CMN / CMN1 / CMN2:
Collector minimum temp.
Adjustment range:
50.0 ... 190.0 °F
[10.0 ... 90.0 °C]
in steps o
f 1.0 °F [0.5
°C
]
Factory setting:
50.0 °F [10.0 °C]
Collector minimum limitation option
OCN / OCN1 / OCN2:
Collector minimum limitation
Adjustment range: OFF / ON
Factory setting: OFF
If the collector minimum limitation option is activated,
the pump (R1 / R2) is only switched on if the adjustable
collector minimum temperature is exceeded. The minimum
temperature prevents the pump from being switched on too
often at low collector temperatures. A fixed hysteresis of
10 °Ra [5 °K] is set for this function
If the collector minimum limitation is active, (flashing) is
shown on the display.
Antifreeze option
OCF / OCF1 / OCF2:
Antifreeze function
Adjustment range: OFF / ON
Factory setting: OFF
The antifreeze function activates the loading circuit between
the collector and the tank when the temperature falls below
the adjusted antifreeze temperature. This will protect the
fluid against freezing or coagulating. If the adjusted antifreeze
temperature is exceeded by 2 °Ra [1 K], the loading circuit
will be deactivated.
When the antifreeze function is activated,
is shown on
the display. If the antifreeze function is active,
and
(flashing) are shown on the display.
Note:
Since this function uses the limited heat quantity
of the tank, the antifreeze function should be
used in regions with few days of temperatures
around the freezing point.
The antifreeze function will be suppressed if the
tank temperature falls below 40 °F [5 °C] in
order to protect the tank from frost damage.
CFR / CFR1 / CFR2:
Antifreeze temperature
Adjustment range:
-40.0 ... +50.0 °F
[-40.0 ... +10.0 °C]
in steps o
f 1 °F [0.5
°C
]
Factory setting:
40.0 °F [4.0 °C]
Tank cooling function
When the tank cooling function is activated, the controller
aims to cool down the tank during the night in order to
prepare it for solar loading on the following day.
If the adjusted maximum tank temperature (S MX / S1MX)
is exceeded and the collector temperature falls below the
tank temperature, the system will be reactivated in order
to cool down the tank. Cooling will continue until the tank
temperature has fallen below the adjusted maximum tank
temperature (S MX / S1MX) again. A fixed hysteresis of
4 °Ra [2 K] is set for this function.
Reference threshold temperature differences for the tank
cooling function are DT O and DT F.
If no DHW consumption is expected for a longer period
of time, the additional holiday cooling option OHOL can
be activated in order to extend the tank cooling function.
The adjustable temperature THOL then replaces the
maximum tank temperature (S MX / S1MX) as a switch-off
temperature for the tank cooling function.
When the holiday cooling function is activated
,
and
(flashing) are shown on the display.
While the holiday cooling function is active,
,
and
(flashing) are shown on the display.
OSTC:
Tank cooling option
Adjustment range: OFF / ON
Factory setting: OFF
THOL:
Holiday cooling temperature
Adjustment range:
70 ... 175 °F
[20 ... 80 °C]
in steps of 1 °F [1 °C]
Factory setting:
110 °F [40 °C]
OHOL:
Holiday cooling option
Adjustment range: OFF / ON
Factory setting: OFF
Note:
If OSTC or OCF is active, the collector minimum
function will be overridden. In that case, the
collector temperature may fall below CMN.