SC105 CS I/O to RS-232 Interface 

 

TABLE 5-1.  Approximate Range, miles and km

 

Data Rate  19 Gauge (0.9 mm) 

24 Gauge (0.5 mm) 

26 Gauge (0.4 mm) 

bps  miles km miles km miles km 

9,600 6.2 10.0 2.8  4.5  2.0  3.3 

1,200 7.6 12.2 3.4  5.5  2.5  4.0 

 

5.1  RAD Modem – Two Way 

4-WIRE UNCONDITIONED

TELEPHONE LINE

OR

TWO TWISTED PAIRS

SRM

9 TO 25 PIN

ADAPTOR

SC105

DATALOGGER

PC

SRM

 

FIGURE 5-1.  Two Way Communication 

When using Campbell Scientific’s datalogger support software to communicate 
through the SC105/RAD modem, “Set-up” the link as a direct connect between 
the datalogger and the desired COM port.  Start two way communication using 
the 

Connect

 button on the tool bar and the 

Connect

 button in the 

Connect

 

window. 

5.2  RAD Modem Wiring and Grounding 

FIGURE 5-2 shows a typical set-up of the RAD modems.  Installation is as 
follows:   

1.  Set the DCE/DTE switch on the back of the RAD modem connected to 

the SC105 to DCE.  For a RAD modem connected to a PC, set the 
DCE/DTE switch to DCE.  For a RAD modem connected to a serial 
printer, set the DCE/DTE switch to DTE. 

2.  Select a cable with two or more twisted pairs.  A recommended direct 

burial rodent resistant cable is listed below.  They also sell several gopher 
resistant cables for even greater protection.   

 Company 

Part 

Number  AWG. 

 Anixter 

F-02P22BPN  22 

 Tel: 

847-677-2600 

 

www.anixter.com 

3.  Wiring connections are made as shown in FIGURE 5-2.  Note wires 

labeled A and B are one twisted pair of the cable.  Wires labeled C and D 
are the other twisted pair.   

4.  Transients induced on the communication line may damage any 

electronics connected at either end of the line.  To decrease the chances 
for damage, spark gaps should be installed as shown in FIGURE 5-2.  The 
transient protection shown may be purchased from Campbell Scientific 
(pn 5563 shown in FIGURE 5-2, pn 6536 includes a plastic case, pn 6361 
includes hardware for mounting to ground lug of Campbell Scientific 

Summary of Contents for SC105 CS

Page 1: ...SC105 CS I O to RS 232 Interface Revision 11 13 C o p y r i g h t 2 0 0 4 2 0 1 3 C a m p b e l l S c i e n t i f i c I n c...

Page 2: ......

Page 3: ...emoving reinstalling and shipping defective products to Campbell Campbell will return such products by surface carrier prepaid within the continental United States of America To all other locations Ca...

Page 4: ...g container Campbell Scientific s shipping address is CAMPBELL SCIENTIFIC INC RMA _____ 815 West 1800 North Logan Utah 84321 1784 For all returns the customer must fill out a Statement of Product Clea...

Page 5: ...u 3 3 1 Set up Menu Selections 4 4 Installation 5 5 RAD Modem Application 5 5 1 RAD Modem Two Way 6 5 2 RAD Modem Wiring and Grounding 6 5 3 Testing RAD Modem Communication 8 6 CDMA Modem Application...

Page 6: ......

Page 7: ...C105 is supplied from the 5 V supply on pin 1 of the datalogger s CS I O port The SC105 will use the 5 V supply to power the RS 232 modem if needed Two way interactive communication Supports most RS 2...

Page 8: ...ection 7 Out RTS Request to Send Modem Enable 8 In CTS Clear to Send 9 In Ring Rings Datalogger CS I O 9 Pin Male Connector Pin out Pin No I O Name Description 1 In 5 V Regulated 5 Volt supply 2 GND G...

Page 9: ...The Set up Menu is shown in FIGURE 3 1 It is accessed by connecting the SC105 s RS 232 port to a PC with the included null modem cable The SC105 also needs to have power Usually the SC105 is powered...

Page 10: ...Addressed Print Device is a mode that allows output from the datalogger when it executes the P96 instruction 2 RS 232 Port Configuration RS 232 baud rate data bits and parity are configured here as w...

Page 11: ...e to lightning is possible If this is a RAD modem application see Section 5 2 RAD Modem Wiring and Grounding 5 RAD Modem Application The SC105 can be used with a short range modem to communicate acros...

Page 12: ...back of the RAD modem connected to the SC105 to DCE For a RAD modem connected to a PC set the DCE DTE switch to DCE For a RAD modem connected to a serial printer set the DCE DTE switch to DTE 2 Select...

Page 13: ...ng the transient spark gap protection is probably not needed FIGURE 5 2 Installation of Spark Gap Protection Occasionally a customer needs to transmit data across longer or smaller gage wires or at hi...

Page 14: ...ter keyboard If the key pressed is not returned then the cable from the modem at the computer to the datalogger modem is defective and will need to be repaired or replaced 3 If steps 1 and 2 pass the...

Page 15: ...ion Typically the Freewave radios will be used in a PakBus network with PakBus OS dataloggers With a PakBus datalogger the CS I O port configuration on the SC105 should be set to SDC 7 SDC 8 SDC 10 or...

Page 16: ...SC105 CS I O to RS 232 Interface 10...

Page 17: ......

Page 18: ...ANADA www campbellsci ca dataloggers campbellsci ca Campbell Scientific Centro Caribe S A CSCC 300 N Cementerio Edificio Breller Santo Domingo Heredia 40305 COSTA RICA www campbellsci cc info campbell...

Reviews: