5
Table 3: DynaMax Wall Hung Service Clearances
Service Clearance, Inches (cm)
Input [BTU/hr]
Front
Top
Right Side
Left Side
Rear
80,000
24” (61cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
100,000
24” (61cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
150,000
24” (61cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
200,000
24” (61cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
250,000
24” (61cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
0” (0 cm)
Figure 3: DynaMax Wall Hung Model Dimensions
Table 4: Appliance Dimensions and Specifications
Equivalent Length of Vent & Air
Intake Pipes at Recommended
Diameter, [in.]
Input
[BTU/hr]
Depth Dim.
"A" [in.]
Dim.
"B"
[in.]
Over 25'
and up to
100'
Over 15'
and up to
25'
Up to 15'
Water
Conn [in.]
NPT
Gas Conn. At
Boiler [in.] NPT
80,000
16 1/2
12
3
3
2
1
1/2
100,000
16 1/2
12
3
3
2
1
1/2
150,000
16 1/2
12
3
3
2
1
1/2
200,000
23 1/2
19
3
3
2
1
1/2
250,000
23 1/2
19
3
3
2
1 1/4
1/2
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent
connections, water pipe connections, circulating pump, bypass piping and other auxiliary equipment, as well as the appliance