
16
9
A CLEARANCE OF 50mm MUST BE MAINTAINED BETWEEN THE
CABINET AND THE REAR WALL OF THE FIREPLACE.
REAR OF THE
Installation into a masonry/brick or mock fireplace.
5.Models CANTIB-NG & CANTIB-LP can be installed onto a masonry/
brick fireplace
or mock fireplace. If installing into a mock fireplace a mock fireplace installation kit
MUST be used. The mock fireplace installation kit can be ordered from the CANNON
distributor. Order specification for the part is ‘MOCKKITRO’.
10
9
Installation instructions
18. Refit the inner glass, making sure not to overtighten the screws.
19. Refit the front glass surround. Ensure that the glass surround is replaced
the correct side up. The rearward sloping frame must be at the top and
the vertical ledge must be at the bottom. Refer figure 30.
20. Reconnect the switch loom to the loom plug.
21. Refit the front glass surround.
22. Connect plug to the wall socket and switch it on.
23. Gas control layout is as indicated in figure 31.
Pressures for ‘Burner full on’ and ‘Burner low flame’ are
factory set, however if pressures need to be checked or
adjusted follow the procedures described below and on the
next two pages.
To check control outlet pressure at burner ‘Full on” and ‘Low Flame”
positions remove the plastic cap from the regulator adjustment location
as indicated in figures 32(a & b).
Gas control
30
31
32
Advise the user in
the operation of the
heater
Important:
To achieve the correct
visual flame effect:
On Propane the gas
pressure must be set
at 2.65 kPa with
burner operating on
maximum setting.
On Natural Gas the
gas pressure must be
set at 0.75 kPa.
Plastic Cap
Pressure adjustment
(Burner ‘Full on’)
Burner adjustment
(Burner ‘Low flame’)
Pressure test point
with captive screw
1. This appliance is to be installed by an authorised service person only.
2. This appliance shall be installed in accordance with the manufacturer’s Installation
instructions, local gas fitting regulations, municipal building codes, electrical wiring
regulations, and AS5601 the Australian Standard for gas installations.
Refer also to AS5601 for pipe sizing tables.
3. Remove the heater from the carton and remove the three transit screws.
Check that the heater is suitable for gas available. Refer to the data label located on
fan chamber base, rear of lower front cover.
(Please dispose of packaging appropriately, keep away from children).
Clearances
4. Ensure the minimum clearances to combustible construction are maint a ined during
installation, including adequate space for the proper operation and servicing of the
heater. For clearances to furniture and curtains refer to warning on page 4.
For minimum clearances refer figures 10 and 11.
Note: Ensure that the combustion air opening under the heater is not obstructed.
Fitment of cabinet depth spacer
The clearance is required for correct fluing of the appliance. If the
than 50mm a cabinet depth spacer must be fitted. The spacer can be ordered from the
Cannon distributor.
Order specification for the spacer is ‘BSPACERX-B’ (black finish) or ‘BSPACERX-P’
(platinum finish).
clearance is less
Opening for heater -
745 - 780 wide,
630 - 650 mm high