MEDIA COOLING PADS OPERATING INSTALLATION:
45
15
Do not expose CELdek
®
evaporative cooling pads to sparks, open flame, welding spatter, temperatures
in excess of 350
0
F, or other sources which may ignite the paper. GLASdek
®
will not readily ignite,
unless exposed to a direct flame or extremely high temperatures for an extended period of time.
Test Results for ASTM-E84 Standard Method of Test for Surface Burning Characteristics of Building Materials
PRODUCT
Flame Spread Index
Smoke Density
CELdek
450
420
GLASdek
0
20
Mi-T-Dark
®
,
DRIFdek
®
, & COOLdek
®
15
745
IMPORTANT
Installation
In order to get the best performance from your Munters cooling pads, they must be installed properly. If you have
purchased a pad with two equal angles, they can be installed in either direction.
Depending on the application, pads are manufactured with special angle combinations. Those having combinations
of 15
0
x 45
0
or 30
0
x 45
0
are made to direct more water toward the
air entering side of the pads. If installed backwards, the pads may
not work properly.
Munters pads must always be installed with the steeper flute
angle sloping down toward the air entering side. The reasoning is
simple, the steeper angle puts more water on the entering side of
the pad where the air is hot, dry, and dusty and extra water it is
needed most. The unequal angles also counteract the tendency
of the air to push the water toward the air leaving side of the pad.
CELdek “New Pad” Odor
CELdek is made from materials similar to those used in paints,
carpets, paneling and wallpaper. CELdek pads must be flushed
with water to remove the new construction odors.
If you find the smell of the new paper to be objectionable, you
should run water over the pad for 2-5 hours without the fan
running. Change the water often, using bleed off or dump cycles.
If the odor continues after one or two days, call Munters
customer service. Please have full details of when and from
whom the pad was purchased.
Caution
The data and suggestions contained herein are based on information Munters believes to be reliable. They are offered in good faith but without guarantee, as conditions and methods of use are beyond our
control. We recommend that the prospective user determine the suitability of our media and suggestions before adopting them on a commercial scale.
For more information Contact Munters Corporation, HumiCool Division 239-936-1555
©Copyright Munters Corporation 2002 Printed in USA