background image

2

Contents

Contents

2

Warranty

3

Distributor

Safety warnings

4-5

What to do if you smell gas

Warnings

Standards

User instructions

6-8

Operating instructions

Cleaning

Flame characteristics

Heater specifications

9

Installation instructions

10-15

Clearances

Installation into a masonry/brick or mock fireplace

Installation WITH a flue connected

Installation WITHOUT a flue connected

Sealing

Gas connection

Log installation

16-17

Fuel bed and log installation

Gas control

17-19

Gas pressure point

Gas pressure adjustment

Installation tips

19

Service instructions

20-21

General

To replace the primary glass

To replace the gas control

To replace the fan

To replace the electronic controller

To remove the burner and electrodes

To check pressures

Trouble-shooting

22-24

Connections

Electric wiring diagram

Data plate

Date installed, Compliance Certificate No.

For service to this appliance

23

8.

Sparks, ignites on low flame

• Check that the wall socket to the appliance has

then extinguishes after 10

correct polarity. Do not use an extension cord. Check

seconds. Continues to spark

polarity in the electrical supply lead to appliance.

during flame presence.

• Check that the sense electrode is in the flame.

• Check that appliance is earthed correctly. A check

between the earth pin on the plug and an unpainted

part of the appliance should see a resistance of

0.1 ohms.

9.

No gas to burner.

• The gas valve should open at the same time as the

igniter sparks. If there is no gas to the burner when

this occurs check the solenoid coils for continuity.

• Check that the gas pressure is present at the test

point when the spark is being generated.

• Check that there is gas to the inlet of the gas control.

10.

Appliance lights but goes

• Test the flame for correct ionisation signal. Connect a

into lockout.

multimeter in series with the flame rod and set the

function to measure micro-amps. The module will go

into lockout if the flame current sensitivity is less than

0.5 micro-amps. The approximate signal strength on

high flame is about 10 micro-amps and on low

4  micro-amps. The signal strength will fluctuate but

should be greater than 1.5 micro-amps at all times.

Take precaution because the ionisation probe can

have a high negative voltage and can cause shock.

11.

Fuse blowing.

• If the fuse continues to blow check the solenoid coils

for signs of them being shorted.

• Check the fan and wiring for short circuit.

Connections

Terminals 5, 6 and 7 at the module 12 way connector

are bridged.

Terminal 10 at the module 12 way connector is the ac-

tive supply via the red wire.

Terminal 11 at the module 12 way connector is the neu-

tral supply via the blue wire.

Terminal 12 at the module 12 way connector is the earth

connection via the green/yellow wire.

Terminal 12 at the module 2 way connector is the neutral

connection via a brown wire which is joined into the

rectifier cable then into the 8 way switch connector blue

wire.

Terminal 14 is an active connection at the module 2 way

connector via a white wire into the 8 way switch connec-

tor. This is active only when the flame is sensed.

36

Summary of Contents for CANTERBURY

Page 1: ...annon This heater is approved for use with Natural and Propane gases Please leave instructions with the owner CANTERBURY INBUILT MODELS USER INSTRUCTIONS INSTALLATION INSTRUCTIONS SERVICE INSTRUCTIONS...

Page 2: ...d Installation WITHOUT a flue connected Sealing Gas connection Log installation 16 17 Fuel bed and log installation Gas control 17 19 Gas pressure point Gas pressure adjustment Installation tips 19 Se...

Page 3: ...serial plate will have it s warranty voided If installation is not carried out in accordance with manufacturer s instruc tions this warranty may be void The customer must keep their Tax Invoice as pr...

Page 4: ...curtains clothing furniture and other flammable materials at least 900mm from front and sides of the heater At the owner s discretion curtain clearance can be less than 900mm as long as they are rest...

Page 5: ...esent switch them on This is to test that there is no interaction between the Cannon heater and other appliances Refer AS5601 For air movement not to affect appliance see clause 5 3 1 For air supply t...

Page 6: ...lay out refer to figure 2 3 To turn heater on press switch to POWER ON position There is a 5 second delay before the burner ignites At this setting the burner is on LOW and the fan speed is on LOW Ref...

Page 7: ...setting Refer figure 7 On low burner setting it is more efficient to operate the fan speed on LOW 8 If the burner fails to ignite wait 20 seconds and repeat the ignition procedure See below To turn b...

Page 8: ...pplier or authorised service person listed in this manual Flame characteristics The heater flame should be stable no lifting from the burner and the logs should glow after approximately 15 minutes ope...

Page 9: ...10 Amp Power consumption 90 VA maximum Minimum cavity Height 605mm dimensions dimensions Width 695mm Depth 385mm Power requirement 240 VAC 10 A Optional Accessories Safety guard Gold trim Mock firepl...

Page 10: ...n clearance can be less than 900mm as long as they are restrained from sides and front of heater For minimum clearances refer fig 9 and 10 Note Ensure that the combustion air opening under the heater...

Page 11: ...1 Refer AS5601 For air movement not to affect appliance see clause 5 3 1 For air supply to appliance see clause 5 4 1 For ventilation requirements see clause 5 4 3 11 Installation WITH a flue connecte...

Page 12: ...12 Installation WITHOUT a flue connection 12 13...

Page 13: ...ng it firmly on either side and pulling it towards yourself see figure 15 8 Remove the lower front cover by unscrewing two M5 screws through the air intake slots see figure 16 If unit is fitted with s...

Page 14: ...Refer figure 20 Sealing 12 All gaps between heater case and fireplace are to be sealed Seal with foam tape around top and sides of heater flange as required Refer figure 21 Seal with fibreglass betwe...

Page 15: ...h heater in position flanges should be hard against masonry Se cure case flanges to masonry Refer figure 23 15 Connect incoming gas supply pipe to regulator For inlet position see figure 24 Close gate...

Page 16: ...The male locating pins on the burner head must engage with corresponding holes in the indi vidual logs a Place log No 1 onto the 2 front left pins on the burner head ensuring that the charring faces...

Page 17: ...cated in figure 31 Pressures for Burner full on and Burner low flame are factory set however if pressures need to be checked or adjusted follow the procedures described below and on the next two pages...

Page 18: ...se pressure 26 Switch the stop button back to Low Flame position as indicated in figure 35 a retain spanner in position and using a screwdriver as per figure 35 b adjust the central screw control to g...

Page 19: ...g of the chimney and fireplace before the installation of a new heater There must be a good seal around the heater gas piping and electrical cable rear entry to stop any leakage of combustion products...

Page 20: ...w re moval of the gas control Remove LH screw from front lower section of ignition device Remove screw from front of rectifier lead located below domed cap on gas control 3 Unplug polarise plug wires...

Page 21: ...he burner should now operate on high setting To replace the fan pressure switch 1 Remove the lower fan cover by unscrewing two M5 screws through the air intake slot Refer page 13 figure 16 of the inst...

Page 22: ...um until the flame has been established Terminal 13 white wire into the 8 way switch connector will be energised as soon as the flame has been sensed 5 Confirm spark is produced A blue spark can be se...

Page 23: ...will go into lockout if the flame current sensitivity is less than 0 5 micro amps The approximate signal strength on high flame is about 10 micro amps and on low 4 micro amps The signal strength will...

Page 24: ...For service to this appliance or spare parts contact the CANNON distributor Sampford IXL spare parts 52 70 Sparks Avenue Fairfield Vic 3078 Phone 1300 727 421 Fax 1300 727 425 email service sampfordix...

Reviews: