6. Normal operation
6. Normal operation
.45.
.44.
OV-G-V1:
300---480V
OV-G-V1-T: 0.01---9S
OV-G-V2:
300---490V
OV-G-V2-T: 0.01---1S
UN-G-V1:
173---336V
UN-G-V1-T: 0.01---9S
UN-G-V2:
132---319V
UN-G-V2-T: 0.01---1S
Startup-T: 10-600S
OV-G-F1: 50.2-63Hz
OV-G-F1-T: 0.01---9S
OV-G-F2: 51-63Hz
OV-G-F2-T: 0.01---9S
UN-G-F1: 47-59.5Hz
UN-G-F1-T: 0.01---9S
UN-G-F2: 47-59Hz
UN-G-F2-T: 0.01---9S
Restore-T: 10-600S
Table 6.2 Setting ranges for User-Def (L-N)
NOTE
The initial value of the User-Def standard is for reference only. It does
not represent a correct value suitable for use.
Table 6.3 Baseline Inverter Settings
Setting
value
Vup-Limit1
660<V<720
Time1
1S
Vup-Limit2
V
≥
720
Time2
0 16S
.
Vdw-Limit1
360
≤
V<528
Time1
2S
Vdw-Limit2
V<360
Time2
0 16S
.
Fup-Limit1
60
.
5Hz
<
F
<
62Hz
Time1
2S
Fup-Limit2
Time2
Fdw-Limit1
Time1
Fdw-Limit2
Time2
F
>
2Hz
6
0 16S
.
57Hz
<
F
<
59.5Hz
2S
57Hz
<
F
0 16S
.
600V Rated (L-N)
381<V<415
1S
V
≥
415
0 16S
.
207
≤
V<304
2S
V<207
0 16S
.
60
.
5Hz
<
F
<
62Hz
2S
F
>
2Hz
6
0 16S
.
57Hz
<
F
<
59.5Hz
2S
57Hz
<
F
0 16S
.
600V Rated (L-L)
6.7 Advanced Settings - Technicians Only
NOTE:
To access to this area is for fully qualified and accredited technicians only.
Please follow 6.4 to enter password to access this menu.
6.7
.
1 Selecting Standard
This function is used to select the grid's reference standard (see Figure 6.16).
YES=<ENT> NO=<ESC>
Standard:UL-600V
Figure 6.16
Selecting the “User-Def” menu will access to the following submenu (see Figure 6.17),
Figure 6.17
OV-G-V1: 400V
OV-G-V1-T: 1.0S
Below is the setting range for “User-Def”. Using this function, the limits can be changed
manually. (These voltage values are the phase voltage)
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard
2. Grid ON/OFF
3. Clear Energy
4. Reset Password
5. Power Control
6. Calibrate Energy
7. Special Settings
8. STD. Mode Settings
9
.
Restore Settings
10. HMI Update
11. Restart HMI
12. Debug Parameter
13. Fan Test
14. DSP Update
15. Compensation Set
16. I/V Curve