background image

10

Temperature adjustment

Set the desired recirculation system temperature by turning the adjustment knob. The graduated 
scale shows the temperatures at which the indicator can be set. A valve temperature setting at about 
10°F (5°C) higher than the water temperature at the valve inlet is recommended, accounting for heat 
losses along the line, to limit the head required at the recirculation pump. Be sure this is the minimum 
flow rate at the mixing valves in the central heating system.

Adjustment locking

After adjusting the temperature, the setting can be locked at the desired value using the adjustment 
knob. Unscrew the locking screw at the top of the adjustment knob, remove the knob and then 
put it back on so that the internal groove couples with the protrusion on the knob holder nut. When 
this block is used, the reference of the indication of the temperature values on the knob is lost. To 
restore it, completely unscrew the lcoking screw. Reposition the knob on MAX value. Tighten the 
locking screw.

Summary of Contents for ThermoSetter 116 Series

Page 1: ...actuator disinfection function models w and w o temperature gauge w and w o check valve connections NPT female 1166 series ThermoSetter w disinfection function by pass cartridge 140 F 60 models w and...

Page 2: ...ubricity so that care must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury WARNING System fluids are under pressure...

Page 3: ...la temp rature peuvent tre dangereux tre s r que la pression a t r duite z ro et la temp rature du syst me est inf rieure 100 F 38 C Le non respect de ces instructions peut entra ner des dommages mat...

Page 4: ...C Factory setting 130 F 55 C Disinfection temperature 1162xx series 160 F 70 C 1166xx series 140 F 60 C Closing temperature 1162xx series 170 F 75 C 1166xx series 150 F 65 C Max inlet temperature 195...

Page 5: ...using flow and thus temperature to increase back to the set temperature as shown in curve 1 If temperature exceeds the set point the plug stays in the minimum closed position as shown in curve 2 The b...

Page 6: ...ath up until the by pass temperature is attained shown in curve 3 If the temperature continues rising beyond this point the flow is reduced through the by pass port to allow thermal balancing even dur...

Page 7: ...case the minimum head loss is produced during this thermal disinfection process Installation Before installing the ThermoSetter flush the pipes to make sure that impurities in system will not interfe...

Page 8: ...NPT F 4 5 7 16 3 1 7 0 75 116150A C NPT F 4 5 5 8 3 1 5 0 70 116151A C NPT F 4 5 5 8 3 1 5 0 70 Models with check valve tail piece C end to end dimension is B with integral outlet temperature gauge B...

Page 9: ...mal working conditions T 10 F Determine the pressure drop across the valve by selecting the branch design GPM on the graph X axis draw a vertical line up to the design curve then go across to the Y ax...

Page 10: ...e this is the minimum flow rate at the mixing valves in the central heating system Adjustment locking After adjusting the temperature the setting can be locked at the desired value using the adjustmen...

Page 11: ...ion control cartridge can be removed from the valve body for periodic inspection cleaning or replacement Innsulation shell The ThermoSetter thermal balancing valve can be supplied with an optional ins...

Page 12: ...0 F 130 F 140 F 120 F NOTE Do not set at temperatures 120 F if anti scald valves are not installed at the xtures Hot water recirculation with thermal balancing valves 230 V 50 Hz THERMAL DISINFECTION...