![Camille Bauer GOSSEN METRAWATT GEOHM C Operating Instructions Manual Download Page 61](http://html1.mh-extra.com/html/camille-bauer/gossen-metrawatt-geohm-c/gossen-metrawatt-geohm-c_operating-instructions-manual_3679155061.webp)
GMC-I Messtechnik GmbH
25
6
Database Function
Displayed measurement data can be saved individually for each measure-
ment to the internal database either with or without a comment. In order
to assign the individual measured values to various buildings, customers
etc., a data record must first be created with its own memory address.
6.1
Creating a Data Record – Data Function
Ð
Press the data softkey.
Ð
First, enter the desired memory address with the softkeys. After
acknowledging this entry with the
START
key (press at center), the
cursor appears at the first entry position (
BUILDING)
.
No entry is required for the customer ID field, as long as measurements
are only performed for a single company.
The
M-TYPE
field (measurement type) is used to designate what kind of
measurement is involved. This entry is required in order to generate a
report with PS3 test instrument software for lightning protection systems.
M-TYPE Setting
Significance
D
Continuity to metallic installations
DG
Continuity to metallic gas lines
DW
Continuity to metallic water lines
DL
Continuity to metallic ventilation systems
D1, D2, D3, D4
Continuity to other, user-defined types of metallic systems
U
Contact resistance measurement at all measuring points in order to
determine continuity of all conductors. The number assigned to the
measurement designates resistance between specific test joints, e.g. mea-
surement number 1 indicates resistance between test joints 1 and 2, mea-
surement 2 between test joints 2 and 3 etc.
E
Measurement of earth dissemination resistance from individual earth
electrodes with open test joints
!
Measurement of earth dissemination resistance for the entire system
with closed test joints
Summary of Contents for GOSSEN METRAWATT GEOHM C
Page 1: ...GEOHM C Erdungsmessger t 3 349 089 01 12 3 11 Bedienungsanleitung...
Page 34: ...34 GMC I Messtechnik GmbH...
Page 35: ...GMC I Messtechnik GmbH 35...
Page 37: ...GEOHM C GB int Earth Tester 3 349 089 03 12 11 10 Operating Instructions...
Page 70: ...34 GMC I Messtechnik GmbH...
Page 71: ...GMC I Messtechnik GmbH 35...
Page 73: ...GEOHM C Appareil de mesure de r sistance de terre 3 349 089 04 12 4 11 Mode d emploi...
Page 106: ...34 GMC I Messtechnik GmbH...
Page 107: ...GMC I Messtechnik GmbH 35...
Page 109: ...GEOHM C Misuratore di terra 3 349 089 10 12 6 11 Istruzioni per l uso...
Page 142: ...34 GMC I Messtechnik GmbH...
Page 143: ...GMC I Messtechnik GmbH 35...
Page 145: ...GEOHM C NL Aardingsmeter 3 349 089 05 3 8 08 Gebruiksaanwijzing...
Page 173: ...GEOHM C E Medidor de resistencia contra a tierra 3 349 089 07 12 4 11 Manual de instrucciones...
Page 206: ...34 GMC I Messtechnik GmbH...
Page 207: ...GMC I Messtechnik GmbH 35...