Thermal shutoff

In the event of a failure of the hot supply port, the piston closes the cold supply port. Similarly, if 
the cold water supply fails, the piston closes the hot supply port. The 

thermostatic mixing

 valve 

requires a minimum temperature differential from hot inlet to mixed water outlet of 18°F (10°C) to 
ensure the correct operation of the thermal shutoff feature.

4

Operating principle

The thermostatic mixing valve mixes hot and cold water in such a way as to maintain constant 
set temperature of the mixed water at the outlet. A thermostatic element is fully immersed into the 
mixed water. This element then contracts or expands causing movement of the piston, closing 
either the hot or cold inlets, regulating the flow rates entering the valve. If there are variations of 
temperature or pressure at the inlets, the internal element automatically reacts to restore the original 
temperature setting. In the event of a failure of either the hot or cold supply, the piston will shut off, 
stopping water discharging from the mixed water outlet. 

COLD INLET

HOT INLET

MIX OUTLET

COLD OUTLET

Summary of Contents for 521201AP

Page 1: ...um flow rate for optimum operation 2 3 gpm 8 5 l min Certifications 1 ASSE 1070 CSA B125 3 2012 certified by ICC ES file PMG 1358 2 NSF ANSI 372 2011 Drinking Water Systems Components Lead Content Red...

Page 2: ...t such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions When...

Page 3: ...tpasinstall mis en service et entretenu correctement selon les instructions contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer...

Page 4: ...water in such a way as to maintain constant set temperature of the mixed water at the outlet A thermostatic element is fully immersed into the mixed water This element then contracts or expands causin...

Page 5: ...and under counter applications in accordance with installation rules and indications specified in ASSE 1070 standards The system must be sized taking into account the current legislation with regard...

Page 6: ...ked at any need Hand changes are forbidden Questodocumentonon daritenersiimpegnativo Ciriserviamoildirittodimodificareinostriprodotti diapportaremiglioramentitecniciedisvilupparliulteriormente Attenzi...

Page 7: ...or associated fittings It is essential that when the installation is designed and or installed all current legislation is noted e g the maximum distance from the outlet of the valve to any terminal fi...

Page 8: ...Installation diagram COLD HOT 8 Point of use 521201A 521201AP...

Page 9: ...to simultaneous demand 5 Once the supply temperatures are stabilized and the normal operating conditions are established the valve can be commissioned The temperature setting can be adjusted by with...

Page 10: ...D C O L D H O T M I X Remove 1 4 hex key from mounting bracket Remove white cap Adjust temperature setting with 1 4 hex key After adjustment lock the temperature with locking nut Replace cap and store...

Page 11: ...e following steps are checked to maintain optimum valve performance Use the folllowing recommended procedure 1 On the Caleffi SinkMixer valves the inlet strainers on both the hot and cold water inlet...

Page 12: ...Starvation of the water supplies at the valve inlets c Incorrect commissioning of the valve Restore inlet conditions within the limits of the valve Erratic flow of water from the valve a Insufficient...