Page 14
SD496260 ISSUE 10
6.0 TECHNICAL DATA
a) These performance figures are based on air @ 30ºC, 60% RH and boiler water @ 80ºC
b) Humidistat adjustable from 20% to 80%
c) Minimum air temperature on standard (A) models 15°C
d) Minimum air temperature on defrost (AX) models 5°C
e) Maximum operating conditions air temp 35ºC and 90% RH.
f) R407c Global Warming Potential (GWP) 1700.
1L/min=0.22gall/min
1m hd =1.4psi
1mm Wg =9.8Pa
MODEL
DH44A/AX
DH66A/AX
DEHUMIDIFICATION
l/hr
1.25
2.41
l/day
30.0
58.0
TOTAL HEAT TO AIR:
DEHUMIDIFIER ONLY
kW
1.6
3.0
DEHUMIDIFIER & LPHW
kW
4.9
8.8
LPHW ONLY
kW
3.3
5.8
NOMINAL POWER CONSUMED:-
FAN ONLY
kW
0.04
0.07
DEHUM' (COMP & FAN)
kW
0.51
0.98
SUPPLY
230V 50Hz
230V 50Hz
FUSE
AMP
10
13
NOMINAL RUNNING AMPS
AMP
2.6
4.2
FULL LOAD AMPS
AMP
3.5
6.0
COMPRESSOR L.R.A.
AMP
12.0
26.0
AIR FLOW
m³/h
440
740
NOISE LEVEL @ 3m
dB/A
42
44
LPHW FLOW RATE
l/min
4.8
10.2
LPHW PRESSURE DROP
m hd
3.8
3.4
LPHW VOLUME
l
0.9
1.4
HERMETIC SYSTEM
REFRIGERANT CHARGE
kg R407c
1.1
1.7
IP RATING
45
45
WEIGHT UNPACKED/PACKED
kg
57/81
74/106
Summary of Contents for DH44 Series
Page 2: ......
Page 23: ...Page 22 SD496260 ISSUE 10 10 0 PERFORMANCE GRAPHS...