CAMPO EQUIPMENT CO. LTD. (ECOBLAZE) 

6 Carson Court, Brampton, ON, CANADA, L6T 4P8 

Tel: (905) 793-2525 | Fax: (905) 793-8768 

www.campoequipment.com

  

pg. 5

 

WIRING

 

The  required  voltage  and  amperage  for  each 
heater is listed in the SPECIFICATIONS section 
of the manual and are also listed on the heater 
identification plate attached to the heater.  If the 
heater needs to be operated on a voltage other 
than that indicated by these decals, consult the 
factory for instructions. If a voltage change has 
been  made,  re-label  the  heater  as  such.  For 
Safety reasons, as well as preventing damage 
to the heater, NEVER leave the wrong decal in 
place.  No  information  is better  than the  wrong 
information. The heater must be wired (at every 
installation)  according  to  the  voltage  and 
amperage  required

.    A  qualified  electrician 

must 

wire 

the 

heater 

appropriately 

according  to  the  wiring  diagram  and  local, 
state, and national codes

.  

The heater must 

be electrically grounded in compliance with 
the National Electrical Code, ANSI/NFPA 70 
and  CSA  C22.1,  Canadian  Electrical  Code 
Part I.  

  
  

GAS CONNECTIONS AND 

SUPPLY 

 

 

WARNING  

Only  qualified  gas  fitting  personnel  shall 

connect  or  disconnect  fuel  supply  lines  to 
supply  tanks  and  or  gas  mains  and  the 
heater gas inlet manifold. 

 

  

All  unions  and  valves  must  be  checked  for 

tightness and proper operation before the initial 
start-up of the heater.  Use Sherlock 5-second 
leak (of the proper temperature) or soapy water 
on  all  connections  to  be  sure  they  are  tight.  
Replace  or  tighten  any  connection  as 
necessary.  
  

The  supply  gas  hose  being  used  must  be 

protected  from  traffic,  building  materials, 
and  contact  with  hot  surfaces  both  during 
usage and while in storage. 

 

 

 

The  supply  gas  hose  shall  be  visually 

inspected prior to each use of the heater.  If 
it is evident there is excessive abrasion or 
wear, or the hose is cut, it must be replaced 
prior to the heater being put into operation.   

 

 

 

The supply gas hose must be replaced with 

a  manufacture’s  authorized  replacement 
part only. 

 

 

 

See the Service Parts section of this manual 
for the appropriate replacement part.  

OPERATING GAS PRESSURES  

  

Minimum inlet pressure - 10 inches W.C (0.36 

PSI) Maximum inlet pressure 

– 14 inches W.C 

(0.50 PSI))  
  
 

OPERATING INSTRUCTIONS  

 

 

Pre-Start Checklist  

  

Before  attempting  to  start  the  Blaze  DF1600, 

several  important  checks  of  the  heater  and 
heater system are critical to safe, efficient, and 
dependable  usage.    Many  potential  problems 
can  be  avoided  by  proper  maintenance  and 
attention.  The  heater  should  be  inspected 
before  each  use,  and  at  least  annually  by  a 
qualified service personnel.  
  
1.  Familiarize  yourself  with  this  Operation  / 

Service Manual.   

2.  Check  the  entire  heater  for  any  sign  of 

physical damage.   

3.  Check for obstructions to the air intake and 

discharge of the heater.  Remove anything 
that  will  obstruct  or  restrict  airflow.    The 
heated  work  area  must  be  ventilated  to 
ensure that all air present in the workspace 
can  be  displaced  continuously  with  fresh 
heated air.  The heater air intake must be 
supplied  with  clean,  fresh  outside  air 
always.  

4.  Check incoming voltage.   
5.  Check  the  entire  heater  for  loose  nuts, 

bolts,  and  electrical  connections.  Be  sure 
the blower mounting bolts are tight.  

Summary of Contents for ECOBlaze DF1600

Page 1: ...t com pg 1 NG LP DIRECT FIRED SPACE HEATER BLAZE DF1600 WWW CAMPOEQUIPMENT COM REPORT 0367GH009S Installation Instructions Manual Maintenance Parts List CAUTION DO NOT TAMPER WITH HEATER OR ITS CONTROLS CALL A QUALIFIED SERVICE TECHNICIAN Retain manual for future reference May 19 2021 CERTIFIED FOR USE IN CANADA AND THE U S A ...

Page 2: ...s remain with the heater GENERAL HAZARD WARNING FAILURE TO COMPLY WITH THE PRE CAUTIONS AND INSTRUCTIONS PROVIDED WITH THIS HEATER CAN RESULT IN DEATH SERIOUS BODILY INJURY AND PROPERTY LOSS OR DAMAGE FROM HAZARDS OF FIRE EXPLOSION BURN ASPHYXIATION CARBON MONOXIDE POISONING AND OR ELECTRICAL SHOCK ONLY PERSONS WHO CAN UNDERSTAND AND FOLLOW THE INSTRUCTIONS SHOULD USE OR SERVICE THIS HEATER IF YOU...

Page 3: ...nsferable to any subsequent owner The warranty period is one year from the date of purchase The warranty covers all defects in material and workmanship insofar as they are of Campo Equipment CO LTD manufacture This warranty is limited to the furnishing of new parts only in the event the original part is determined to be defective by Campo Equipment CO LTD The warranty does not include transportati...

Page 4: ...erature is well below the material flash point Under no circumstance should any combustible material be stored in the airstream within 15 feet 4 57 m of the air discharge port or within 6 15 2cm of the top sides or ends of the heater WARNING This heater must be placed at least 10 Ft 3 05M from any LP Gas Container The discharge air stream of this heater must not be directed toward any LP Gas conta...

Page 5: ...hten any connection as necessary The supply gas hose being used must be protected from traffic building materials and contact with hot surfaces both during usage and while in storage The supply gas hose shall be visually inspected prior to each use of the heater If it is evident there is excessive abrasion or wear or the hose is cut it must be replaced prior to the heater being put into operation ...

Page 6: ...power supply compartment there are four CAM locks and a 3 Phase 250V 30 Amp male plug use either one of them When using the plug make sure that the CAM locks have caps on them The main power switch should be in the OFF positions This power source must include a Short Circuit protection device such as a circuit breaker or fusible With all connections secure including grounds energize the heater Pla...

Page 7: ...RNING A qualified electrician must make the adjustments 4 Check to be sure the air proving switch sensor tubes are clear of any obstructions NOTE Listen to hear the pilot solenoid valve click If the click is not heard the solenoid valve may not be opening and may be defective Sparking should also be present at the spark igniter in the burner If the click is heard and pressure is registered move th...

Page 8: ...g and gas codes When storing the heater indoors the gas connection between the heater and the supply cylinder must be disconnected Preparing After Extended Storage Several days or weeks before the heater will be used attention should be paid to properly preparing the heater for service Since the heater is an important element of your operation it only makes sense that a certain amount of time is n...

Page 9: ...Minimum flame results from zero volts DC The DF1600 heater has a minimum BTU input rating of 324538 BTUs on NG 81782 Kcal and 326289 BTUs 82223 Kcal on LP The Belimo Modulating System has been pre set at the factory to insure this input No field adjustment of this set point is required Conventional Remote Thermostat The optional remote thermostat if used connects to the remote thermostat receptacl...

Page 10: ...tory and should be changed by authorized service personnel only Igniter To start ignition the igniter must be adjusted properly and must not be damaged or defective Periodically the igniter should be inspected for damage corrosion and separation To inspect and adjust the igniter use the following procedure 1 Remove the igniter from the burner 2 Visually inspect the igniter for corrosion and damage...

Page 11: ...od Remember that the blower must be operating properly for the burner to operate The switch can be tested using an ohmmeter To test use the following procedure 1 Disconnect the main power supply open the Electrical Compartment 2 Set the ohmmeter in the continuity test mode 3 With the main switch in OFF position place one tester lead on the common contact and one tester lead on the contact relative...

Page 12: ... continuity light to the switch N O contacts Place the Heat Fan switch to FAN position The ohmmeter should read low resistance or the continuity light should come on When the blower is stopped the light should go out and the resistance reading should be high If the contacts remain closed regardless of the blower status the air switch must be replaced Contact the factory in the event the switch mus...

Page 13: ...there is power to the VFD Burner does not ignite 1 Voltage insufficient 1 Check incoming supply 2 Electrode disconnected adjusted incorrectly defective 2 Connect adjust replace electrode 3 Air Proving Sw Disconnected defective 3 Connect Replace Air Proving Sw 4 Tilt switch Disconnected or Unit is not on a level surface or defective 4 Connect Replace Tilt Switch or Level the Unit 5 Fan Over heat sw...

Page 14: ...ng Sw 5 Flame rod dirty defective 5 Clean Replace Flame Rod 6 Inadequate fuel delivery 6 Fill Tank replace regulators valves check gas lines for obstructions TROUBLESHOOTING DF1600 DIRECT FIRED HEATER PROBLEM CONDITION REMEDY Heater overheating 1 Gas pressure excessive 1 Adjust replace regulator 2 RTC Discharge Temperature Sensor defective 2 Replace sensor troubleshoot modulation system ...

Page 15: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com pg 15 WIRING DIAGRAM ...

Page 16: ...oltmeter C70064 3 POSITION SWITCH C70069 FIXING COLLAR C70067 N O CONTACT BLOCK C70028 VFD C70137 R Fan 500 C90025 Power On Indicator Light GREEN C90029 Outlet for Plug C70052 TILT SWITCH C82036 Spark Controller C80186 MAIN CONTROLLER C82163 Actuator ball valve 11 2 NPT C80916 12 Discharge Air tube C60139 Temperature Sensor c w Stew C82164 Bracket Assy Kit 1 2 C82165 MODULATING ACTUATOR C60136 1 4...

Page 17: ...5 Street Elbow C80123 1 5 Union C82050 1 1 2 x 1 1 2 x 3 4 T section C82051 3 4 to 1 4 reducer C60143 1 1 2 X 1 4 Nipple C82052 1 4 elbow C80913 1 4 NPT x 1 4 90 component male elbow C82053 1 1 2 MAIN VALVE C82054 Maxitrol Pressure Regulator C82055 1 1 2 ASCO Solenoid Valve C60137 1 4 Maxitrol pressure regulator C60129 57 5 Copper Tubing C50251 High Pressure Switch C70041 RELAY C70042 RELAY BASE C...

Page 18: ...BRACKET C82084 SUPPLY PANEL RECTANGULAR ASSY C82087 Serial Number variable data C82088 Warning Use with Propane or Natural Gas Only C82090 Caution supply cord C82091 Caution door panel closed C82092 caution adequate ventilation C82093 General Hazard Warning C82094 Warning Max Inlet Pressure C82095 Position Heater Properly before use C82096 Wiring Diagram C82097 DF 1600 logo C82098 Decal Campo Logo...

Page 19: ... ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com pg 19 C82056 1 1 2 RTC ball valve C82040 Contactor C82041 Transformer C82042 RELAY 240A C50242 Aux Contact N O 50A ...

Reviews: