1. This appliance is to be installed by a licensed service person only.
2. This appliance shall be installed in accordance with the manufacturer’s

installation instructions, local gas fitting regulations, municipal building

codes, electrical wiring regulations, and AS5601 the Australian Stand-

ard for gas installations. Refer also to AS5601 for pipe sizing tables.

3. Remove the heater from the carton and remove the three transit screws.

Check that the heater is suitable for gas available. Refer to the data

label located on the fan chamber base, rear of pedestal front.
(Please dispose of packaging appropriately, keep packaging away

from children).

     Clearances

4. Ensure the minimum clearances to combustible construction are main-

tained during installation, including adequate space for the proper

operation and servicing of the heater.
Keep curtains*, furniture and other flammable materials at least 900mm

from front of heater.
* Curtain clearance can be less than 900mm as long as they

are restrained from sides and front of heater.
For minimum clearances refer fig 9 and 10.
Note: Ensure that the combustion air opening under the heater

is not obstructed.

 

A CLEARANCE OF 50

MM

 MUST BE MAINTAINED BETWEEN THE

REAR OF THE CABINET AND THE REAR WALL OF THE FIREPLACE.

     Installation into a masonry/brick or mock fireplace.

5. Models CANTIB-NG & CANTIB-LP can be installed onto a masonry/

brick fireplace or mock fireplace. If installing into a mock fireplace a

mock fireplace installation kit MUST be used. The mock fireplace instal-

lation  kit can be ordered from the CANNON distributor. Order speci-

fication for the part is ‘MOCKKITRO’.
For installation onto a masonry or brick fireplace WITH a flue connec-

tion refer figure 11. For installation WITHOUT a flue connected refer

figures 12 & 13. After installation of the heater/flue test the flue to

confirm air vents are unobstructed. If an exhaust fan or other heating

appliances are present switch them on. This is to test that there is no

interaction between the CANNON heater and other appliances.

10

9

Installation instructions

15

     Gas connection

13. Slide heater into the fireplace ensuring that gas inlet pipe is fed through

the hole at the rear bottom RHS of the heater. Refer figure 22 and gas

connection figure 24.

-

14.With heater in position, flanges should be hard against masonry. Se-

cure case flanges to masonry. Refer figure 23.

15. Connect incoming gas supply pipe to regulator. For inlet position see

figure 24. Close gate over gas supply and seal around the pipe with

fibreglass insulation material. Sealing is important as it prevents leak-

age from fan chamber into chimney: also check for gas soundness.

         

20

23

22

24

Summary of Contents for CANTERBURY

Page 1: ...annon This heater is approved for use with Natural and Propane gases Please leave instructions with the owner CANTERBURY INBUILT MODELS USER INSTRUCTIONS INSTALLATION INSTRUCTIONS SERVICE INSTRUCTIONS...

Page 2: ...d Installation WITHOUT a flue connected Sealing Gas connection Log installation 16 17 Fuel bed and log installation Gas control 17 19 Gas pressure point Gas pressure adjustment Installation tips 19 Se...

Page 3: ...serial plate will have it s warranty voided If installation is not carried out in accordance with manufacturer s instruc tions this warranty may be void The customer must keep their Tax Invoice as pr...

Page 4: ...curtains clothing furniture and other flammable materials at least 900mm from front and sides of the heater At the owner s discretion curtain clearance can be less than 900mm as long as they are rest...

Page 5: ...esent switch them on This is to test that there is no interaction between the Cannon heater and other appliances Refer AS5601 For air movement not to affect appliance see clause 5 3 1 For air supply t...

Page 6: ...lay out refer to figure 2 3 To turn heater on press switch to POWER ON position There is a 5 second delay before the burner ignites At this setting the burner is on LOW and the fan speed is on LOW Ref...

Page 7: ...setting Refer figure 7 On low burner setting it is more efficient to operate the fan speed on LOW 8 If the burner fails to ignite wait 20 seconds and repeat the ignition procedure See below To turn b...

Page 8: ...pplier or authorised service person listed in this manual Flame characteristics The heater flame should be stable no lifting from the burner and the logs should glow after approximately 15 minutes ope...

Page 9: ...10 Amp Power consumption 90 VA maximum Minimum cavity Height 605mm dimensions dimensions Width 695mm Depth 385mm Power requirement 240 VAC 10 A Optional Accessories Safety guard Gold trim Mock firepl...

Page 10: ...n clearance can be less than 900mm as long as they are restrained from sides and front of heater For minimum clearances refer fig 9 and 10 Note Ensure that the combustion air opening under the heater...

Page 11: ...1 Refer AS5601 For air movement not to affect appliance see clause 5 3 1 For air supply to appliance see clause 5 4 1 For ventilation requirements see clause 5 4 3 11 Installation WITH a flue connecte...

Page 12: ...12 Installation WITHOUT a flue connection 12 13...

Page 13: ...ng it firmly on either side and pulling it towards yourself see figure 15 8 Remove the lower front cover by unscrewing two M5 screws through the air intake slots see figure 16 If unit is fitted with s...

Page 14: ...Refer figure 20 Sealing 12 All gaps between heater case and fireplace are to be sealed Seal with foam tape around top and sides of heater flange as required Refer figure 21 Seal with fibreglass betwe...

Page 15: ...h heater in position flanges should be hard against masonry Se cure case flanges to masonry Refer figure 23 15 Connect incoming gas supply pipe to regulator For inlet position see figure 24 Close gate...

Page 16: ...The male locating pins on the burner head must engage with corresponding holes in the indi vidual logs a Place log No 1 onto the 2 front left pins on the burner head ensuring that the charring faces...

Page 17: ...cated in figure 31 Pressures for Burner full on and Burner low flame are factory set however if pressures need to be checked or adjusted follow the procedures described below and on the next two pages...

Page 18: ...se pressure 26 Switch the stop button back to Low Flame position as indicated in figure 35 a retain spanner in position and using a screwdriver as per figure 35 b adjust the central screw control to g...

Page 19: ...g of the chimney and fireplace before the installation of a new heater There must be a good seal around the heater gas piping and electrical cable rear entry to stop any leakage of combustion products...

Page 20: ...w re moval of the gas control Remove LH screw from front lower section of ignition device Remove screw from front of rectifier lead located below domed cap on gas control 3 Unplug polarise plug wires...

Page 21: ...he burner should now operate on high setting To replace the fan pressure switch 1 Remove the lower fan cover by unscrewing two M5 screws through the air intake slot Refer page 13 figure 16 of the inst...

Page 22: ...um until the flame has been established Terminal 13 white wire into the 8 way switch connector will be energised as soon as the flame has been sensed 5 Confirm spark is produced A blue spark can be se...

Page 23: ...will go into lockout if the flame current sensitivity is less than 0 5 micro amps The approximate signal strength on high flame is about 10 micro amps and on low 4 micro amps The signal strength will...

Page 24: ...For service to this appliance or spare parts contact the CANNON distributor Sampford IXL spare parts 52 70 Sparks Avenue Fairfield Vic 3078 Phone 1300 727 421 Fax 1300 727 425 email service sampfordix...

Reviews: