Simply turn of the main switch and turn it back 
on that would reset the entire system.  
  

5.  The  DFC+  will  always  display  the  current 

discharge air temperature. Press any arrow 
key  to  change  the  discharge  setpoint 
temperature. Once an arrow key is pressed, 
the LED will display the text for the current 
setpoint  temperature.  Use  the  down  or  up 
key  to  set  a  new  discharge  temperature, 
then  press  the  middle  key  to  save  the 
changes made. If a key is not pressed for 10 
seconds, the DFC+ will exit without saving. 
When adjusting the set point range, the set 
point cannot surpass the set Low and High 
values. That is 120°F to 250°F. 

 

WARNING  

If  unit  fails  to  ignite  or  function  properly; 

disconnect  fuel  and  power  supplies  and 
contact authorized service personnel. 

 

 

 

NOTE:  

If  the  blower  does  not  turn  on,  check 

the  control  braker 

(The “Power” indicator light 

will confirm  that the control  braker  is good) or 
make sure the VFD is energized.  

NOTE: 

 

Placing  the Main switch in the “OFF” 

position will automatically reset the heater if the 
control is in a lock out condition. If the burner 
still does not ignite, use the following sequence 
of steps:  
  
1.  Make sure the gas pressure is adequate.   
  
2.  Check to make sure all manual valves are 

open  between  the  fuel  source  and  the 
burner.   

  
3.  Check  to  make  sure  the  proper  voltage  is 

supplied to the heater.   

  

WARNING

 

 A qualified electrician must make the 
adjustments.

  

  
4.  Check  to  be  sure  the  air  proving  switch 

sensor tubes are clear of any obstructions.  

  

NOTE: 

 Listen to hear the pilot solenoid valve 

click.  If the click is not heard, the solenoid valve 

may  not  be  opening  and  may  be  defective. 
Sparking  should  also  be  present  at  the  spark 
igniter  in  the  burner  If  the  click  is  heard  and 
pressure is registered, move the main switch to 
the  “OFF”  position  and  place  the  Heat/Fan 
switch in the “center” position. Lockout power 
to the heater and check the following:  
  
1.  Check the igniter for corrosion and proper 

separation.    Be  sure  the  insulator  is  not 
cracked  and  is  properly  seated  in  the 
burner.    Check  the  connections  for  clean, 
dry,  and  tight  contact.  Check  the  ignition 
wire for cuts and cracks that may allow the 
spark voltage to jump to ground before the 
igniter.  Also  check that  the  ignition  wire  is 
securely 

fastened 

to 

the 

ignition 

transformer high voltage terminal.   

   
2.  Check  the  burner  ports  for  obstructions.  

Remove any obstruction.  

 
3.  Check  the  electrical  system  including 

wiring,  connections,  switches,  and  major 
electrical components.   

  
4.  Check  the  input  voltage  and  phase  to  the 

heater; adequate voltage and proper phase 
is necessary for proper function.   

  
5.  Restore power to the heater and place the 

Main switch in the "ON" position then place 
the Heat/Fan switch to 

‘HEAT’ position and 

allow the heater to go through its start up.   

  

NOTE: 

 If  the  burner  does  not  ignite  after  the 

start up, see TROUBLESHOOTING section.  
  

NOTE:

    The  thermostat  must  be  set  above 

ambient.  

 

 

 
Stopping Heater  

 

 

NOTE:

  if  the  heater  is  being  stopped  for  an 

extended period. 
  
1.  Turn manual inlet valve to OFF position.   
  

Summary of Contents for ECOBlaze DF1600

Page 1: ...t com pg 1 NG LP DIRECT FIRED SPACE HEATER BLAZE DF1600 WWW CAMPOEQUIPMENT COM REPORT 0367GH009S Installation Instructions Manual Maintenance Parts List CAUTION DO NOT TAMPER WITH HEATER OR ITS CONTROLS CALL A QUALIFIED SERVICE TECHNICIAN Retain manual for future reference May 19 2021 CERTIFIED FOR USE IN CANADA AND THE U S A ...

Page 2: ...s remain with the heater GENERAL HAZARD WARNING FAILURE TO COMPLY WITH THE PRE CAUTIONS AND INSTRUCTIONS PROVIDED WITH THIS HEATER CAN RESULT IN DEATH SERIOUS BODILY INJURY AND PROPERTY LOSS OR DAMAGE FROM HAZARDS OF FIRE EXPLOSION BURN ASPHYXIATION CARBON MONOXIDE POISONING AND OR ELECTRICAL SHOCK ONLY PERSONS WHO CAN UNDERSTAND AND FOLLOW THE INSTRUCTIONS SHOULD USE OR SERVICE THIS HEATER IF YOU...

Page 3: ...nsferable to any subsequent owner The warranty period is one year from the date of purchase The warranty covers all defects in material and workmanship insofar as they are of Campo Equipment CO LTD manufacture This warranty is limited to the furnishing of new parts only in the event the original part is determined to be defective by Campo Equipment CO LTD The warranty does not include transportati...

Page 4: ...erature is well below the material flash point Under no circumstance should any combustible material be stored in the airstream within 15 feet 4 57 m of the air discharge port or within 6 15 2cm of the top sides or ends of the heater WARNING This heater must be placed at least 10 Ft 3 05M from any LP Gas Container The discharge air stream of this heater must not be directed toward any LP Gas conta...

Page 5: ...hten any connection as necessary The supply gas hose being used must be protected from traffic building materials and contact with hot surfaces both during usage and while in storage The supply gas hose shall be visually inspected prior to each use of the heater If it is evident there is excessive abrasion or wear or the hose is cut it must be replaced prior to the heater being put into operation ...

Page 6: ...power supply compartment there are four CAM locks and a 3 Phase 250V 30 Amp male plug use either one of them When using the plug make sure that the CAM locks have caps on them The main power switch should be in the OFF positions This power source must include a Short Circuit protection device such as a circuit breaker or fusible With all connections secure including grounds energize the heater Pla...

Page 7: ...RNING A qualified electrician must make the adjustments 4 Check to be sure the air proving switch sensor tubes are clear of any obstructions NOTE Listen to hear the pilot solenoid valve click If the click is not heard the solenoid valve may not be opening and may be defective Sparking should also be present at the spark igniter in the burner If the click is heard and pressure is registered move th...

Page 8: ...g and gas codes When storing the heater indoors the gas connection between the heater and the supply cylinder must be disconnected Preparing After Extended Storage Several days or weeks before the heater will be used attention should be paid to properly preparing the heater for service Since the heater is an important element of your operation it only makes sense that a certain amount of time is n...

Page 9: ...Minimum flame results from zero volts DC The DF1600 heater has a minimum BTU input rating of 324538 BTUs on NG 81782 Kcal and 326289 BTUs 82223 Kcal on LP The Belimo Modulating System has been pre set at the factory to insure this input No field adjustment of this set point is required Conventional Remote Thermostat The optional remote thermostat if used connects to the remote thermostat receptacl...

Page 10: ...tory and should be changed by authorized service personnel only Igniter To start ignition the igniter must be adjusted properly and must not be damaged or defective Periodically the igniter should be inspected for damage corrosion and separation To inspect and adjust the igniter use the following procedure 1 Remove the igniter from the burner 2 Visually inspect the igniter for corrosion and damage...

Page 11: ...od Remember that the blower must be operating properly for the burner to operate The switch can be tested using an ohmmeter To test use the following procedure 1 Disconnect the main power supply open the Electrical Compartment 2 Set the ohmmeter in the continuity test mode 3 With the main switch in OFF position place one tester lead on the common contact and one tester lead on the contact relative...

Page 12: ... continuity light to the switch N O contacts Place the Heat Fan switch to FAN position The ohmmeter should read low resistance or the continuity light should come on When the blower is stopped the light should go out and the resistance reading should be high If the contacts remain closed regardless of the blower status the air switch must be replaced Contact the factory in the event the switch mus...

Page 13: ...there is power to the VFD Burner does not ignite 1 Voltage insufficient 1 Check incoming supply 2 Electrode disconnected adjusted incorrectly defective 2 Connect adjust replace electrode 3 Air Proving Sw Disconnected defective 3 Connect Replace Air Proving Sw 4 Tilt switch Disconnected or Unit is not on a level surface or defective 4 Connect Replace Tilt Switch or Level the Unit 5 Fan Over heat sw...

Page 14: ...ng Sw 5 Flame rod dirty defective 5 Clean Replace Flame Rod 6 Inadequate fuel delivery 6 Fill Tank replace regulators valves check gas lines for obstructions TROUBLESHOOTING DF1600 DIRECT FIRED HEATER PROBLEM CONDITION REMEDY Heater overheating 1 Gas pressure excessive 1 Adjust replace regulator 2 RTC Discharge Temperature Sensor defective 2 Replace sensor troubleshoot modulation system ...

Page 15: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com pg 15 WIRING DIAGRAM ...

Page 16: ...oltmeter C70064 3 POSITION SWITCH C70069 FIXING COLLAR C70067 N O CONTACT BLOCK C70028 VFD C70137 R Fan 500 C90025 Power On Indicator Light GREEN C90029 Outlet for Plug C70052 TILT SWITCH C82036 Spark Controller C80186 MAIN CONTROLLER C82163 Actuator ball valve 11 2 NPT C80916 12 Discharge Air tube C60139 Temperature Sensor c w Stew C82164 Bracket Assy Kit 1 2 C82165 MODULATING ACTUATOR C60136 1 4...

Page 17: ...5 Street Elbow C80123 1 5 Union C82050 1 1 2 x 1 1 2 x 3 4 T section C82051 3 4 to 1 4 reducer C60143 1 1 2 X 1 4 Nipple C82052 1 4 elbow C80913 1 4 NPT x 1 4 90 component male elbow C82053 1 1 2 MAIN VALVE C82054 Maxitrol Pressure Regulator C82055 1 1 2 ASCO Solenoid Valve C60137 1 4 Maxitrol pressure regulator C60129 57 5 Copper Tubing C50251 High Pressure Switch C70041 RELAY C70042 RELAY BASE C...

Page 18: ...BRACKET C82084 SUPPLY PANEL RECTANGULAR ASSY C82087 Serial Number variable data C82088 Warning Use with Propane or Natural Gas Only C82090 Caution supply cord C82091 Caution door panel closed C82092 caution adequate ventilation C82093 General Hazard Warning C82094 Warning Max Inlet Pressure C82095 Position Heater Properly before use C82096 Wiring Diagram C82097 DF 1600 logo C82098 Decal Campo Logo...

Page 19: ... ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com pg 19 C82056 1 1 2 RTC ball valve C82040 Contactor C82041 Transformer C82042 RELAY 240A C50242 Aux Contact N O 50A ...

Reviews: