position. The following figure represents the sequence of 
events for starting control of the refrigeration unit.

t

t

t

t

OFF

ON

R

OFF

ON

P

OFF

ON

S

OFF

ON

A

T1

W

Fig. 8.o

Key:

A

Control request

T1 Pre-positioning time

P

Pre-positioning

W Wait (wait)

S

Standby

t

Time

R

Control

Positioning (change cooling capacity)

This control status is only valid for controllers connected to the pCO 
via RS485. If there is a change in unit cooling capacity of at least 10%, 
sent from the pCO via RS485, the valve is positioned proportionally. In 
practice, this involves repositioning starting from the current position in 

Summary of Contents for EVD ice

Page 1: ...H i g h E f f i c i e n c y S o l u t i o n s EVD ice NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT User manual Superheat control for unipolar electronic expansion valve...

Page 2: ......

Page 3: ...not use corrosive chemicals solvents or aggressive detergents to clean the device do not use the product for applications other than those specified in the technical manual All of the above suggestio...

Page 4: ......

Page 5: ...2 Special control function smooth lines 14 5 3 Service parameters 14 6 PROTECTORS 15 6 1 Protectors 15 7 PARAMETERS TABLE 17 8 NETWORK CONNECTION 18 8 1 RS485 serial configuration 18 8 2 Network conne...

Page 6: ......

Page 7: ...om controllers 1 1 Models P N Description EVDM011R3 EVD ice 115 230 V E2V stator display EVDM011R1 EVD ice 115 230 V E2V stator display Ultracap module connector EVDM011R4 EVD ice 115 230 V E3V stator...

Page 8: ...portant install EVD ice on the evaporator away from the places where ice forms connect the power and serial cables in the IP65 junction box for assembly of the E2V E3V valve see the ExV system guide 0...

Page 9: ...Regulator P T EEV M Condenser Electrical panel Compressor Condenser unit Evaporator unit Solenoid valve IP65 L N Fig 2 d WITHOUT SOLENOID VALVE WITH ULTRACAP MODULE COLD ROOM IN COLD ROOM OUT COLD RO...

Page 10: ...d pressure probe see the chapter on Commissioning 2 connectthepowercableandthedigitalinputcable forthemaximum length see the technical specifications 3 poweronthedriver thedisplaywilllightup andthedri...

Page 11: ...than 9 are displayed in two steps first the sign then the tens and units GASType Mode Super Heat GASType Mode Super Heat 123 GASType Mode Super Heat GASType Mode Super Heat 99 Fig 3 b Note the decima...

Page 12: ...Superheat set point GASType Mode Super Heat 7 Press PRG Set for 2 seconds to exit the commissioning procedure and start control The standard display is shown 4 2 Parameters first configuration Import...

Page 13: ...through the nozzle corresponds to the flow rate required by the compressor In this way the evaporation process will take place along the entire length of the evaporator and there will be no liquid at...

Page 14: ...ol temperature approaches the set point the Smooth_line parameter is used to prevent the valve from closing by reducing the evaporator s cooling capacity In order to use this function the digital inpu...

Page 15: ...activation threshold depending on the operating conditions of the controlled unit this is set in Service programming mode integration time which determines the intensity if set to 0 the protector is...

Page 16: ...refrigerant charge or when there are sudden variations in the load The protector is also useful in multiplexed systems showcases as allows all the utilities to be enabled at the same time without cau...

Page 17: ...Po Valve opening 0 100 A 1 0 R CP PID proportional gain 15 0 800 A 11 10 R W ti PID integral time 150 0 999 s I 17 144 R W C1 LowSH protection threshold 5 9 5 9 Superheat set point K F A 12 11 R W C2...

Page 18: ...00 2 stop bit parity odd 15 4800 1 stop bit parity odd 16 9600 1 stop bit parity odd 17 19200 1 stop bit parity odd 2 0 17 Important all controllers connected in a serial network need to be set with t...

Page 19: ...RS485 rear connector Offline Device model Online Offline Device setup Read instant values of control parameters Select Load to load a list of project parameters hex modify and save a new project Setup...

Page 20: ...iguration page parameters p_GAS_TYPE refrigerant and p_SUPER_MAIN_REGULATION type of control b on the Configuration page parameter p_SH_SET Fig 8 m 3 Savethelistofparameterswithanewname forexample NEW...

Page 21: ...om dew_f_l Dew f low 17239 32768 32767 I 35 162 R W Net_alarm Network alarm 0 0 1 D 1 0 R all E6 Emergency_closing_alarm Mains power failure 0 0 1 D 2 1 R all E5 S1_alarm Probe S1 alarm 0 0 1 D 3 2 R...

Page 22: ...r or when reaching the control set point It can also occur when opening the digital input which involves closing the valve or in the event of a probe alarm In general it can be said that the electroni...

Page 23: ...a power failure proceed as follows remove the valve stator set the PID proportional gain 0 The valve will remain stopped at the initial opening position set by corresponding parameter Retrieve physica...

Page 24: ...ent of probe or valve malfunctions to protect the compressor using the relay to control the solenoid valve or to simply signal a possible risk In fact incorrect measurement of the evaporation pressure...

Page 25: ...inets only Decrease the value of the Valve opening at start up parameter on all the utilities making sure that there are no repercussions on the control temperature Liquid returns to the compressor on...

Page 26: ...the valve by placing it in manual control and closing or opening it com pletely One complete opening must bring a decrease in the superheat and vice versa If the movement is reversed check the electri...

Page 27: ......

Page 28: ...EL INDUSTRIES HeadQuarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency EVD ice 0300038EN rel 1 1 23 04 20...

Reviews: