6
1. Plug the power cord into the wall socket and turn on the power
to the heater, see figure 1. Refrain from using an extension
cord.
2. For control lay-out refer to figure 2
3. To turn heater on press switch to POWER ON position. There
is a 5 second delay before the burner ignites. At this setting the
burner is on LOW and the fan speed is on LOW. Refer
figure 3.
The burner will ignite on both HIGH and LOW settings.
4. To turn burner to HIGH setting, press switch for HIGH setting.
Refer figure 4.
.
User instructions
Operating instructions
1
2
4
3
15
23.Gas control layout is as indicated in figure 26.
Pressures for ‘Burner full on’ and ‘Burner low flame’ are factory
set, however if pressures need to be checked or adjusted fol-
low the procedures described below and on the next two pages.
To check control outlet pressure at burner ‘Full on” and ‘Low
Flame” positions remove the plastic cap from the regulator ad-
justment location as indicated in figures 27 (a) & (b).
24 The pressure point is closed with a captive screw. Turn screw 6
revolution anticlockwise to open the pressure point as indicated
on figure 28 (a) and place manometer tube over the test point
as per figure 28 (b).
26
27
28
Gas control
Gas pressure point