background image

zz

+050001660 - rel. 1.

4

 - 1

5

.11.201

6

E

3

V-C - 

電子膨張弁

 / Electronic expansion valve

Fig.1

OK

OK

NO

取付け位置

 / Positioning

gasket

フィルター

ガスケット

filter

T.Max
700° C

60 Nm

3 mm

A

B

C

  ねじ込み

First step tightening

(

手動

 / 

manually

)

D

   締付け

Second step tightening

(

スパナで

 / 

with key

)

E

溶接時の注意

 / Welding and handling

General features

The E3V-C electronic valve is used as the pressure controller in transcritical circuits with CO2 refrigerant (R744). Only CAREL 

control devices should be used to manage the E3V-C. Do not use the E3V-C valves outside of the normal operating conditions, 
shown below.

Positioning

The E3V-C valve is single-acting, with the fl uid entering through the side connection (Fig. 1). If using shutoff  valves before the 
expansion valve, the circuit must be set up so that no fl uid hammer is created near the valve. 
The shutoff  valve and expansion valve must never be closed at the same time, to avoid dangerous excess pressure in the circuit. 
Always install the mechanical fi lter supplied.
The valve can be oriented in any direction, with the exception of the stator pointed downwards (valve upside down).

Welding and handling

The E3V-C valves must be welded to the circuit in the correct direction of fl ow.
Follow the steps shown in Fig. 2, proceeding as follows:

1. 

Take the valve from the packaging.

2. 

If assembled, disassemble the valve body and the cartridge.

3. 

Wrap a wet rag around the valve and braze without overheating the valve, aiming the fl ame at the ends of the fi ttings. Use alloys with 
a fusion temperature less than 700° C. If welded using other methods, do not exceed 100° C on the valve body. Avoid leaving solid 
residues inside the valve body; it is recommended to fl ux with a suitable shielding gas.

4. 

Make sure that the cartridge O-ring is present and in position (Fig. 2-B). 

5. 

Make sure that the metal mesh fi lter supplied is inserted on the cartridge (Fig. 2-B). Otherwise, position it as shown in the fi gure, 
making sure it is fully inserted.

6. 

First step tightening (by hand). Screw the cartridge in the threaded valve body; do this operation manually up to 3 mm from 
the assembly (Fig. 2.c.). 

Attention

! To this height, the manual installation should be easy; otherwise, the shutter may not be 

properly inserted in the orifi ce.

7.

Second step tightening (with key). Tighten the cartridge on the valve body with a torque of 60 Nm suggested using a wrench 
32 (Fig. 2.d). 

Attention!

 In the case of the shutter is not properly inserted in the orifi ce, the fi nal tightening may damage the 

cartridge.

8. 

To allow faster valve assembly, it is recommended not to remove the motor from the cartridge. If removing and reassembling the 
motor, make sure that the red stator is fully inserted in the cartridge, completely tightening the black nut until deforming the rubber 
ring on the stator (tightening torque 0.3 Nm).

9. 

Connect the pre-wired connector to the socket on the stepper motor and tighten the screw with a tightening torque of 0.5 Nm 
following the instructions in Fig. 3. Then connect the four-pin end of the cable to the corresponding terminals on the CAREL EVD*** 
driver or approved CAREL controller and set the parameters as shown in the table below.

no.

Model

Min step

Max step

Close steps

Step/s speed

mA pk

mA hold

% duty

0

CAREL E

X

V

50

480

500

50

450

100

30

CAREL electronic valve controllers increase the duty cycle by 30% to 100% when closing so as to shorten stopping times; to 
further accelerate this procedure, the valve can be controlled at a maximum frequency of 150 steps/s. For further information 
of the parameters to be set in the driver, see the controller manual.

Warning! If the threaded rod completely comes out of the cartridge socket, proceed as follows:

•  Tighten the rod to the cartridge without the motor inserted – turn until hearing a click (this indicates that the anti-rotation 

device is aligned).

•  Insert the motor on the cartridge and connect it to the CAREL driver, following the instructions shown below (electrical 

connections).

•  Set the driver in manual operation and set a number of 480 steps (complete opening); start the sequence of steps, the rod will 

position itself inside the anti-rotation guide to allow correct installation.

Do not exert torsion or deforming stress on the valve or the connection pipes. Do not hit the valve with hammers or other 
objects. Do not use pliers or other tools that may deform the external structure or damage the internal parts. Never aim the 
fl ame at the valve. Never place the valve near magnetic fi elds.
Never install or use the valve in the event of:
•  deformation or damage to the external structure;
•  heavy impact, due for example to dropping;
•  damage to the electrical parts (stator, contact carrier, connector,...).
CAREL does not guarantee the operation of the valve in the event of deformation of the external structure or damage to the 
electrical parts.  IMPORTANT: the presence of dirt particles may cause valve malfunctions.

Electrical connections

Connect an IP67 connector with moulded cap only (E2VCAB0***), in which the pin mapping is 1 Green, 2 Yellow, 3 Brown, 4 White. Then 
connect the four motor phases to your driver so that phase 1 of the valve corresponds to terminal 1 of the driver, and so on. Important: 
phase no. 4 is marked on the valve stator with the earth symbol.
An optional shielded connector with moulded cap is available (E2VCABS***) for applications with specifi c electromagnetic disturbance, 
in compliance with the standards in force, 89/336/EEC and later amendments.
Avoid using standard DIN 43650 connectors, as these will not guarantee optimum product performance.

O

perating specifi cations CAREL E

3

V-C

Compatibility 

R744 (not be used with mineral oils)

Maximum Operating Pressure (MWP)

140 barg (2031 PSIg)  -  (UL/CSA, MWP=1740PSIg/120 barg)

Maximum Operating diff erential pressure (MOPD)

90 barg (1305 PSIg)

P.E.D.

Gr. 2, art. 

4

,  par. 3

Refrigerant temperature

-40T65°C (-40T149°F)

Room temperature

-30T50 °C (-22T122 °F)

Contact CAREL for other normal operating conditions or alternative refrigerants.

CAREL stator E

3

V-C

Two pole low voltage stator

Phase current

450 mA

Drive frequency

50 Hz (up to 150 Hz for emergency closing)

Phase resistance (25°C / 77°F)

36 Ohm ± 10%

Index of protection

IP67 with E2VCAB***

Step angle

15 °

Linear advance/step

0,02 mm (0,001 inches)

Connections

4 wires (AWG 18/22)

Complete closing steps

500

Control steps

480

概要説明

E3V-C 

電子バルブは、

CO

2

(R744)

冷媒の超臨界回路において圧力制御を行う目的で使用できます。

E3V-C 

の制御

用のは

CAREL

製のコントローラをご使用ください。

E3V-C

バルブは、下記に示す条件を外れたところで使わないで下

さい。

取付け位置

 E3V-C

は、片流れのバルブです。サイドの継手が入口です

 (Fig. 1

 

参照

)

上流側にシャットオフ弁を取付ける場合は、液

ハンマーがE3V-Cの近くで生じないように配管設計して下さい。

シャットオフ弁とE3V-Cを同時に閉弁すると危険な

液封状態となりますので、絶対に同時閉弁はしないで下さい。常に上流側にはフィルターを取付けて下さい。バル

ブは、ステータが下向き(バルブが逆さま状態)にならない限りどんな姿勢でも取付け可能です。

溶接時の注意

E3V-C

は、正しい流れ方向に回路に溶接接続する必要があります。

Fig.2

を参照しながら、下記の説明に従って溶接作業をお願いします。

1.

パッケージからバルブを取り出します。

2.

本体とカートリッジが組みあがっている場合は、カートリッジを取り外して下さい。

3.

バルブに濡れ雑巾を巻き付けて、炎を継手端部方向に向けてバルブがオーバーヒートしないように溶接します。

溶融温度が

700

℃以下のロウ材を使って下さい。他の方法で溶接を行う場合は、バルブ本体の温度が100℃を越

えない様にして下さい。固形異物がバルブ内に残らない様にして下さい。

適切な不活性ガスと、フラックスを

使って下さい。

4.

オーリングがカートリッジにきちんとついていることを確認します

(Fig. 2-B)

5.

金属製メッシュフィルターが、カートリッジに挿入されていることを確認します

(Fig. 2-B)

。外れている時は、十

分に奥まで挿入します。

6.

最初は手でカートリッジを本体にねじ込みます。

Fig.2-C

に示すように手でねじ込んでいくと3mm位の隙間が残り

 

ます。注意

!

 

この位置までは手の力で容易に簡単にねじ込めます。そうでない場合、シャッターが適切にオリ

フィスに挿入していない可能性があります。

7.

8. 

次にスパナで締め付けます。推奨トルク

60 Nm 

でカートリッジを本体に締めこみます

(Fig. 2.d).

。注意

!

 N

シャッ

ターが適切にオリフィスに収まっていないとカートリッジを壊してしまう可能性があります。

迅速に組立てを行うためには、モータをカートリッジから取り外さないで行うことを推奨します。もし、モータ

を外してから組み立てる場合は、赤色のステータを十分にカートリッジに挿入し、黒色のキャップをゴムリング

が変形するくらいしっかりとねじ込んでください

 (

推奨トルク

 0,3 Nm)

9.

