background image

 User manual for APPEB1012 Revision 1.2, Oct 2019 

Solar Energy Harvesting Supercapacitor Evaluation Board using a 
PMIC with MPPT 

© CAP-XX Pty Limited 2019  |  Tel +61 2 9420 0690  |  www.cap-xx.com 

Page 

10

 of 

11

 

PMIC controlled output voltage 

When  the  PMIC  controlled  output  mode  (CTRL)  is  selected,  the  voltage  range  of  which  output 
enables  is  determined  by  the  charge  management  configuration.  The  upper  threshold  is  Vchrdy 
which enables the output voltage to the load whilst the output is disabled typically 600ms after the 
supercapacitor voltage drops below Vovdis. 

 

Figure 9: Example output voltage operation 

In  figure  9,  HA102  is  connected  to  the  APPEB1012  and  the  supercapacitor  voltage  and  output 
voltage was observed. The system configuration was connected as CFG[2:0] = [0 0 0] such that 
the PMIC entered custom mode as described in table 3. Custom external resistors were chosen to 
create the charge management equal to the first row of table 4. 

In this example, Vovch = 2.7; Vchrdy = 2.57V; Vovdis = 2.2V and a constant current of 100mA was 
drawn as the load. Furthermore, a power supply limited at 50mA was used as a representation of a 
solar cell.  

Since the lower threshold of the output voltage is 600ms after the Vscap falls below Vovdis we can 
calculate the lower threshold from 

𝑖

=

𝐶

𝑣

𝑡

 

Where 

𝑖

 is the load current, 

𝐶

 is the capacitance of the supercapacitor, 

𝑣

 is the voltage drop and 

𝑡

 is the time taken. Since a HA102 is 0.24F, using the above equation, we can calculate the lower 

threshold voltage to be 

𝑉

!"#$%

=

𝑉

!"#$%

𝑖

𝐶

𝑡

 

=

2

.

2

𝑉

0

.

1

𝐴

0

.

24

𝐹

×

0

.

6

𝑠

 

=

1

.

95

𝑉

 

Hence, the lower and upper output voltage thresholds are at 1.95V and 2.57V as seen in figure 9. 

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0

0.5

1

1.5

2

2.5

3

-2.5

2.5

7.5

12.5

17.5

22.5

Cu

rre

nt

 (A

)

V

oltage

 (V)

Time (s)

APPEB1012 100mA discharge

Vout
Vscap
Current
MPP
[1:0]
Vmpp / Voc

Output is 

enabled back 

Output is disabled

600ms after 

Vscap falls below 

Vovdis

Boost mode

Summary of Contents for APPEB1012

Page 1: ...uation Board using a PMIC with MPPT CAP XX Pty Limited 2019 Tel 61 2 9420 0690 www cap xx com Page 1 of 11 Evaluation board user manual APPEB1012 User Manual for APPEB1012 Solar Energy Harvesting Supe...

Page 2: ...with Open circuit voltage sensing for MPPT every 5s Configurable MPPT with 2 pin programming Selectable Vppt Voc ratio of 70 75 85 90 Vin operation from 50mV to 4 5V Configurable cell voltage control...

Page 3: ...xternal resistors that can be used to set these voltages to other values The output of the board can be either directly connected to a load or controlled by the PMIC The PMIC enables the output when t...

Page 4: ...supercapacitor DIR or controlled by the PMIC CTRL When the direct output is chosen on JP3 output control PFETs M3 M5 are bypassed and M3 M4 and M5 are OFF only drawing 200nA leakage current When the...

Page 5: ...CAP XX prismatic dual cells are installed in the same direction Please ensure that the active balance configuration header is connected to the cell midpoint as shown in red in figure 3 below Figure 3...

Page 6: ...eader must be connected to GND as shown in red on the left of figure 5 When 2 CAP XX cylindrical supercapacitors are connected as dual cells both supercapacitors should be fitted with their correct po...

Page 7: ...e LDO outputs one high and one low voltage are accessible from the LVOUT and HVOUT headers with voltages Vlv and Vhv respectively to supply circuits that require a stable voltage If enabled LVOUT and...

Page 8: ...rs that set custom mode All six configuration resistors shown in Figures 6 and 7 must be installed as follows Vovch Vchrdy and Vovdis are defined by R2 R3 R5 and R6 If we define the total resistor RT...

Page 9: ...reshold voltages to be different from the PMIC inbuilt options Table 4 Example resistor values for typical use Output mode selection APPEB1012 has two output modes either directly connect the output t...

Page 10: ...e 3 Custom external resistors were chosen to create the charge management equal to the first row of table 4 In this example Vovch 2 7 Vchrdy 2 57V Vovdis 2 2V and a constant current of 100mA was drawn...

Page 11: ...1 changes from low to high to warn that the system will soon shut down and 600ms later when shutdown occurs STATUS 1 and STATUS 0 both go from high to low This is illustrated in figure 10 Figure 10 Ex...

Reviews: