background image

Maintenance

In service tests should be conducted regularly to monitor and record the performance of the valve. 
Deterioration in performance can indicate the need for servicing of the valve and/or water supply. 
If, during these tests, the mixed water temperature has changed significantly from the previous 
test results, record the change before re-adjusting the mixed water temperature. If the final mixed 
water temperature is greater than the permitted values, Verify details quoted in the Installation and 
Commissioning sections of this manual and that service work is required.

The following actions are recommended at least every 12 months, or more frequently if the need 
arises, and that the following steps are checked to maintain optimum valve performance.

Use the folllowing recommended procedure:
1) On the Caleffi SinkMixer valves, the inlet strainers on both the hot and cold water 
  inlet ports can be removed for cleaning by unscrewing the inlet union nut on the cold port and,
  with a screw driver, pop strainer out of the hot port.
2) If service is required, cleaning and de-scale as needed, or replace these check valves, see page
  6 for code numbers.

Once the above servicing is performed follow the commissioning details in the previous section 
ensuring that a suitably accurate thermometer is used.

Should the valve still not function correctly, it may be necessary to replace the valve entirely. 
Contact Caleffi Technical Support for details and advice.

Spare parts

Spare parts are available for the Caleffi SinkMixer valves, see page 6.

11

strainers

check valves

check valve 

holder

Summary of Contents for 521201AP

Page 1: ...um flow rate for optimum operation 2 3 gpm 8 5 l min Certifications 1 ASSE 1070 CSA B125 3 2012 certified by ICC ES file PMG 1358 2 NSF ANSI 372 2011 Drinking Water Systems Components Lead Content Red...

Page 2: ...t such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions When...

Page 3: ...tpasinstall mis en service et entretenu correctement selon les instructions contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer...

Page 4: ...water in such a way as to maintain constant set temperature of the mixed water at the outlet A thermostatic element is fully immersed into the mixed water This element then contracts or expands causin...

Page 5: ...and under counter applications in accordance with installation rules and indications specified in ASSE 1070 standards The system must be sized taking into account the current legislation with regard...

Page 6: ...ked at any need Hand changes are forbidden Questodocumentonon daritenersiimpegnativo Ciriserviamoildirittodimodificareinostriprodotti diapportaremiglioramentitecniciedisvilupparliulteriormente Attenzi...

Page 7: ...or associated fittings It is essential that when the installation is designed and or installed all current legislation is noted e g the maximum distance from the outlet of the valve to any terminal fi...

Page 8: ...Installation diagram COLD HOT 8 Point of use 521201A 521201AP...

Page 9: ...to simultaneous demand 5 Once the supply temperatures are stabilized and the normal operating conditions are established the valve can be commissioned The temperature setting can be adjusted by with...

Page 10: ...D C O L D H O T M I X Remove 1 4 hex key from mounting bracket Remove white cap Adjust temperature setting with 1 4 hex key After adjustment lock the temperature with locking nut Replace cap and store...

Page 11: ...e following steps are checked to maintain optimum valve performance Use the folllowing recommended procedure 1 On the Caleffi SinkMixer valves the inlet strainers on both the hot and cold water inlet...

Page 12: ...Starvation of the water supplies at the valve inlets c Incorrect commissioning of the valve Restore inlet conditions within the limits of the valve Erratic flow of water from the valve a Insufficient...