background image

ACT-7

Quick start guide

Summary of Contents for ACT-7

Page 1: ...ACT 7 Quick start guide...

Page 2: ...ot operate this device if it has missing damaged insecure guards or electrical components Ensure the device is sited on rm level ground Locate away from any possible unauthorised interference Ensure e...

Page 3: ...operate from a standard domestic wall socket The size of any extension cable that may be used is 2 5mm2 minimum up to a maximum length of 10 metres For longer lengths 4 0mm2 cable must be used If the...

Page 4: ...ng down the length of the room If there is more than one ACT 7 in the same area then they would normally be positioned side by side and equally spaced along the long wall all pointing in the same dire...

Page 5: ...ct level when delivered Look through the inspection window and check that the level is between the MAX and MIN on the tank in the back of the room unit If necessary top up the room unit with antifreez...

Page 6: ...ust be set to ducted mode Only use fan speeds in the RED range on the fan speed indicator for ducted operation Mode switch Top position fan only mode is selected In fan only mode air circulates but th...

Page 7: ...ed temperature Press and hold the enter key for two seconds then release to enter the Settings menu With the Temperature option highlighted press the enter key Use the up and down keys to change the h...

Page 8: ...w pressure faults are indicated by a ashing red H or L respectively and must be reset to resume normal operation See troubleshooting section Resetting the alarms Fault symbols In the Settings menu scr...

Page 9: ...s full a blue bucket ashes on the console While this is ashing the ACT 7 continues to work for a further 30 seconds After 30 seconds if the condensate tank has not emptied the pump continues to operat...

Page 10: ...Reset alarm Advanced settings Changing the o set An o set is used to calibrate the temperature shown on the main screen In the Settings menu scroll down to Advanced settings and push enter Highlight O...

Page 11: ...11 ACT 7 QUICK START GUIDE Press enter to move onto the next digit When enter is pressed on the nal digit the value is stored...

Page 12: ...Setting the language Advanced menu Enable Pin Language In the Advanced menu scroll down to Language and push enter Language Menu English Francais Deutsch Use the up and down arrows to select the desi...

Page 13: ...ined in the system which may spill when the ACT 7 is moved Routine maintenance The air lter must be kept clean Never allow the lter to become obstructed with dust or dirt If allowed to do so poor perf...

Page 14: ...erature and wait six minutes for time delay on start up to elapse Insufficient air ow from room unit Fan speed dial set to minimum Change the position of the fan speed dial No cooling HP alarm showing...

Page 15: ...15 ACT 7 QUICK START GUIDE...

Page 16: ...Calorex Heat Pumps Limited The Causeway Maldon Essex CM9 4XD United Kingdom t 44 0 1621 857171 e service calorex com www calorex com...

Reviews: