background image

2

Contents

Contents

2

Warranty

3

Safety warnings

4-5

What to do if you smell gas

Warnings

Standards

User instructions

6-8

Operating instructions

Cleaning

Heater specifications

9

Installation instructions

10-12

Clearances

Installation into a masonry fire place

Sealing

Gas connection

13-14

Fuel bed and log installation

Gas control

15-16

Gas pressure point

Gas pressure sdjustment

Service instructions

17

General

To replace the gas control

To replace the fan

To replace the electronic controller

To remove the burner and electrodes

To check pressures

Trouble shooting

18-19

Connections

Electric wiring diagram

Authorised service agents

19

9

No gas to burner.

• The gas valve should open at the same time as the

igniter sparks. If there is no gas to the burner when

this occurs check the solenoid coils for continuity.

• Check that the gas pressure is present at the test

point when the spark is being generated.

• Check that there is gas to the inlet of the gas control.

10

Appliance lights but goes

• Test the flame for correct ionisation signal. Connect a

into lockout.

multimeter in series with the flame rod and set the

function to measure micro-amps. The module will go

into lockout if the flame current sensitivity is less than

0.5 micro-amps. The approximate signal strength on

high flame is about 10 micro-amps and on low

4  micro-amps. The signal strength will fluctuate but

should be greater than 1.5 micro-amps at all times.

Take precaution because the ionisation probe can

have a high negative voltage and can cause shock.

11

Fuse blowing.

• If the fuse continues to blow check the solenoid coils

for signs of them being shorted.

• Check the fan is and wiring for short circuit.

Terminals 5, 6 and 7 at the module 12 way connector are bridged.

Terminal 10 at the module 12 way connector is the active supply

via the red wire.

Terminal 11 at the module 12 way connector is the neutral supply

via the blue wire.

Terminal 12 at the module 12 way connector is the earth connec-

tion via the green/yellow wire.

Terminal 12 at the module 2 way connector is the neutral connec-

tion via a brown wire which is joined into the rectifier cable then

into the 8 way switch connector blue wire.

Terminal 14 is an active connection at the module 2 way connector

via a white wire into the 8 way switch connector. This is active only

when the flame is sensed.

Connections

31

Summary of Contents for CANTIB

Page 1: ...approved for use with Natural and Propane gases Please leave instructions with the owner INBUILT MODELS CANTIB CANTIBLP CANTIBM CANTIBMLP USER INSTRUCTIONS INSTALLATION INSTRUCTIONS SERVICE INSTRUCTI...

Page 2: ...ces Installation into a masonry fire place Sealing Gas connection 13 14 Fuel bed and log installation Gas control 15 16 Gas pressure point Gas pressure sdjustment Service instructions 17 General To re...

Page 3: ...accordance with manufacturer s instructions this warranty may be void The customer must keep their Tax Invoice as proof of purchase of this product and compliance certificate as proof of required inst...

Page 4: ...ains clothing furniture and other flammable mate rials at least 900mm from front and sides of the heater At the owner s discretion curtain clearance can be less than 900mm as long as they are restrain...

Page 5: ...nnually to be made by a licensed service per son It is important that circulating air passageways of the appliance be kept clean dirt and lint free for a safe and efficient operation of the heater 12...

Page 6: ...2 3 To turn heater on press switch to POWER ON position There is a 5 second delay before the burner ignites At this setting the burner is on LOW and the fan speed is on LOW Refer figure 3 The burner...

Page 7: ...itch for HIGH setting Refer figure 6 7 To turn the burner to LOW setting press switch for LOW setting Refer figure 7 On low burner setting it is more efficient to operate the fan speed on LOW 8 If the...

Page 8: ...f your heater requires attention contact your supplier or licensed service person listed in this manual Important The appliance should be inspected before use and at least annu ally by an authorised s...

Page 9: ...ropane gas Regulated to supply 2 70 kPa to appliance Fan Three speed Controller Electronic Minimum cavity Height 605mm dimensions dimensions Width 695mm Depth 385mm Power requirement 240 VAC 10 A Opti...

Page 10: ...om sides and front of heater For minimum clearances refer fig 9 and 10 Note Ensure that the combustion air opening under the heater is not obstructed 4 Models CANTIB CANTIBLP should only be installed...

Page 11: ...d 9 Disconnect the switch loom connector from the loom plug 10 To remove the front heater surround undo two s t screws one either side from the bottom flange of the front panel as indi cated in figure...

Page 12: ...efer figure 17a Seal with fibreglass between bottom of heater case and base of fireplace 13 Slide heater into the fireplace ensuring that gas inlet pipe is fed through the hole at the rear bottom RHS...

Page 13: ...bed is retained by a spring clip fixed to the rear of the burner chamber FUEL BED MUST BE HARD UP AGAINST REAR OF BURNER 17 Carefully unpack the log set Logs are numbered as follows No 1 Left front l...

Page 14: ...No 3 log see figure 24 18 Refit the inner glass making sure not to overtighten the screws 19 Refit the front glass surround Ensure that the glass surround is replaced the correct side up The rearward...

Page 15: ...wo pages To check control outlet pressure at burner Full on and Low Flame positions remove the plastic cap from the regulator ad justment location as indicated in figures 27 a b 24 The pressure point...

Page 16: ...for Natural Gas and 1 1 kPa for LPG Turn clock wise to increase pressure and anti clockwise to decrease pressure 27 Switch burners off and remove the manometer tube Tighten pressure test point by tur...

Page 17: ...fixing the fan to the burner chamber underside 3 Replace in reverse order 1 Remove two screws from controller front 2 Disconnect plug 3 Replace in reverse order 1 Follow steps 7 to 11 of the installat...

Page 18: ...roduced Check that spark lead is connected into module Check the continuity of the HT cable Check that there is no short circuit to earth and spark gap is correct Refer figure 31 A positive check is t...

Page 19: ...han 1 5 micro amps at all times Take precaution because the ionisation probe can have a high negative voltage and can cause shock 11 Fuse blowing If the fuse continues to blow check the solenoid coils...

Page 20: ...N dis tributor in your state Sampford Staff Pty Ltd 421 Smith Street Fitzroy Vic 3065 Vic Tas 03 9418 5800 NSW 02 9331 8888 SA NT 08 8212 7000 Qld 07 3358 3000 WA 08 9242 5333 ACT 02 6280 4177 Elsewhe...

Reviews: