Page 12

SD496260 ISSUE 10

4.4 FRESH AIR FEATURE

70.00

70

.0

0

The facility to draw fresh air through the dehumidifier is incorporated into the design.
After removing the blanking plate,  a suitable spigot may be attached to the back of the

dehumidifier.

M6 FIXINGS

DH44 STYLE DEHUMIDIFIER SHOWN

Summary of Contents for DH44 Series

Page 1: ...12 0 SPARE PARTS LISTS 24 Contents 1 1 MOUNTING POSITION 2 1 2 WALL HANGING FLOOR STANDING 4 2 1 CONDENSATE DRAIN CONNECTION 5 2 2 ELECTRICAL CONNECTION 6 3 0 HUMIDISTAT SETTINGS 7 4 1 OPTIONAL HUMID...

Page 2: ......

Page 3: ...umidifier is positioned on a wall the wall needs to be load bearing A plaster board or wood cladded wall is not sufficiently strong 1 1 MOUNTING POSITION Health and Safety This appliance is not intend...

Page 4: ...IT IS USED ON ALL INSTALLATIONS WHEN FITTED A 30mA RCD SHOULD BE USED IF THE UNIT IS WITHIN 1 25M OF THE POOL HORIZONTALLY THEN IT MUST BE 2 5M ABOVE THE POOL SURFACE ALTHOUGH THE UNIT IS 2 5M ABOVE T...

Page 5: ...315 00 630 00 931 00 WALL REMOVE GROMMETS 95 00 MAX 30 00 340 00 274 20 294 20 FIT ANTIVIBRATION BUFFERS DH44 MODEL DH66 MODEL When the dehumidifier is unpacked it is suitable for use standing on the...

Page 6: ...he condensate output and electrical connections can be at either end of the machine at the side or in the back depending on the requirements of the user To gain access to the unit remove the covers un...

Page 7: ...are made to the terminal box on the outside of the electric box in the bottom right hand corner of the dehumidifier The machine should be installed in accordance with EMC2004 108 EC FAN MODE SWITCH A...

Page 8: ...ive humidity is lower the air is drier To set the dial turn it so that the requred room humidity is positioned adjacent to the reference mark as shown below A room relative humidity of 50 to 60 is rec...

Page 9: ...LOREX PART SD385250 SIEBE PART No 119 1701 91100 REMOVE LINK BOILER DEMAND SIGNAL VOLT FREE HUMIDISTAT N L2 L L1 E GND 8 7 6 5 4 3 2 1 AIR STAT COMMON 12V REMOTE AIR THERMOSTAT CONNECTIONS FOR M C WIT...

Page 10: ...XIMUM DEHUMIDIFICATION REMOVE PINK WIRE LINK 12V COMBINED REMOTE HUMIDISTAT AIR STAT CONNECTIONS 1mm SQ CABLE 250M MAX HUMIDISTAT AIR STAT NOT SUPPLIED WE RECOMMEND CALOREX PART SD385252 EBERLE PART N...

Page 11: ...he machine The connections project 40mm out from the left hand side of the DH44 and the right hand side of th DH66 Attention Flow bottom connection Return top connection The 3 way motorised diverting...

Page 12: ...front covers in front of the evaporator fins and is accessed by removing the covers Undo the screw in each side moulding and lift off covers This should only be done with the power turned OFF From tim...

Page 13: ...URE 70 00 70 00 The facility to draw fresh air through the dehumidifier is incorporated into the design After removing the blanking plate a suitable spigot may be attached to the back of the dehumidif...

Page 14: ...ine A card will then be sent to you for your completion Health and Safety As the Heat Pump contains electrical and rotational equipment it is important that ONLY competent persons carry out any work o...

Page 15: ...EL DH44A AX DH66A AX DEHUMIDIFICATION l hr 1 25 2 41 l day 30 0 58 0 TOTAL HEAT TO AIR DEHUMIDIFIER ONLY kW 1 6 3 0 DEHUMIDIFIER LPHW kW 4 9 8 8 LPHW ONLY kW 3 3 5 8 NOMINAL POWER CONSUMED FAN ONLY kW...

Page 16: ...LTERED COMP EXTERNAL O L DELETED 1105 GSM 14 3 06 ELEC BOX OUTLINE C4 FAN SPEED CAPACITOR KONDENSATOR VENTILATORGESCHWINDIGKEIT CONDENSATEUR D ACCELERATION DU VENTILATEUR S1 HP LP D K MC MV C2 C1 Y A...

Page 17: ...GR 12V COIL BR MC D FT SH K C2 GR HARDKICK CAP RELAY C3 WITH REMOTE HUMIDISTAT BR 6 9 11 4 7 10 RELAY 3 K 3 1 R R 0 5 O 0 5 O L P H W VALVE GR O B BR B B BR Y O GR TERMINAL BLOCK BOILER DEMAND SIGNAL...

Page 18: ...SELECTEUR DE MODE DU VENTILATEUR REINITIALISATION DEFAUT HAUTE PRESSION REINITIALISATION DEFAUT BASSE PRESSION TEMPORISATEUR RELAIS COMPRESSEUR MOTEUR DU VENTILATEUR CONDENSATEUR DU COMPRESSEUR CONDE...

Page 19: ...SATEUR AIS ESSEUR ENTILATEUR U COMPRESSEUR U VENTILATEUR OMAGNETIQUE VRAGE TEMPORISE TAT LPHW ARRAGE OSTAT E DEGIVRAGE RMATEUR B R BL 12V AC REMOTE HUMIDISTAT R W P O 6 9 11 4 7 10 RELAY 2 K P REMOVE...

Page 20: ...suffered frost damage 8 The electrical supply is insufficient or in anyway incorrect IF IN DOUBT PLEASE ASK Note The Reply Paid Warranty Registration Card must be returned to ensure that the correct w...

Page 21: ...HP LP SCHRADER SCHRADER SERVICE SERVICE LP HP 3 8 TEV CONDENSER 1 4 PROCESS PORT 3 8 1 4 1 8 EQUALISATION LINE 3 8 3 8 DRIER EVAPORATOR COMPRESSOR PHIAL TEV SUCTION ACCUMULATOR DEFROST PROBE 9 0 REFR...

Page 22: ...HP LP SCHRADER SCHRADER SERVICE SERVICE LP HP 3 8 TEV CONDENSER 1 4 PROCESS PORT DEFROST PROBE 3 8 1 4 1 8 EQUALISATION LINE 3 8 3 8 DRIER EVAPORATOR COMPRESSOR PHIAL TEV SUCTION ACCUMULATOR VALVE SO...

Page 23: ...Page 22 SD496260 ISSUE 10 10 0 PERFORMANCE GRAPHS...

Page 24: ...96260 ISSUE 10 MACHINE TYPE DIMENSION X DH44 SERIES 950 00 DH66 SERIES 1415 00 1171 00 3120 FRAGILE FRAGILE HANDLE WITH CARE FRAGILE HANDLE WITH CARE 362 00 X PACKED DEHUMIDIFIERS 11 0 PACKED MACHINE...

Page 25: ...DISTAT N L2 L L1 E GND BOILER DEMAND SIGNAL VOLT FREE 8 7 6 5 4 3 2 1 12V AC REMOTE AIR STAT 12V AC COMMON REMOTE STAT REMOVE LINK 5 6 WHEN REMOTE IS FITTED 54 56 COMPRESSOR COVER NOT SHOWN ON THIS VI...

Page 26: ...3050 SUPPORT LEG 2 off 17 SD492750 FOOT ADJUSTABLE 4 off 18 SD494150 TUBE INSERT 4 off 19 SA118351 DEFROST STAT 1 off 20 SD111051 PIPE FLEXIBLE CLEAR PVC 16 BORE 0 4 m 30 SD492450 WALL BRACKET 1 off 3...

Page 27: ...EMAND SIGNAL VOLT FREE 8 7 6 5 4 3 2 1 12V AC REMOTE AIR STAT 12V AC COMMON REMOTE STAT REMOVE LINK 5 6 WHEN REMOTE IS FITTED 54 56 WATER IN WATER OUT 67 57 B A LPHW AIR BLEED VALVE 55 COMPRESSOR COVE...

Page 28: ...T 4 off 19 SA118351 DEFROST STAT 1 off 20 SD111051 PIPE FLEXIBLE CLEAR PVC 16 BORE 0 4 m 30 SD492450 WALL BRACKET 1 off 31 SD492350 BRACKET MACHINE 1 off 32 SD496250 OWNERS INSTALLATION MANUAL 1 off 4...

Page 29: ...BRACKET 30 WALL BRACKET 10 2 16 18 17 6 TEV PROBE 64 X X L N 66 3 45 2 8 9 20 7 49 GAS CHARGE R407c 58 PART VIEW ON X X 5 14 15 19 AIR SAMPLING IN AIR OUT A VERSION AX VERSION 4 20 80 60 4 0 13 59 OP...

Page 30: ...D493050 SUPPORT LEG 2 off 17 SD492750 FOOT ADJUSTABLE 4 off 18 SD494150 TUBE INSERT 4 off 19 SA118351 DEFROST STAT 1 off 20 SD111051 PIPE FLEXIBLE CLEAR PVC 16 BORE 0 8 m 30 SD492451 WALL BRACKET 1 of...

Page 31: ...5 4 3 2 1 12V AC REMOTE AIR STAT 12V AC COMMON REMOTE STAT REMOVE LINK 5 6 WHEN REMOTE IS FI TTED D494050 issue 1 FAN CONTINUOUS FAN CY CLE L N X X TEV PROBE 3 8 9 20 45 49 GAS CHARGE R407c 66 58 PART...

Page 32: ...BE INSERT 4 off 19 SA118351 DEFROST STAT 1 off 20 SD111051 PIPE FLEXIBLE CLEAR PVC 16 BORE 0 8 m 30 SD492451 WALL BRACKET 1 off 31 SD492351 BRACKET MACHINE 1 off 32 SD496250 OWNERS INSTALLATION MANUAL...

Page 33: ...L2 L L1 E GND BOILER DEMAND SIGNAL VOLT FREE 8 7 6 5 4 3 2 1 12V AC REMOTE AIR STAT 12V AC COMMON REMOTE STAT REMOVE LINK 5 6 WHEN REMOTE IS FITTED 25 HARD START CAP 27 31 3 RUN CAP 6 8 R3 R2 26 R1 F...

Page 34: ...6 TERMINAL BLOCK 8 WAY 16A 1 off 6 SD089550 DELAY TIMER 7 SEC TO 9 MIN 1 off 7 SD188950 ROCKER SWITCH 1 POLE C O 1 off 8 SD493402 LOOM ASSY 1 off 9 SD189050 LABEL ROCKER SWITCH 1 off 25 SD073150 CAPAC...

Page 35: ...NITS 1 SD487450 SIDE MOULDING LH 1 00 off 2 SD487451 SIDE MOULDING RH 1 00 off 3 SD487650 FRONT PANEL AIR IN 1 00 off 4 SD487801 LOUVRE ASSY 1 00 off 5 SD487750 FRONT PANEL TOP EDGE 1 00 off 6 PUSH NU...

Page 36: ...5 SA493602 ITEM PART No DESCRIPTION QUAN UNITS 1 SD487450 SIDE MOULDING LH 1 00 off 2 SD487451 SIDE MOULDING RH 1 00 off 3 D487651 FRONT PANEL AIR IN 1 00 off 4 SD487802 LOUVRE ASSY 1 00 off 5 D48775...