Calix ODC-80 Installation Guide
33
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2003 Calix. All Rights Reserved.
Procedure to test AC power levels
Procedure to replace AC power cover plates
Step
Action
1.
Set main power to the cabinet to ON.
2.
At the AC Load Center, set the Main breaker to ON.
3.
Using a volt meter test between L1 and neutral.
a. place one lead on L1
b. place the other lead on neutral
c. verify that the volt meter reads between 110 and 120 VAC
4.
Using a volt meter test between L2 and neutral.
a. place one lead on L2
b. place the other lead on the neutral
c. verify that the volt meter reads between 110 and 120 VAC
5.
Using a volt meter test between L1 and L2.
a. place one lead on L1
b. place the other lead on L2
c. verify that the volt meter reads between 220 and 240 VAC
6.
At the AC Load Center, set all breakers, except the rectifier breakers, to ON.
Step
Action
1.
In the front equipment compartment, re-attach the AC load center front
panel.
2.
In the side splice compartment, re-attach the AC cover plate over the AC
entry tray.
Summary of Contents for ODC-10
Page 1: ...Calix ODC 80 Installation Guide July 2003 Part 220 00029 Rev 11...
Page 2: ......
Page 6: ......
Page 7: ...1 Chapter Before You Begin Installing the ODC 80...
Page 8: ......
Page 23: ...2 Chapter Placing the ODC 80 on a Pad...
Page 24: ......
Page 30: ......
Page 31: ...3 Chapter Installing Power Subscriber Cables and Equipment...
Page 32: ......
Page 74: ......
Page 75: ...4 Chapter Maintaining and Troubleshooting the ODC 80...
Page 76: ......
Page 80: ......
Page 92: ......
Page 103: ...5 Chapter Reference...
Page 104: ......
Page 106: ......