![Camille Bauer SIRAX BM1450 Operating Instructions Manual Download Page 31](http://html.mh-extra.com/html/camille-bauer/sirax-bm1450/sirax-bm1450_operating-instructions-manual_487907031.webp)
PM 1001812 000 00
Device handbook SIRAX BM1450
31/36
Continuation Table 12: 4X-Adress register
Address
Parameter
Read / write
Start Address Hex
Default values
High Byte
Low Byte
40115
User screen 6 (see Table 2, page 11)
R/W
00
72
10
40117
User screen 7 (see Table 2, page 11)
R/W
00
74
11
40119
User screen 8 (see Table 2, page 11)
R/W
00
76
14
40121
User screen 9 (see Table 2, page 11)
R/W
00
78
15
40123
User screen 10 (see Table 2, page 11)
R/W
00
7A
18
40125
Pulse divisor for pulse output 1 (see Table 9, page 18)
R/W
00
7C
1
40127
Pulse divisor for pulse output 2 (see Table 9, page 18)
R/W
00
7E
1
40133
Pulse width for pulse output (60, 100 and 200 ms)
R/W
00
84
100
40219
Select relay output 1 (see chapter 6.5.1, page 15)
R/W
00
DA
0
40221
Parameters for limit value output
(For limit relay, see Table 6, page 15)
(For pulse relay, see Table 7, page 16)
(For timer relay, see Table 16, page 33)
R/W
00
DC
0
40223
Selection Configuration Relay 1
(For limit relay, see Table 15A, page 33)
(For timer, see table 15B, page 33)
R/W
00
DE
0
40225
Trip point Limit 1(see table 6, page 15)
(±10...±120%) / (10...120%) / (10...9999999)
R/W
00
E0
0
40227
Hysteresis Limit 1(0.5...50)
R/W
00
E2
0
40229
Relay 1 / Energizing delay (0...9999)
R/W
00
E4
0
40231
Relay 1 / De-Energizing delay (0...9999)
R/W
00
E6
0
40233
Select relay output 2 (see chapter 6.5.1, page 15)
R/W
00
E8
0
40235
Parameters for limit value output
(For limit relay, see Table 6, page 15)
(For pulse relay, see Table 7, page 16)
(For timer relay, see Table 16, page 33)
R/W
00
EA
0
40237
Selection Configuration Relay 2
(For limit relay, see Table 15A, page 33)
(For timer, see table 15B, page 33)
R/W
00
EC
0
40239
Trip point Limit 2 (see table 6, page 15)
(±10...±120%) / (10...120%) / (10...9999999)
R/W
00
EE
0
40241
Hysteresis Limit 1(0.5...50)
R/W
00
F0
0
40243
Relay 2 / Energizing delay (0...9999)
R/W
00
F2
0
40245
Relay 2 / De-Energizing delay (0...9999)
R/W
00
F4
0
40247
Select relay output 3 (see chapter 6.5.1, page 15)
R/W
00
F6
0
40249
Parameters for limit value output
(For limit relay, see Table 6, page 15)
(For pulse relay, see Table 7, page 16)
(For timer relay, see Table 16, page 33)
R/W
00
F8
0
40251
Selection Configuration Relay 3
(For limit relay, see Table 15A, page 33)
(For timer, see table 15B, page 33)
R/W
00
FA
0
40253
Trip point Limit 3 (see table 6, page 15)
(±10...±120%) / (10...120%) / (10...9999999)
R/W
00
FC
0
40255
Hysteresis Limit 3 (0.5...50)
R/W
00
FE
0
40257
Relay 3 / Energizing delay (0...9999)
R/W
01
0
0
40259
Relay 3 / De-Energizing delay (0...9999)
R/W
01
2
0
40261
Select relay output 4 (see chapter 6.5.1, page 15)
R/W
01
4
0