SC105 CS I/O to RS-232 Interface 

5.3  Testing RAD Modem Communication 

The modem communication link is divided into the following three sections:   
1) RAD modem computer end, 2) cable from computer modem to datalogger 
modem, 3) RAD modem datalogger end.  When unable to establish 
communication with the datalogger, test each of the three sections. 

Before proceeding through the testing procedures, a terminal emulator software 
program such as HyperTerminal

TM

 or Campbell Scientific’s datalogger support 

software (

Test Terminal Emulator

) must be used to communicate through the 

COM port of the computer.  Once the emulator program is set up, testing can 
proceed as follows: 

1.  Disconnect the four conductor cables from the SRM-6A RAD modem at 

the computer end.  Jumper the XMT + to RCV + and jumper the XMT – 
to RCV –.  This creates a transmit loop which allows any key pressed at 
the computer keyboard to be seen on the screen.  If the key pressed is not 
seen, check the following:  COM port configuration, 25-pin cable from 
the computer to the modem, and the RAD modem. 

2.  Reconnect the four conductor cables to the modem at the computer end 

and disconnect the cable from the modem at the datalogger end.  Twist 
together the XMT + wire and RCV + wire, twist together the XMT – wire 
and the RCV – wire.  Repeat step 1 by pressing a key on the computer 
keyboard.  If the key pressed is not returned, then the cable from the 
modem at the computer to the datalogger modem is defective and will 
need to be repaired or replaced. 

3.  If steps 1 and 2 pass, the modem at the datalogger is suspect.  Disconnect 

the modem from the SC105 and bring the modem to the computer site.  
Attach the modem to the computer, and repeat step 1 by jumpering the 
terminals of the modem and pressing a key on the computer keyboard. 

If the above tests pass and communication to the datalogger still has not been 
established, perform tests 4, 5, and 6.   

4.  A 12 V lead acid battery supply should not be discharged below 11.76 V.  

If this occurs, the batteries will go into a deep discharge state and will 
need to be replaced.  The CR10 will function properly on a battery voltage 
of 10 to 15 volts.  Check the 12 V supply with a voltmeter. 

5.  On the wiring panel of most Campbell Scientific dataloggers there is a 

terminal marked 5 V.  Check the 5 V supply with a voltmeter.  This 5 V 
supply should be within a tenth of a volt.  If not, it would indicate a 
problem. 

6.  To verify that the datalogger and its serial I/O port are working, try to 

access input memory locations using a laptop PC with the SC105 (using a 
null modem cable connection).  Configure the SC105 CS I/O Port to 
Modem Enable for this test. 

7.  If test 6 fails, use a CR10KD Keyboard Display to access input locations.   

If the datalogger passes tests 4, 5, and 7, but fails test 6, then the SC105 is 
suspect and will need to be repaired or replaced. 

Summary of Contents for SC105 CS

Page 1: ...SC105 CS I O to RS 232 Interface Revision 11 13 C o p y r i g h t 2 0 0 4 2 0 1 3 C a m p b e l l S c i e n t i f i c I n c...

Page 2: ......

Page 3: ...emoving reinstalling and shipping defective products to Campbell Campbell will return such products by surface carrier prepaid within the continental United States of America To all other locations Ca...

Page 4: ...g container Campbell Scientific s shipping address is CAMPBELL SCIENTIFIC INC RMA _____ 815 West 1800 North Logan Utah 84321 1784 For all returns the customer must fill out a Statement of Product Clea...

Page 5: ...u 3 3 1 Set up Menu Selections 4 4 Installation 5 5 RAD Modem Application 5 5 1 RAD Modem Two Way 6 5 2 RAD Modem Wiring and Grounding 6 5 3 Testing RAD Modem Communication 8 6 CDMA Modem Application...

Page 6: ......

Page 7: ...C105 is supplied from the 5 V supply on pin 1 of the datalogger s CS I O port The SC105 will use the 5 V supply to power the RS 232 modem if needed Two way interactive communication Supports most RS 2...

Page 8: ...ection 7 Out RTS Request to Send Modem Enable 8 In CTS Clear to Send 9 In Ring Rings Datalogger CS I O 9 Pin Male Connector Pin out Pin No I O Name Description 1 In 5 V Regulated 5 Volt supply 2 GND G...

Page 9: ...The Set up Menu is shown in FIGURE 3 1 It is accessed by connecting the SC105 s RS 232 port to a PC with the included null modem cable The SC105 also needs to have power Usually the SC105 is powered...

Page 10: ...Addressed Print Device is a mode that allows output from the datalogger when it executes the P96 instruction 2 RS 232 Port Configuration RS 232 baud rate data bits and parity are configured here as w...

Page 11: ...e to lightning is possible If this is a RAD modem application see Section 5 2 RAD Modem Wiring and Grounding 5 RAD Modem Application The SC105 can be used with a short range modem to communicate acros...

Page 12: ...back of the RAD modem connected to the SC105 to DCE For a RAD modem connected to a PC set the DCE DTE switch to DCE For a RAD modem connected to a serial printer set the DCE DTE switch to DTE 2 Select...

Page 13: ...ng the transient spark gap protection is probably not needed FIGURE 5 2 Installation of Spark Gap Protection Occasionally a customer needs to transmit data across longer or smaller gage wires or at hi...

Page 14: ...ter keyboard If the key pressed is not returned then the cable from the modem at the computer to the datalogger modem is defective and will need to be repaired or replaced 3 If steps 1 and 2 pass the...

Page 15: ...ion Typically the Freewave radios will be used in a PakBus network with PakBus OS dataloggers With a PakBus datalogger the CS I O port configuration on the SC105 should be set to SDC 7 SDC 8 SDC 10 or...

Page 16: ...SC105 CS I O to RS 232 Interface 10...

Page 17: ......

Page 18: ...ANADA www campbellsci ca dataloggers campbellsci ca Campbell Scientific Centro Caribe S A CSCC 300 N Cementerio Edificio Breller Santo Domingo Heredia 40305 COSTA RICA www campbellsci cc info campbell...

Reviews: