CALEFFI SATK32107 Series Instructions Manual Download Page 8

8

Electrical installation

1

2

3

4

5

6

7

Formato A3

FOGLIO 2 

Centralina SATK II

SCALA 

DISEGNATO: D.V.
FILE: G095_02A6

DATA:  07/12/2016

CODICE: CRAE030

FINITURA: 

OGGETTO

MATERIALE: 

 

REV.N. 

REV. N. 1

GRADO RUGOSITA' SUPERFICI

RETTIFICA
PRESSOFUSIONE

PIALLATURA
TORNITURA

3-6

0,4-3

1,6-3

0,1-0,8

FUSI O STAMPATI

+/- 0,5%

+/- 2°

+/- 10%

LAVORATI

ANGOLI

0 - 80

> 80

+/- 30'

+/- 0,1

+/- 0,25

TOLLERANZA GENERALE

SPESSORE

LUNGH. O Ø

ANGOLI

VIETATA LA RIPRODUZIONE

NON RILEVARE LE QUOTE DAL DISEGNO

EXP PORT OTS

RT

PREPAID

AUX

RS-485 BUS

8

Connection to the electric supply

The appliance is supplied with an electric supply cable which is not fitted 

with a plug.

The appliance should be electrically connected to a 230 V    (AC) single-

phase + earth mains supply using the three-wire cable marked with the 

label as specified aside, observing the LIVE (L) - NEUTRAL (N) polarities 

and the earth connection. This line must be connected to a circuit breaker 

device.

To extend the cable if necessary, use a flexible cable suitable for kitchen 

and heating appliances and for home, kitchen and office installations, also 

in humid environments subject to medium levels of mechanical stress (e.g. 

H05V2V2-F: Uo/U 300/500 V). Cable minimum cross-section 3 x 0,75 mm

2

.

Make sure that the electrical system can withstand the maximum power 

consumption of the appliance, with particular emphasis on the cross-

section of the wires. If you have any doubts, contact a qualified technician 

to request a thorough check of the electrical system.

Electrical safety of the appliance is only achieved when it is correctly 

connected to an effective earthing system, constructed as specified in 

current safety regulations. This is a compulsory safety requirement. 

Observe the applicable regulations in force in the country of installation.

Use the cable pathway provided, as shown in figure 1.

Optional electric connections

The controller has a door on the front providing access to terminal boards 

for optional wiring (see chapter “circuit board details”). The connections in 

question are all low voltage or potential-free. Any wiring must be directed 

toward the exterior of the HIU, using the pathways provided in the insulation 

and on the frame. All the low voltage lines must be routed through a single 

dedicated cable raceway, using the pathway that is not used for the electric 

supply cable (see figure 2), so that they are separate from the 230 V electric 

cables. Any other high voltage connection, e.g. the one from the auxilliary 

microswitch (see pages 13 and 16) must pass through the same cable 

pathway used for the main electric supply.

Remote user interface connection

The HIU user interface has the dual function of control device and room 

thermostat. The remote user interface can be installed on board the HIU 

or in the room in a position where the temperature measurements will be 

of significance for control of the heating function (in a heated room in a 

position where the temperature read by the thermostat is not affected by 

any nearby heat sources).

Installation on board the HIU

If the remote user interface is fitted in the dedicated location on the cover of 

the HIU, the thermostat function must be disabled (in this case an external 

thermostat must be used, as described in the next section). The adjacent 

figures show how to install the remote control unit:

-  Feed the cable from the regulator through the hole in the cover (3);

-  Feed the cable from the regulator through the rear of the interface (4);

-  Connect the two wires to the terminals on the electronic circuit board (the 

cable is not polarised) (5);

-  Close the interface and position it in its housing on the cover (6), (7);

-  If necessary, secure the interface from inside the cover by means of the 

supplied pair of self tapping screws, spacers, and washers;

-  Plug in the connector (8).

The thermostat function is enabled by default (refer to the remote 

control user manual for disabling it).

Installation in the room

Use the cable outlet provided for connection of the remote user interface 
to the electronic circuit board.
The chrono-thermostat function has to be enabled through the remote 
control. Refer to the dedicated user manual for the procedure.

Use of an external room thermostat

An external room thermostat, if installed, must necessarily be with 

potential-free contact

.

The external thermostat has to be connected to the terminals “RT” shown 
in the adjacent figure. The terminals can be accessed by removing the door 
on the HIU electronic regulator (see page 19).
In case the thermostat function of the remote user interface is enabled, 
any external thermostat will work in parallel (management of different 
temperature zones). Alternatively, when the thermostat function of the 
remote user interface is disabled, the interface can be used to define 
the hourly programming of the space heating function for all thermostats 
connected to the terminals “RT”.

Refer to the user interface dedicated manual.

Summary of Contents for SATK32107 Series

Page 1: ...stallation 5 Hydraulic components and diagram 4 Dimensions Technical specifications 3 Safety instructions 2 DHW function Comfort functions Primary flow rate limitation Circulator curves and setting Au...

Page 2: ...lled and in compliance with current legislation 5 The device must always be earthed before it is connected to the electric supply If the device must be removed always disconnect the earth connection a...

Page 3: ...nimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V AC 10 50Hz Max power consumption 80 W Protection class IP 40 Pump UPM3 15 70 Actuators 24 V stepper motor Probes...

Page 4: ...9 Return temperature probe 10 Pressure gauge 11 Safety thermostat 12 130 mm heat meter template 13 1 4 F pressure test port 14 Connection for M10x1 heat meter return probe 15 Primary drain cock 16 Con...

Page 5: ...aulic installation Preliminary operations installation without template After having established the point of installation of the appliance perform the following operations Mark the holes required for...

Page 6: ...m in order to remove any residue or impurities that could endanger correct operation of the HIU In order to facilitate these operations a manual bypass flushing valve is available code 789110 N B In t...

Page 7: ...pipe To tighten the nuts apply maximum tightening torque of 25 Nm taking account of the indications of the heat meter manufacturer install the flow probe in the M10 pocket B Please refer to the heat m...

Page 8: ...ctric supply Remote user interface connection The HIU user interface has the dual function of control device and room thermostat The remote user interface can be installed on board the HIU or in the r...

Page 9: ...to the HIU and check for the presence of any error signal If there is any eliminate the fault indicated see page 18 and proceed with setting the set point of the domestic water and heating cycles pro...

Page 10: ...rature compensation day night Daytime night time setting temp Temperature display ambient set point probes prog Heating hourly programming and comfort function reset Resettable error reset floor slab...

Page 11: ...on day night Daytime night time setting temp Temperature display ambient set point probes prog Heating hourly programming and comfort function reset Resettable error reset floor slab heating function...

Page 12: ...e the modulating valve is opened gradually until the set point temperature is reached if the return temperature is lower than or equal to the set limit value In case this condition is not met the flow...

Page 13: ...es is 42 60 C while the range of possible return temperatures is 15 45 C if these set points cannot be changed you must set parameter t07 to value 0 in the technical menu see access to technical menu...

Page 14: ...DHW production The flow rate limitation is imposed by controlling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possib...

Page 15: ...two seconds and then press the same key repeatedly until reaching the required characteristic refer to the figure below Having identified the required characteristic head flow rate chart shown below w...

Page 16: ...ow pump normally OFF The contact must be closed if any HIU function is active DHW production heating pre heating Parameter t05 must be set to 1 2 4 7 This value t05 7 is set by default example 2 Disti...

Page 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Page 18: ...m an external device indicating zero credit Corrective action Check the electrical connections or in the case of zero credit top up the external device contact the service supplier Heat interface unit...

Page 19: ...RT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT T ORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT T LAVORATI ANGOLI 30 TOLLERANZA GENERALE ANGOLI EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OU...

Page 20: ...ween 0 9 and 1 2 bar Restore the pressure value if necessary Re open the shut off valves and restore secondary circuit pressure to a value between 1 3 and 1 7 bar Check for the absence of any liquid d...

Page 21: ...tuator see previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correc...

Page 22: ...ature set point disable the function primary circuit strainer of the HIU clogged call qualified personnel to have it serviced exchanger partly clogged call qualified personnel to have it serviced modu...

Page 23: ...in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not worki...

Page 24: ...ernal sensor prepayment auxilliary microswitch Modbus if required been carried out 15 Has the remote user interface been configured for installation on board thermostat function disabled inside the ap...