配線済みのコネクタをステッパーモータの

ソケット部にFig.3に示すように締付けトルク0.5Nmでねじ留めします。

次に4ピンの反対側を

CAREL

製ドライバ

 EVD*** 

または、

CAREL

の認証するコントローラの該当端子に接続します。

その後、下記に示す内容でパラメータを設定します。

モデル

最少ステップ数 最大ステップ数

閉弁ステップ数 ステップ

/

相電流 

mA

保持電流 

mA

デューティー比

%

0

CAREL E

X

V

50

480

500

50

450

100

30

電子膨張弁用の

  Carel 

製コントローラは、弁閉時にステップ時間を短縮するためにデューティサイクルを

30% 

100% 

に上げます。さらにこの速度を上げるために最大励磁速度の

150

ステップ

/

秒に制御できます。ドライバ

のパラメータ設定についてはコントローラのマニュアルを参照下さい。

警告

もし、ロッドが完全にカートリッジソケットから出てきている時は、次のように対応ください。

モータを外しておいてロッドをカートリッジにカチッと音がするまで(アンチローテーション装置が位置決めを

終了した音)回しながら押し込みます。

モータをカートリッジに挿入し、下記の電気接続の説明に沿って

 CAREL

のドライバに接続します。

ドライバをマニュアル操作し、全開ステップ数として480を設定します。ステップシーケンスを始めるとロッド

が自分自身の位置をアンチローテーションガイド内で正しい位置に収まります。

弁、又は、接続配管をねじったり引っ張ったりしないで下さい。弁をハンマーあるいはその他の物で叩かないで下

さい。外部の構造が変形したり内部の部品の破損原因となるペンチあるいはその他の工具を使わないで下さい。弁

に火炎をあてないで下さい。弁は磁気製品に近づけないで下さい。次の場合、弁の取付や使用をしないで下さい。

外部の構造が変形、破損したとき

製品落下など、強烈な衝撃があったとき

電子部品は破損されたとき(ステーター、コンタクトキャリア、コネクターなど)

 

外部構造の変形や電子部品の破損が出た場合、

CAREL

は弁の稼動を保証いたしません。

 

重要:粒子状ゴミが付着す

ると、弁の故障の原因に成ります。

電気接続

モールドキャップの

IP67 

コネクタ

(E2VCAB0***) 

に接続します。ピン番号は、

1

(緑)、

2

(黄色)、

3

茶色)、

4

(白)

です。モータの

4

相をドライバの端子に接続しますが、相

1

がドライバの端子

1

というように接続します。重要

4

弁のステーターにアースのマークを表示しています。

  EEC

指令

89/336

の要求とその後の修正説明によって、電磁干渉

により影響を受ける応用について、オプションのシールド式コネクター(

E2VCABS***

)を提供することができます。

標準的コネクタの

 DIN 43650 

は、バルブの最適性能を保証できないため使用しないでください。

CAREL E

3

V-C

の仕様

適合冷媒

R744 (

鉱物油は不可

)

最高使用圧力

 (MWP)

140 barg (2031 PSIg)  -  (UL/CSA, MWP=1740PSIg/120 barg)

最高作動圧力差

 (MOPD)

90 barg (1305 PSIg)

P.E.D.

Gr. 2, art. 

4

, par. 3

流体温度

-40T65°C (-40T149°F)

周囲温度

-30T50 °C (-22T122 °F)

上記以外の条件や冷媒でご使用の場合は、

CAREL 

までご相談ください。

CAREL E

3

V-C

のステータ

低電圧バイポーラステータ

相電流

450 mA

駆動周波数

50 Hz (

緊急閉弁時は

150 Hz

まで

)

相抵抗

 (25 °C)

36 Ohm ± 10%

保護等級

IP67

E2VCAB***

を使用時

ステップ角

15 °

リニア直進

/

ステップ

0,02 mm (0,001 inches)

接続

4 fi li (AWG 18/22)

全閉ステップ数

500

制御ステップ数

480

Fig. 2

JPN

重要

Carel

では、

Carel

製ドライバのみをご

使用いただく場合に限って、

Carel 

ExV

の正しい操作を保証します。

 

Carel ExVs

を他メーカーのドライバで

ご使用される場合、事前に

Carel

の同

意が無い限り、自動的に保証が無効

になります。

詳細については、この製品をインス

トールする前に「

EEV

システムの操作

マニュアル(コード

+030220811

)」

をお読みください。

 

このマニュアル

は、

www. 

carel.com

の「ドキュメン

ト」ダウンロードエリアで入手でき

ます。

IMPORTANT

Carel guarantees the correct opera-
tion of the Carel ExV, if driven by Carel 
drivers only. The use of the Carel ExVs 
with other manufacturers driver, if not 
expressely agreed with Carel, will auto-
matically void the warranty.

For more information, read the “EEV 
systems operating manual (code 
+030220811) before installing this pro-
duct. The manual is available in the “do-
cumentation” download area at www.
carel.com.

JPN