MC-II Flow Analyzer
15
5.
Select or deselect the Pulse Output option. The default setting is
OFF
.
If your MC-II is
not
configured with the pulse output option, press
ENTER/STEP
to accept the default setting,
OFF
, and proceed to
Step 6.
If your MC-II is configured with the pulse output option, you have the
option of leaving the option disabled (
OFF
), or entering a scale fac-
tor.
To enter a scale factor, press
INCREMENT
repeatedly to select
the volume increment that will cause a pulse output to occur. Press
ENTER/STEP
to accept the selection. For instruction on choosing an
appropriate scale factor, see Appendices A and B.
The
CodE
menu will appear in the top display.
6.
Enable/disable the password-protected security feature by accepting
the default
no
setting on the
CodE
menu, or by pressing
INCREMENT
to toggle the setting to
YES
. Press
ENTER/STEP
to
save the setting. The bottom screen will change to a numerical data
entry field, prompting you to enter a numeric password of up to six
digits.
Note—Choose a number that is easily remembered. Record the pass-
word for future reference if necessary. You will be asked for it each
time you press
ACCESS
(to enter the Calibration mode) or
RESET
(to reset the total). For more information on the password protection
security feature, see “Enable Password Security Option,” page 11.
Select or deselect the
Pulse Output option.
RATE
RATE
RATE
RATE
RATE
Select or deselect the
Password Security
option.
Summary of Contents for NuFlo MC-II
Page 1: ...NUFLO MC II FlowAnalyzer User Manual Manual No 100079666 Rev OE ...
Page 6: ...MC II Flow Analyzer 2 Figure 1 Nomenclature exterior ...
Page 7: ...MC II Flow Analyzer 3 Figure 2 Nomenclature interior ...
Page 32: ...MC II Flow Analyzer 28 ...
Page 38: ...MC II Flow Analyzer 34 ...
Page 44: ...40 MC II Flow Analyzer ...
Page 45: ......
Page 46: ......